Product Description
RPW404P-FTL Room control module
Room control module with temperature sensor with SolarRadio technology,
integrated bidirectional EnOcean wireless interface and algorithm for
self-learning of utilization time profiles/heating profiles in rooms.
Application
Solar-powered, self-learning room control module with LCD and smart commu-
nication management.
for measuring room temperature, independent generation of utilization time
profiles and their continuous dynamic adjustment/optimization and for wireless
transmission of measured values.
Operating elements for manually changing the comfort mode or economy mode
status to adjust the room setpoint.
Together with the MD15-FTL radio actuator, the RPW404P-FTL room control
module constitutes a functional unit for easy room temperature control.
The following EnOcean Equipment Profiles (EEP) are supported:
■EEP D2-10-30 *
* You can find information about the protocol description on the EnOcean
Technology website http://www.enocean-alliance.org/en/enocean_standard/

APage 2 / 30
Product DescriptionRPW404P-FTL
Datasheet 1.10-65.030-01-EN Issue 2017-04-03
Content Page
Important Information on Product Safety ....................................................................................................... 3
Item..................................................................................................................................................................... 5
Technical Data .................................................................................................................................................. 5
Dimensions ....................................................................................................................................................... 6
Radio Interface.................................................................................................................................................. 6
Installation ......................................................................................................................................................... 7
General installation instructions ........................................................................................................................ 7
Controls and functional components.............................................................................................................. 9
Indicators on the display................................................................................................................................ 10
Commissioning ............................................................................................................................................... 11
Switching the device on/off ............................................................................................................................. 11
“Test installation location” function.................................................................................................................. 12
Teaching in the MD15-FTL radio partner on the RPW404P-FTL.................................................................... 13
Mounting .......................................................................................................................................................... 14
Removal ........................................................................................................................................................... 16
Operating level ................................................................................................................................................ 16
Setting the initial display.................................................................................................................................. 16
Setting the setpoint ......................................................................................................................................... 16
Manually switching between comfort and economy mode.............................................................................. 17
Automatically switching between comfort and economy mode.......................................................................18
Closing the valve manually ............................................................................................................................. 18
Restoring defaults ........................................................................................................................................... 18
Menu level........................................................................................................................................................ 19
Config menu.................................................................................................................................................... 19
Setting vacation mode..................................................................................................................................... 19
Setting the time and date ................................................................................................................................ 20
Setting the 12/24 hour display......................................................................................................................... 21
Switching the temperature scale °C/°F ........................................................................................................... 22
Info menu ........................................................................................................................................................ 23
Set setpoints in Setpoint menu ....................................................................................................................... 24
Service level .................................................................................................................................................... 24
Messages ......................................................................................................................................................... 28
Status messages............................................................................................................................................. 28
Malfunction messages .................................................................................................................................... 30

A
Page 3 / 30
Datasheet 1.10-65.030-01-EN
RPW404P-FTLProduct Description
Issue 2017-04-03
Important Information on Product Safety
Safety instructions
This data sheet contains information on installing and commissioning the product “RPW404P-FTL”.
Read this product description prior to installation, commissioning or operation. No previous special
knowledge is required to commission and operate this product.
If you have any questions that are not resolved by this data sheet, you can obtain further information
from the supplier or manufacturer.
If the product is not used in accordance with this data sheet, intended use could be impaired.
Unauthorized conversion and modifications to the device are not permitted for safety reasons and will
result in the loss of all claims against the manufacturer.
The applicable local regulations must be observed when installing and using the device.
Meaning of the symbols
WARNING
Indicates a hazard of medium risk which can result in death or severe bodily injury if it is not avoided.
!CAUTION
Indicates a hazard of medium risk which can result in material damage or malfunctions if it is not
avoided.
NOTE
Indicates additional information that can simplify the work with the product for you.
Notes on disposal
In accordance with the applicable laws and directives of the European Union countries, the product
should not be disposed of with household waste. This ensures environmental protection and
sustainable recycling or raw materials.
Private users should contact their local retailer or their local authority for information regarding
environmentally safe recycling of old appliances.
Commercial users should contact their supplier and observe the conditions of the purchase
agreement. This device may not be disposed of together with other commercial waste.

