KNX GIRA 2015 00 Bedienungsanleitung

Dimming actuator, 4-gang
Table of Contents
1 Safety instructions.............................................................................................................3
2 Device components...........................................................................................................3
3 Function ............................................................................................................................4
4 Operation ..........................................................................................................................6
5 Information for electrically skilled persons ........................................................................8
5.1 Mounting and electrical connection........................................................................ 8
5.2 Commissioning .................................................................................................... 10
6 Technical data.................................................................................................................11
7 Troubleshooting ..............................................................................................................13
8 Accessories.....................................................................................................................16
9 Warranty..........................................................................................................................16
2 / 16
82402732 07.06.2021

1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire or property damage possible. Please read and follow manual
fully.
Danger of electric shock. Always disconnect before carrying out work on the device
or load. In so doing, take all the circuit breakers into account, which support danger-
ous voltages to the device and or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage
because mains potential even is applied on the load when the output is switched off.
Always disconnect before carrying out work on the device or load. To do so, switch
off all associated circuit breakers.
Risk of destruction of the dimmer and load if the set operating mode and load type do
not match. Set the correct dimming principle before connecting or exchanging the
load.
Fire hazard. For operation with inductive transformers, each transformer must be
fused on the primary side in accordance with the manufacturer's instructions. Only
safety transformers according to EN 61558-2-6 may be used.
This manual is an integral part of the product, and must remain with the end cus-
tomer.
2 Device components
Image1: Device components
(1) Button field for manual operation
(2) Programming button and LED
(3) KNX connection
(4) Status LEDs for outputs
(5) Load connections
3 / 16
82402732 07.06.2021
Dimming actuator, 4-gang

3 Function
System information
This device is a product of the KNX system and complies with the KNX directives.
Detailed technical knowledge obtained in KNX training courses is a prerequisite to
proper understanding.
The function of this device depends upon the software. Detailed information on load-
able software and attainable functionality as well as the software itself can be ob-
tained from the manufacturer´s product database.
The device can be updated. Firmware can be easily updated with the Gira ETS Ser-
vice App (additional software).
The device is KNX Data Secure capable. KNX Data Secure offers protection against
manipulation in building automation and can be configured in the ETS project. De-
tailed specialist knowledge is required. A device certificate, which is attached to the
device, is required for safe commissioning. During mounting, the device certificate
must be removed from the device and stored securely.
Planning, installation and commissioning of the device are carried out with the aid of
the ETS, version 5.7.3 and above.
– Operation in KNX system for Standard and Comfort devices.
– Operation in Gira One system for Standard devices only.
Intended use
– Switching and dimming of
incandescent lamps,
HV halogen lamps,
dimmable HV-LED lamps,
dimmable compact fluorescent lamps,
dimmable inductive transformers with LV halogen or LV LED lamps,
dimmable electronic transformers with LV halogen or LV LED lamps
– Operating in KNX systems
– Mounting on DIN rail according to EN 60715 in sub-distribution unit
If inductive or electronic transformers are connected, observe the data of the
transformer manufacturer on loads and the dimming principle.
HV-LED and compact fluorescent lamps generate high pulsed currents, when
they are operated in the leading edge phase control.
Our dimmers take into account the different electronic characteristics of most
LED lamps found on the market. However, it cannot be guaranteed that in indi-
vidual cases the desired results may not be achieved.
Product characteristics
– Outputs can be operated manually, construction site mode
4 / 16
82402732 07.06.2021
Dimming actuator, 4-gang

– Feedback in manual mode and in bus mode
– Disabling of individual outputs via bus
– Status feedback
– KNX Data Secure compatible
– Updateable with ETS Service App
Only for "Comfort" version:
– Disabling of individual outputs manually or by bus
Dimming operation characteristics
– Automatic or manual selection of the dimming principle suitable for the load
– Protected against no-load, short-circuit and overheating
– Feedback of the switching position and the dimming value
– Parameterisable switch-on and dimming behaviour
– Time functions: switch-on delay, switch-off delay, staircase lighting timer with
run-on time
– Light scene operation
– Status indicator of the outputs via LED
– Mains failure longer than approx. 5 seconds leads to switch-off of the dimming
actuator. Depending on the parameter setting, the connected load is calibrated
after mains voltage return.
– Power extension possible by means of power boosters.
Only for "Comfort" version:
– Signal in the event of a short-circuit
– Increase in output power possible through parallel switching of multiple out-
puts
– Operating hours counter
Delivery state: Construction site mode, outputs can be operated using button
field.
Flickering of the connected lamps due to undershoot of the specified minimum
load or through centralised pulses from the power stations. This does not rep-
resent any defect in the device.
Logic function characteristics
Only for "Comfort" version:
– Logic gate
– Transformer (conversion)
– Disabling element
– Comparator
– Limit value switch
5 / 16
82402732 07.06.2021
Dimming actuator, 4-gang

4 Operation
Operating elements
Image2: Operating elements
(4) Status LEDs for outputs
– on: output switched on, 1...100%
– flashes at 1 Hz: short-circuit or manual mode
– flashes at 2 Hz: overload, mains voltage failure or firmware update
(6) Button ǃ
– Manual operation
(7) LED ǃ
– on: continuous manual mode
(8) LED ON|+
– on: selected output on, 1...100%
– flashes: Firmware update
(9) Button ON|+
– Switch on/increase brightness
(10) Button OFF|−
– Switch off/reduce brightness
(11) LED OFF|−
– on: Selected output off
– flashes: Firmware update
(12) Button ALL OFF
– Switching off all outputs
Operating modes
– Bus operation: operation via push-button sensors or other bus devices
– Temporary manual control: manual control locally with keypad, automatic re-
turn to bus control
– Continuous manual mode: Exclusively manual operation on the device
No bus operation is possible in manual mode.
6 / 16
82402732 07.06.2021
Dimming actuator, 4-gang

