MULTI V Modular Heat Pump Product Data
2. Specifications
System Specifications
Module Specifications
HP 5
Model Name
Set ARUN050LMS0
Compressor Module ARUN050LMC0
Heat Exchanger Module ARUN050GME0
Capacity
Cooling* (Rated) kW 14.0
Btu/h 47,800
Heating* (Rated) kW 14.0
Btu/h 47,800
Heating* (Max.) kW 16.0
Btu/h 54,600
Input
Cooling* (Rated) kW 4.12
Heating* (Rated) kW 3.59
Heating* (Max.) kW 4.32
EER Based on Rated capacity 3.40
COP Based on Rated capacity 3.90
Based on Max. capacity 3.70
Power Factor Rated - 0.93
Number of maxmum connectable indoor units 10
HP 5
Model Names Compressor Module Heat Exchanger Module
ARUN050LMC0 ARUN050GME0
Casing Color Morning Gray Galvanized Steel Plate
Dimensions
(W × H × D)
Net mm 580 × 700 × 500 1,562 × 460 × 688
Shipping mm 618 × 833 × 564 1,806 × 537 × 825
Weight Net kg 70.0 89.0
Shipping kg 75.0 101.0
Compressor
Type Hermetic Motor Compressor -
Piston Displacement cm³/rev 31.6 -
Number of Revolution rev/min 3,600 -
Motor Output W 3,200 -
Starting Method DC Inverter Starting -
Oil Type FVC68D (PVE) -
Heat Exchanger - Wide Louver Plus
Fan
Type - Sirocco Fan
Motor Output × Number W - 400 × 2
Air Flow Rate (Rated) m³/min - 60
ft³/min - 2,542
Drive - Direct
External Static
Pressure
Nominal (Rated, Factory Set) mmAq(Pa) - 3 (29)
Max. mmAq(Pa) - 16 (157)
Pipe Connctions
Liquid mm(inch) Ø 9.52(3/8) to IDU Ø 12.7(1/2) to Comp. Module
Gas mm(inch) Ø 15.88(5/8) to IDU Ø 19.05(3/4) to Comp. Module
Drain mm(inch) - 25(1)
Sound Pressure
Level
Cooling (Rated) dB(A) 45 45
Heating (Rated) dB(A) 45 45
Sound Power Level dB(A) - -
Protection Devices
High pressure protection - High pressure sensor -
Compressor/Fan - Over-heat protection Fan driver overload protector
Inverter - Over-heat protection
Over-current protection -
Communication Cable (VCTF) No.×mm² 2C × 1.0 ~ 1.5 to IDU 2C × 1.0 ~ 1.5 to Comp. Module
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions :
• *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe Length and Difference of Elevation :
– Heat Exchanger Module ~ Compressor Module = 5m
– Compressor Module ~ Indoor Unit = 7.5m
– Difference of Elevation (Heat Exchanger Module~ Compressor Moduler ~ Indoor Unit) is Zero.
6. The maximum combination ratio is 130%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)