Lutron Electronics Sivoia QED Betriebsanleitung

Wiring and
Programming
Guide
045-101-12
rev A
Window Systems
Quiet Electronic Drives

Technical Support :
+44-(0)20-7702-0657
Sivoia QEDTM Quiet Electronic Drive Window System ii
Table of Contents
SYSTEM WIRING
Electronic Drive Unit (EDU) Wiring . . . . . . . . . 1.2
Single EDU Wiring . . . . . . . . . . . . . . . . . . . . . 1.3
Wire and Power Supply Specification . . . . . . . 1.4
Wiring Using Individual Power Supplies . . . . . 1.5
Multiple EDU Wiring . . . . . . . . . . . . . . . . . . . 1.7
SV-CCI-8 Wiring Detail . . . . . . . . . . . . . . . . . 1.8
Infrared Receivers . . . . . . . . . . . . . . . . . . . . 1.9
PROGRAMMING OVERVIEW
System Overview . . . . . . . . . . . . . . . . . . . . . 2.2
ADDRESSING
Addressing from Controls . . . . . . . . . . . . . . . 2.6
Addressing from the EDU . . . . . . . . . . . . . . . 2.32
SETTING LIMITS
Setting Limits from the EDU . . . . . . . . . . . . . 2.3
Setting Limits from Controls . . . . . . . . . . . . . 2.10
ASSIGNING EDUs
Assigning EDUs to Controls . . . . . . . . . . . . . . 2.15
Assigning EDUs to Multi-group IR Transmitters 2.20
PRESETS
Storing Presets . . . . . . . . . . . . . . . . . . . . . . . 2.28
Locking Presets . . . . . . . . . . . . . . . . . . . . . . 2.30
LEVEL ADJUST
Adjusting Individual Levels . . . . . . . . . . . . . . 2.24
ADVANCED PROGRAMMING
Adding Components . . . . . . . . . . . . . . . . . . . 2.31
Restoring Keypads and CCIs to
Default Settings . . . . . . . . . . . . . . . . . . . . . . 2.35
Restoring Entire System to Default Settings . . 2.38
Restoring EDU to Default Settings . . . . . . . . . 2.43
Multiple Groups with the CCI . . . . . . . . . . . . . 2.44
TROUBLESHOOTING
Troubleshooting Chart . . . . . . . . . . . . . . . . . . 3.2
For information on placement and mounting of the
EDU brackets, refer to the installation guide
included with each roller blind and curtain.

Technical Support :
+44-(0)20-7702-0657
Sivoia QEDTM Quiet Electronic Drive Window System 1.1
Sivoia QEDTM
System Wiring

Technical Support :
+44-(0)20-7702-0657
WIRING
Sivoia QEDTM Quiet Electronic Drive Window System 1.2
EDU wiring
Wiring
FUNCTION:
Sivoia QED Electronic Drive Units (EDUs) are designed to
function in four ways:
• A single EDU can be controlled individually by a keypad,
IR transmitter, or contact closure interface (CCI).
• Multiple EDUs can be linked through programming to
operate in groups and subgroups, regardless of location
on the link. EDU groupings can be changed at any time
simply by reprogramming the system.
• EDUs can be operated by larger entire-room or whole-
house lighting control systems such as Lutron’s
GRAFIK
Eye
®
, or
HomeWorks
®
systems.
• EDUs can also be operated by control systems made by
other manufacturers.
GENERAL FACTS:
• Microprocessors are contained in the EDU, keypad, CCI
and IR transmitter, allowing high-level programming
from any source.
• The keypads are low-voltage and receive their power
from the EDUs. EDUs receive their power via a 24 V~
power supply. One power supply is required per EDU.
• Keypads are wired directly to a communication link,
which connects to one or more EDUs, CCIs and keypads.
See Programming Section for more information on EDU
grouping by function.
• A contact closure input is available, when required, to
connect with an outside system. The contact closure
input wires to the EDU communication link.
PLANNING YOUR INSTALLATION:
Taking time to plan out the wiring on paper will help
enormously, especially in multiple EDU installations.
Some common questions to answer up front include:
• What are the power requirements?
Sivoia QED
system operates on 24 V~ and requires
the use of a low-voltage power supply.
The specification of the power supply is provided on
page 1.4.
Each EDU must be powered from its own power
supply.
A certified electrician should install all of the line
voltage power.
The keypads are all low-voltage and can be installed
by a low-voltage system installer.
• What size of cable is needed?
Please refer to the charts on page 1.4.
• Can I expand the system later on?
A communication link can connect up to 96 total
devices (EDUs, keypads or CCIs).
An external keypad power supply is required when
the total number of keypads and CCIs in an
installation exceeds the number of
Sivoia QED
EDUs.

