Lehigh SOLITAIRE WBX-4 Bedienungsanleitung

F196
SOLITAIRE
MASTER STATION MANUAL
Lehigh Electric Products Company
6265 Hamilton Boulevard
Allentown, PA 18106
(610) 395-3386 (610) 395-7735 (FAX)
The WBX Master Station Manual V1.0

F196
TABLE OF CONTENTS
INTRODUCTION ................................................ 1
SYSTEM SPECIFICATIONS ........................................ 1
INSTALLATION ................................................. 1
FIGURE 1 - Single Circuit Feed Wiring ............................... 2
FIGURE 2 - Multi-wire Branch Circuit ............................... 3
FIGURE 3 - Low Voltage Wiring of Two Stations ...................... 3
FIGURE 4 - Low Voltage Wiring of Three Stations ...................... 4
SYSTEM OVERVIEW ............................................. 5
FIGURE 5 - The WBX 2000 Master Station Front Panel ................. 6
CONFIGURING THE STATION ..................................... 7
ALL LOCK ..................................................... 7
AREA NUMBER ................................................ 8
CHANNEL FUNCTION ........................................... 8
LOW LEVEL SETTING ........................................... 9
HIGH LEVEL SETTING ........................................... 9
FULL PRESET .................................................. 10
PARTIAL LOCK ................................................. 10
OPERATING THE STATION ....................................... 11
ACTIVATING A PRESET ......................................... 11
TEMPORARILY MODIFYING AN ACTIVE PRESET ..................... 11
MODIFYING AN ACTIVE PRESET .................................. 12
STORING A MODIFIED PRESET ................................... 13
MODIFYING A FADE TIME ....................................... 13
USING THE INFRARED CONTROLLER .............................. 14
APPENDIX A
TROUBLESHOOTING GUIDE ...................................... 15

F196
TECHNICAL INQUIRY
This equipment uses AC line voltages which could cause injury. Only individuals experienced
with electrical and electronic equipment should remove panels or attempt to service this
system. Tampering with the system could cause electrical shock.
All questions regarding this equipment should be referred to :
Lehigh Electric Products Company
6265 Hamilton Boulevard
Allentown, PA. 18106-9789
Phone: (610)395-3386
Fax: (610)395-7735
Hours: Monday - Friday 8:00AM to 5:00PM EST
WARRANTY
Subject to the terms of this paragraph, the supplier warrants its title to the products sold by it
and warrants to the Purchaser that its products are free of defects in workmanship or material
and are in conformity with applicable specifications and descriptions of the supplier. No claim
shall be maintained hereunder unless the facts giving rise to it are discovered within 12 months
after initial energizing of said equipment, and written notice received by Lehigh Electric
Products Co. within 30 days of discovery. Damage due to misuse, abuse, inadequate wiring is
not covered by this warranty. The sole and exclusive liability of the supplier, for Breach of
Warranty shall be, at its option, to replace or repair the product or part concerned F.O.B. its
factory or such place as it may designate. The warranties stated in this paragraph are exclusive
of all other warranties, written or oral, statutory, expressed or implied, none of which shall
apply to the sale of the suppliers products hereunder.

INTRODUCTION Page 1
F196
INTRODUCTION
The Lehigh Electric Products Co., Solitaire System is designed to be a self-contained
preset lighting control system, i.e. no external dimming rack is necessary. The
Solitaire is a microprocessor based unit that can control up to 2000 Watts (16.7A) of
lighting load and is available in a 4 and a 6 channel version.
SPECIFICATIONS
Model Numbers: WBX-4 (4-Channel) and WBX-6 (6-Channel)
Electrical Ratings: 120VAC, 60HZ
Maximum Lighting Load Per Channel: 800 Watts (6.7 Amps)
Maximum Total Lighting Load: 2000 Watts (16.7 Amps), total combined load of all
channels cannot exceed 2000 W
Compatible Load Types: Incandescent; use optional Power Booster for Magnetic,
Electronic Low Voltage, Fluorescent or for 277 Volt loads
Maximum Number of Channels per Station: 6(for more channels, multiple stations
may be daisy chained together, see Figure 3 and Figure 4 for low voltage wiring)
Allowable Fade Times: 0 - 59 seconds and 1 - 60 minutes
Maximum Number of Optional Remote Stations per Master Station: 3
Maximum Allowable Ambient Temperature: 40 C (104 F)
Approvals: "UL Listed to U.S. and Canadian safety standards"
INSTALLATION
Always check all applicable N.E.C. and local electrical codes before beginning
installation. The Solitaire mounts in a 4 gang, 3 1/2" deep back box. All line voltage
wiring is terminated to screw terminal blocks located on the rear of the unit. All low
voltage control wiring between master stations or optional remote stations is Class
2. The Solitaire must be grounded to an N.E.C. earth ground by connecting to the
chassis ground pigtail provided.
The Solitaire can be fed by either a single 15 - 20 Amp circuit breaker or a two-pole
15 - 20 Amp circuit breaker wired as a "multi-wire branch circuit" as defined in the
N.E.C.*. The Solitaire also requires a Neutral to power the station control
electronics.
Lighting Load Circuit Breaker Needed
12 Amps or less (1) 15 Amp
12 - 16 Amps (1) 20 Amp
up to 16.7 Amps (1) Two-pole 15 -20 Amp*
*Both circuit breakers in a multi-wire branch circuit must be on the same phase.