APage 4 / 30
Product DescriptionRPW404P-FTL
Datasheet 1.10-65.030-01-EN Issue 2017-04-03
Care instructions
The room control module should be cleaned with due care. Moisture must not be allowed to enter the
housing.
!CAUTION
Housing with a sensitive surface.
Shocks and abrasive cleaning materials can lead to scratches and a dulling of the surface.
Remove the protective foil only after you have finished all work.
Do not use any abrasive cleaning materials or cleaning products to clean the device. Clean the
housing with a moist, lint-free cloth.
NOTE
This device contains a humidity sensor. This humidity sensor is influenced by chemical substances
in the air that can be produced, for example, due to the evaporation of cleaning and care products
used to clean the room.
NOTE
The operating modes described here only apply for the self-learning room control consisting of:
- MD15-FTL radio actuator and
- RPW404P-FTL room control module.
Other radio partners, e.g. gateways, can generate other functions.
Comfort mode: Operating mode for a room that is in use (usage status: “Present”). The setpoint for
comfort mode is used as the basis for control.
Economy mode: Energy-saving operating mode (usage status: “Absent”) for a room that is not in
use. The setpoint for economy mode is used as the basis for control.

A
Page 5 / 30
Datasheet 1.10-65.030-01-EN
RPW404P-FTLProduct Description
Issue 2017-04-03
Item
Technical Data
RPW404P-FTL Room control module with temperature sensor with SolarRadio technology, inte-
grated bidirectional EnOcean wireless interface.
Automatic determination of the utilization time profile/heating profile in the room for
automatic control of comfort mode and economy mode.
For self-learning, energy self-sufficient and occupation-dependent control of the
room temperature in conjunction with the MD15-FTL radio actuator.
Nominal voltage Dual power supply consisting of a solar cell and an internal energy stor-
age unit with priority management
additional internal energy source uses 2 3.6 V AA lithium batteries
Measured quantity Room temperature in homes or offices
Measuring system Temperature sensor:
Occupancy sensor:
- Integrated digital sensor
- Integrated PIR (“Passive infrared”) sensor
Measuring range 0 °C to 50 °C
Measuring tolerance Typically ±0.3 K
Display LCD display:
■room temperature, date or time, as selected
■Status indicators
Controls ■Occupancy button: manually switch between comfort
mode/economy mode
■Directional button up: increase value
■Directional button down: reduce value
■Shift button: for selecting menus or displays
Interfaces EnOcean® radio interface:
■Radiogram: EnOcean radiogram, bidirectional
■Frequency: 868.3 MHz
■Duty cycle: < 1%
■Cyclic transmission/reception intervals
Communication cycle 10 min
Transmission power < 10 mW
Illumination strength Min. 150 lux recommended
Operating range Radio:
Occupancy sensor:
Approx. 30 m in buildings (depending on building
structure)
Approx. 10 m
Housing Plastic housing, RAL 9010 (pure white), 7001
Other colors on request
Protection class III
Degree of protection IP30
Ambient temperature 0..50 °C
Ambient humidity During operation: 20..85% r.h., non-condensing
Out of operation: 5..90% r.h., non-condensing
Mounting Flexible mounting using screws or adhesive

APage 6 / 30
Product DescriptionRPW404P-FTL
Datasheet 1.10-65.030-01-EN Issue 2017-04-03
Dimensions
Radio Interface
The radio communication with the radio partner is cyclical, bidirectional and includes an intelligent
synchronization process.
If the radio communication between the room control module and the radio partner is interrupted, an
internal resynchronization algorithm starts automatically.
Radio interference is indicated on the screen by corresponding icons (see page 28).
!CAUTION
This product uses only EnOcean wireless telegrams.
Only devices that support the EncOcean radio standard can be used as radio partners.
Maintenance Maintenance-free
Weight 0.22 kg
Dimensions WxHxD in mm: 90 x 153.7 x 26.7
91,6
90,0
10,5
9,2
19,74,1
153,7
7,0
R 30,0
2,5