single EDU wiring
Technical Support :
+44-(0)20-7702-0657
WIRING
Sivoia QEDTM Quiet Electronic Drive Window System 1.3
Wiring
Lutron Sivoia QED
seeTouch keypad
BACK
4
3
2
1
Common
12V
MUX
MUX
AC
AC
EGND
Basic Installation (Plug-In Power Supply shown)
AC
GRD
AC
.75
.75
.75"
.75"
male EDU
connector
female terminal
block
p/n 441487
To other EDUs,
keypads, CCIs
AC
Earth Ground
AC
24 V~ Power Supply
24 V~ Power Supply
LUTRON

Technical Support :
+44-(0)20-7702-0657
WIRING
Sivoia QEDTM Quiet Electronic Drive Window System 1.4
wire and power supply specifications
Wiring
WIRE TYPES
ACommunications Link
4 Conductor 1.0 mm2(#18AWG) (twisted and
shielded)
Maximum comm Link - 1220 m (4000 ft)
GRX-CBL-346S-500 may be used for the Com-
munication Link as long as the 1.0 mm
2
(18
AWG) conductors are used for the +12V and
Common
BPower Supply
3 Conductor 1.5–0.75 mm2(#16–20AWG)
POWER SUPPLY
MAXIMUM WIRE LENGTH
Keypad to Power Panel
1 keypad - 305 m (1000 ft)
2 keypads - 150 m (500 ft)
3 keypads - 90 m (300 ft)
4 keypads - 60 m (200 ft)
EDU to Panel
1.5 mm2(#16AWG) - 60 m (200 ft)
1.0 mm2(#18AWG) - 45 m (150 ft)
0.75 mm2(#20AWG) - 30 m (100 ft)
Note: Power supply wires should NOT be in the same
shielding as communication wires.
1) GENERAL REQUIREMENTS:
a) MUST have independent 3rd party certification to
Safety Isolating Transformer Standard EN61558-2-6.
b) Manufacturer MUST be able to provide documentation
supporting the 3rd party certification.
c) The CE mark alone is NOT acceptable.
d) One power supply is required per motor.
(failure to do so may cause the system to function
improperly)
2) ELECTRICAL RATINGS:
a) Input Voltage: As Appropriate, 50/60 Hz
b) Output voltage:
• Nominal: 24 Volts AC RMS
• Minimum: 22.5 Volts AC RMS at 3 Amps (Maximum
Load on Secondary)
• Maximum: 30 Volts AC RMS with No Load on
Secondary.
• 67 VA minimum at 90% Line Voltage
• 100 VA maximum
3) OUTPUT PROTECTION:
a) Fused Secondary
b) Resetable or Non-Resetable
• 3 Amps Minimum
• 5 Amps Maximum
4) GENERAL INFORMATION:
a) Depending on the weight and thickness of the fabric:
• A 50 VA rated transformer will drive approximately
5m
2(55 ft2) of fabric.
• A 100 VA rated transformer will drive approximately
10 m2(110 ft2) of fabric.

Technical Support :
+44-(0)20-7702-0657
WIRING
Sivoia QEDTM Quiet Electronic Drive Window System 1.5
wiring using individual power supplies
CCI
CCI
Sivoia QED
Keypad
Sivoia QED
Keypad
Sivoia QED EDU
IR Receiver
Sivoia QED EDU
IR Receiver
Sivoia QED EDU
IR Receiver
Sivoia QED EDU
IR Receiver
24 V~
Power
Supply
Sivoia QED EDU
IR Receiver
Sivoia QED EDU
IR Receiver
To Lighting System
(Lutron GRAFIK Eye)
2 conductors
not used
Sivoia QED Communications Link
(4 conductor, 1.0 mm
2
(18 AWG) twisted
shielded) (GRX-CBL-346S-500)
Power Cable (3 conductor)
A
B
B
A
Wiring
24 V~
Power
Supply
24 V~
Power
Supply
24 V~
Power
Supply
24 V~
Power
Supply