INSTALLATIONPage 2
F196
The following installation should only be performed by a trained electrical technician:
1. Test each load circuit for shorted or open wiring by turning the circuit on with
a standard light switch, before attaching wire to the station.
2. Fix any faulty wiring before installing the station.
3. To prevent electrical shock or equipment damage always disconnect power
before installing or servicing this station.
4. Wire the station as shown in Figure 1 for a single circuit feed and as shown in
Figure 2 for a multi-circuit branch feed.
5. For multi-stations follow the high voltage wiring shown in Figure 1 or Figure 2 for
each station. Then follow the wiring in Figure 3 or Figure 4 (depending on the
number of stations) for the system low voltage wiring.
6. The minimum high voltage wiring size is 14 gauge for up to 15 amps. 12 gauge
wire must be used for 15 amps to 20 amps.
7. Recheck all connections that were made.
8. Screw the station into the back box.
9. Gently flex the front panel overlay and position it over the station buttons and
displays.
10. Release the flex and allow the overlay tabs to enter the slots on the front panel
bezel.
jumper required
FIGURE 1
Rear View of Station
with Single Circuit Feed

INSTALLATION Page 3
F196
*NEC multi-wire branch
circuit must be on same
phase
FIGURE 2
Rear View of Station with
Multi-Wire Branch Circuit Wiring
Station 2 Station 1
Pair #1
Pair #2
Use only the following wire: Belden #9729, #1215A, #8162, #9829, #9842 or Alpha #9360.
(Two twisted/shielded pairs, RS422 quality cable.)
Wiring Chart
Station 2 Station 1 Wire Pair
pin 5 pin 3 #1
pin 6 pin 4 #1
pin 3 pin 5 #2
pin 4 pin 6 #2 FIGURE 3
Rear View of Low Voltage Wiring
for Two Master Stations

INSTALLATIONPage 4
F196

SYSTEM OVERVIEW Page 5
F196
SYSTEM OVERVIEW
The Solitaire System consists of a Solitaire Master Station and optional remote
stations. The Solitaire Master Station allows presets to be set and stored in
memory, fade times to be modified, and buttons and/or memory to be locked.
Remote stations are needed for more sophisticated functions such as activating
Presets 7 thru 18, auto-sequencing presets, combining areas, and selectively locking
remote stations.
This manual uses some common lighting terms that need to be understood.
PRESETS: A Solitaire Master Station will store up to 18 presets (lighting "looks") for
future recall. Each "look" stores user programmed levels for all of the lights
connected to the station.
CHANNELS: Each preset has either 4 or 6 channels (per master station). A channel
is one or more lights which are to be controlled together as a group. All the lights
on a channel must be wired together and connected to the channel output terminals
on the master station. For example, if Channel 5 is wired to the chandelier in your
dining area, every time Channel 5 is changed the chandelier's lighting intensity will
change.
FADE: A fade is the gradual changing of light intensity from its present level to a
new level.
FADE TIME: Each preset has a programmable fade time. A fade time is the time it
takes the lights to fade to the new level after a preset is activated. A fade time of 2
seconds up to 60 minutes can be set for each preset.
NON-DIM: Each channel can be set as either a dimmer or a non-dim. A non-dim
channel has only two lighting levels: OFF (0%) and FULL (100%). Non-dim
channels do not fade like a channel set as a dimmer. Channels configured as non-
dims will turn on or off abruptly during the fade. A channel must be set to non-dim
if it is connected to a standard fluorescent ballast, fan motor, or a receptacle. Also a
channel should be set as a non-dim if it is desired to only have a lighting fixture turn
off and on. Non-dim channels turn on or off when the fade is about 50% complete
AREA: Each station has a user programmable area number from 1 to 8. All stations
with the same area number will share the same information. The stations must have
their channels connected to different light fixtures. When a button is pressed on
station 1 the same button press will be transmitted to station 2. When optional
remote stations are present, they must be given the same area number as the
Master Station that they are controlling.

SYSTEM OVERVIEWPage 6
F196
FIGURE 5 - Solitaire Station Front Panel
DISPLAYS
7 Segment Displays: show fade time remaining, error conditions and also show
configuration information.
Channel Bargraphs: show the present lighting level for each channel and also show
configuration information.
LED's: show which Preset (1 thru 6) is active. The LED's will not light for Presets 7
thru 18, which will only be indicated at the remote preset station.
BUTTONS
Presets: activate the numbered preset (1 thru 6).
Off: fades all the lights to the “Lowest Level Settings” (see page 9) over a
preassigned fade time of 10 seconds. The Off Preset levels or its fade time
cannot be modified, when active.
Fade Time: starts "Change Fade Time Mode", where the fade time can be assigned
for each preset.
Store: saves the data to memory. In Preset Mode, it saves the channel levels on
the lights. In "Change Fade Time Mode", it saves the new fade time.
Infrared Sensor: receives infrared control signal to activate Presets 1 thru 6, OFF,
MASTER UP & DOWN from an optional Lehigh Electric hand held
infrared controller.
Master Up & Down: change all active channel levels at one time. The channel
levels will increase or decrease as long as the appropriate
master button is held down.
Channel Up & Down: individually changes the level of a channel. The channel level
will increase or decrease as long as the appropriate channel
button is held down.

CONFIGURATION Page 7
F196
CONFIGURING THE STATION
To enter Configuration Mode:
press and hold the OFF button,
then press the Preset 1 button
The first item in configure is "All
Lock". Select the items that you want to configure from those listed below. To
select another item to configure press the appropriate preset button. At any point
you may exit Configuration Mode by pressing:
1) STORE - to save any configuration 2) OFF - to exit without
changes and exit saving
ALL LOCK (BUTTON LOCK)
The display will blink the "All Lock" status as either:
AU (All Unlock Mode) - all of the buttons will function
or
AL (All Lock Mode) - all of the buttons are locked and will not
function, except to unlock the station
Press to toggle the station between locked and unlocked mode.
= locked
= unlocked