After a bus failure and restoration the device switches to bus operation.
The manual mode can be disabled in ongoing operation via a bus telegram.
Switching on temporary manual operation mode
Operation using the button field is programmed and not disabled.
■ Press button ǃ (6) briefly.
LED ǃ (7) flashes, LED A1... (4) of the first configured output flashes.
Short-time manual operation is switched on.
After 5 s without a button actuation, the actuator returns automatically to bus
operation.
Switching off temporary manual operation mode
The device is in short-term manual mode.
■ No button-press for 5 s.
- or -
■ Press ǃ (6) button briefly as many time as necessary until the actuator
leaves the short-time manual mode.
Status LED A1... (4) no longer flash, but rather indicate the output status.
Short-time manual operation is switched off.
When switching off the manual control, the outputs, depending on the pro-
gramming, switch to the active position, e.g. forced position, logic operation.
Switching on permanent manual operation mode
Operation using the button field is programmed and not disabled.
■ Press the ǃ (6) button for at least 5 s.
LED ǃ (7) lights, LED A1... (4) of the first configured output flashes.
Continuous manual mode is switched on.
Switching off permanent manual operation mode
The device is in continuous manual mode.
■ Press the ǃ (6) button for at least 5 s.
LED ǃ (7) is off.
Continuous manual mode is switched off. Bus operation is switched on.
When switching off the manual control, the outputs, depending on the pro-
gramming, switch to the active position, e.g. forced position, logic operation.
7 / 16
82402732 07.06.2021
Dimming actuator, 4-gang

Operating the outputs
The device is in continuous or short-term manual mode.
■ Press the button ǃ (6) briefly as many times as necessary until the desired
output is selected.
The LED of the selected output A1... (4) flashes.
The LEDs ON|+ (8) and OFF|− (11) indicate the status.
■ Operate output with ON|+ (9) button or OFF|− (10) button.
Short: switch on/off.
Long: dim brighter/darker.
Release: Stop dimming.
The LEDs ON|+ (8) and OFF|− (11) indicate the status.
Short-term manual mode: After running through all of the outputs the device
exits manual mode after another brief actuation.
Switching off all outputs
The device is in continuous manual mode.
■ Press the button ALL OFF (7).
All outputs are shut off.
5 Information for electrically skilled persons
DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
5.1 Mounting and electrical connection
Connecting the device
■ Connect bus line with KNX device connection terminal observing the correct
polarity.
■ Attach the cover cap to the KNX connection as protection against hazardous
voltages.
8 / 16
82402732 07.06.2021
Dimming actuator, 4-gang

CAUTION!
Danger of destruction. 400 V are shorted when outputs switched in parallel are con-
nected to different outer phase conductors.
The device will be destroyed.
Always connect outputs switched in parallel to the same outer phase conductor.
Delivery state: The outputs can be operated with manual control.
In the "Universal" operating mode, the dimming actuator only calibrates itself again
after disconnection of the load and also after commissioning using the ETS.
Capacitive-inductive mixed load is not permitted.
For LED leading edge phase control: Connect a maximum of 2 electronic
transformers per output.
Connect 600 Watt LED lamps or compact fluorescent lamps at most per
16ampere circuit breaker. When connecting transformers, observe the data of
the transformer manufacturer.
Only for "Comfort" version:
Several dimmer outputs can be combined for dimming greater lamp loads.
Only utilise parallel-switched outputs up to 95 % each. Do not connect any
compact fluorescent lamps to dimmer outputs switched in parallel.
Observe delivery state. Before connecting parallel outputs and switching on,
program the dimming actuator with ETS to the changed output configuration.
Do not expand parallel-switched dimmer outputs with power packs.
9 / 16
82402732 07.06.2021
Dimming actuator, 4-gang

Image3: Comfort variant of the device connection with dimmer outputs switched in
parallel (connection example)
■ Connect the lamp loads according to the connection example.
5.2 Commissioning
Safe-state mode
The safe-state mode stops the execution of the loaded application program.
Only the system software of the device is still functional. ETS diagnosis func-
tions and programming of the device are possible. Manual operation is not
possible.
Activating safe-state mode
■ Switch off the bus voltage or remove the KNX device connection terminal.
■ Wait about 15 s.
■ Press and hold down the programming button.
■ Switch on the bus voltage or attach the KNX device connection terminal. Re-
lease the programming button only after the programming LED starts flashing
slowly.
The safe-state mode is activated.
10 / 16
82402732 07.06.2021
Dimming actuator, 4-gang
Dieses Handbuch passt für folgende Modelle
1
Inhaltsverzeichnis
Andere KNX Controller Handbücher

KNX
KNX GIRA 5065 00 Bedienungsanleitung

KNX
KNX Jung 2304.16 REG HE Bedienungsanleitung

KNX
KNX Module SAS-04.16 Bedienungsanleitung

KNX
KNX GIRA Bedienungsanleitung

KNX
KNX GIRA Bedienungsanleitung

KNX
KNX Berker 7531 40 18 Bedienungsanleitung

KNX
KNX GIRA Bedienungsanleitung

KNX
KNX Push Button RF+ Bedienungsanleitung

KNX
KNX Jung 230011SU Bedienungsanleitung

KNX
KNX GIRA Standard Bedienungsanleitung