Technical Support :
+44-(0)20-7702-0657
WIRING
Sivoia QEDTM Quiet Electronic Drive Window System 1.6
wiring using individual power supplies
Wiring
Open
Close
LUTRON
AC
GRD
AC
AC
GRD
AC
AC
GRD
AC
A
B
For larger systems with more than four keypads, distribute keypads evenly on link - maximum one keypad
between EDUs.
Up to four keypads and 120 m (400 ft) total length of communications wire, no requirement for even
distribution.
Open
Close
LUTRON
Open
Close
LUTRON
AC
GRD
AC
AC
GRD
AC
AC
GRD
AC
WIRE TYPES
ACommunications Link
4 Conductor 1.0 mm2(#18AWG) (twisted and
shielded)
BPower Supply
3 Conductor 1.5–0.75 mm2(#16–20AWG)
MAXIMUM WIRE LENGTH
EDU to EDU - 150 m (500 ft)
Maximum total communications link - 1220 m (4000 ft)
Power supply to EDU
1.5 mm2(#16AWG) - 60 m (200 ft)
1.0 mm2(#18AWG) - 45 m (150 ft)
0.75 mm2(#20AWG) - 30 m (100 ft)
• One CCI counts as one keypad
• Number of keypads and CCIs not to exceed number of
EDUs without the need additional power supplies.
Open
Close
LUTRON
B
24 V~
Power
Supply
24 V~
Power
Supply
24 V~
Power
Supply
24 V~
Power
Supply
24 V~
Power
Supply
24 V~
Power
Supply

Technical Support :
+44-(0)20-7702-0657
WIRING
Sivoia QEDTM Quiet Electronic Drive Window System 1.7
multiple EDU wiring
Wiring
Lutron Sivoia QED
seeTouch keypad
BACK
To other
EDUs,
keypads,
or CCIs
To other
EDUs,
keypads,
or CCIs
• Every keypad, CCI, and EDU is connected by the
Sivoia
QED
TM
Communication Link.
• Wire each EDU to a separate power supply.
• Each EDU must be EARTH grounded.
• Each power supply, of any type, can power ONLY ONE
EDU, regardless of blind size.
A Communications Link 4 Conductors
B Power Wires 3 Conductors
Please refer to Tables on page 1.4 for details on these
wires.
4
3
2
1
Common
12V
MUX
MUX
AC
AC
EGND
Common
12V
MUX
MUX
AC
AC
EGND
female EDU connectorfemale EDU connector
A
B
AC
Earth Ground
AC
24VAC Power Supply
AC
Earth Ground
AC
24VAC Power Supply

Technical Support :
+44-(0)20-7702-0657
WIRING
Sivoia QEDTM Quiet Electronic Drive Window System 1.8
SV-CCI-8 wiring detail
Wiring
Input channel will accept dry contact closures and open
collector outputs (Vce ≤0.3 V).
Do not apply voltage to any input channel.
• By default all contact closures on a CCI operate the
same group of EDUs.
• By default the CCI has Open, Close, Preset 1, Preset 2,
Preset 3, Stop, Raise, and Lower inputs.
• LEDs provide feedback on contact closure state.
Input 1 - Defaults to Open
Input 2 - Defaults to Preset 1
Input 3 - Defaults to Preset 2
Input 4 - Defaults to Preset 3
Input 5 - Defaults to Close
Input 6 - Defaults to Stop
Input 7 - Defaults to Raise
Input 8 - Defaults to Lower
External Switch Closures
(supplied by customer)
Sivoia QED
Communication Link:
To other keypads, CCIs and EDUs.
4 (MUX)
3 (MUX)
2 (12 V)
1 (Common)
A
• Terminal blocks accommodate 1.5–0.5 mm2
(14–22 AWG) wire.
• The CCI can be configured to control two groups with
Open, Preset, Close, and Stop functionality, or with
Open, Close, Raise, and Lower functionality.
• The CCI can be configured to control four groups with
Open and Close functionality.
Andere Handbücher für Sivoia QED
5
Inhaltsverzeichnis
Andere Lutron Electronics Jalousie Handbücher