A
Page 7 / 30
Datasheet 1.10-65.030-01-EN
RPW404P-FTLProduct Description
Issue 2017-04-03
Installation
!CAUTION
This product description describes the specific settings and functions of the RPW404P-FTL room
control module. In addition to these instructions, the product description of the radio partner must also
be observed.
General installation instructions
It is not always possible to freely select the installation location of devices which communicate
wirelessly, as radio data transmission is influenced to a greater or lesser extent by structural or spatial
factors.
In order to establish operational and reliable communication paths, the following aspects must be
considered before and during planning:
■Structural factors restrict the transmission ranges which can be reached. Building materials and
screening elements (e.g. suspended ceiling elements, installation shafts, fire doors, etc.) must be
taken into consideration during planning.
!CAUTION
Elevated humidity increases natural signal damping.
NOTE
Recommendation: Plan radio paths horizontally on a single level with max. 30 m between the
trasmitting and receiving modules.
■Designed only for use in rooms.
■Observe minimum distances to potential sources of interference.
- Min. 0.5 m to high-frequency sources of interference (such as microwaves, transformers or
computers)
- Min. 0.5 m to transmitters of other radio systems (such as a cordless telephone or headphones)
- Min. 0.1 m to metal and door frames
■Minimize the effect of wall thickness (for example partition walls or room dividers) by ensuring that
the radio signal passes through the walls at as close to a right angle as possible.
■Do not select installation locations in the radio shadow of screening building parts/structures No
direct reception possible.
■Where the device is installed at the limits of reliability, change the position of the transmitter/
receiver slightly if possible (reduce overlapping effects of radio waves).

APage 8 / 30
Product DescriptionRPW404P-FTL
Datasheet 1.10-65.030-01-EN Issue 2017-04-03
■The room control module should be installed in a location where it is exposed to the air circulation
in the room so that it can quickly and accurately record the room temperature.
■As a result of the autonomous operation and wireless installation of RPW404P-FTL, the selected
installation location can be changed and optimized at any time without additional effort.
The installation location must have sufficient lighting; using the device in unlit rooms (such as interior
kitchens/bathrooms) shortens long-term functionality.
The solar cell is optimized for indoor use and it works particularly efficiently with diffuse lighting.
!CAUTION
Prolonged illumination at high intensities, e.g.
- direct sunlight or
- artificial light (such as halogen emitters) can cause damage to the solar cell.
1,5m
= 0,5m
>
150 Lux

A
Page 9 / 30
Datasheet 1.10-65.030-01-EN
RPW404P-FTLProduct Description
Issue 2017-04-03
Controls and functional components
Item Designation Explanation
01 Display Displays information regarding the current status
02 Occupancy sensor Detects presence/absence for the utilization time profile
03 Solar cell Generates energy for the room control module
04 Directional button up To set: increase value
05 Magnetic contact
(below the housing)
For selecting the service level, see p. 24
06 Directional button
down
To set: reduce value
07 Shift button For selecting the display or menus
08 Occupancy button - Switching between comfort mode/economy mode,
see page17
- For switching the RPW404P-FTL on/off ( ith the setting
button); see page 11
- For setting functions
09 Setting button - Switches the room control module on (together with the
occupancy button), see page 11
- Starts the login process; see page 13
- Resets the room control module to factory settings,
see page 18
10 Service connection
(underside)
For authorized service technicians only
01
02
03
04
05
06
07
08 09
10

APage 10 / 30
Product DescriptionRPW404P-FTL
Datasheet 1.10-65.030-01-EN Issue 2017-04-03
Indicators on the display
Item Icon/display Explanation
01 Time The information field displays the time (HH:mm)
02 Information field Display of the room temperature, date, time (= initial display, can be
configured) or messages
03 Windows Rapid temperature drop detected
04 Message Status or malfunction messages present
05 Battery Room control module energy storage unit charging state < 30%
06 Actuators Teach-in-modes for actuators active
07 Display lock Buttons are not responsive
08 Occupancy Occupancy sensor is active (test installation location), detected pres-
ence/absence and vacation mode
09 Auto Learned utilization time profile is active, automatic mode
10 Bars Displays the field strength quality of the receiving wireless signal,
only in the Info menu
11 Gateway Remote access via the EnOcean system gateway, teach-in-modes
for gateway active
12 Antenna Status of the radio connection
13 Vacation mode This icon appears on the display when vacation mode is activated
14 Sun The solar cell is active (test installation location).
Summer mode is active
15 PM Afternoon time, if the 12 hour display is activated
16 Fahrenheit Information field displays the temperature in degrees Fahrenheit (°F)
17 Degrees Celsius Information field displays the temperature in degrees Celsius (°C)
01
02
03
04
05 06 07 08 09
10
11
12
13
14
16
17
15
Inhaltsverzeichnis