
5
3.2.1 INSTALLATION PROCEDURE
To install a Mesta DPM with CTs (current transformers) monitoring the “line” side of the DPM, perform
the following recommended procedure. Do not attempt to turn on power to the DPM until all steps have
been completed. The line side is defined as the wiring from the utility that powers both the DPM and the
loads to be corrected. Conversely, the load side is defined as the wiring “after” the DPM that powers
only the loads to be corrected. The CTs should be rated for the maximum anticipated load current of
the conductor on which they will be installed. The I.D. of the CTs should be larger than the O.D. of the
conductors. For detailed installation drawings, refer to the customer installation diagram for your
particular model in appendix B of this manual.
Note: The Mesta DPM may not operate properly if power factor correction capacitors are connected on
the load side of the CTs. CTs must be installed on the load side of these capacitors for proper operation.
Consult factory for any questions regarding the presence of power factor correction capacitors.
1) It is highly recommended for safety reasons to turn off power feeding the circuit that powers the
DPM and loads to be corrected prior to proceeding.
2) Designate the 3 phases of your power circuit as phases A, B, and C. Phase rotation is not a
concern, so the designation you make is arbitrary. If power is off and kept off until all of the
remaining steps are completed, the remaining steps may be performed in any order; otherwise
step 3 must precede step 4.
3) Terminate the secondary leads of CT A to A+ and A- terminals, CT B to B+ and B- terminals,
and CT C (Optional) to C+ and C- of P1 of the CT Interface board inside the DPM enclosure. If
using CTs supplied by Mesta, the black lead is the “+” lead and the white lead is the “-“ lead.
Use a tightening torque of 4 in. lb. Also, use the provided mounting points and wire ties to route
the CT wires and provide strain relief.
4) Encircle the conductor(s) you designated as phase A of your power circuit that feed both the
DPM and the loads to be corrected with the CT marked “A”. Make sure to orient the CT so that
its arrow is in the direction from the line side (utility) to the DPM/load side. Repeat for phases B
and C (Phase C current sensor is required if single phase (line to neutral) loads are
present).
5) Through a breaker or set of fuses, wire the power wiring from your designated phase A to the
left-most terminal of the switch inside the DPM. Similarly, wire the power wiring from your
designated phase B to the middle terminal and phase C to the right-most terminal of the switch.
WARNING:
Once the circuitry that the CTs are monitoring is energized, DO NOT disconnect secondary wires of the
CTs from P1 or remove P1 from the CT Interface Board. Power feeding the circuitry monitored by the
CTs must be turned off before P1 connections are removed. Circuitry should not be reenergized until
either the CTs are removed or the secondary wires are properly terminated. CTs should never be
installed on live circuitry if the secondary wires are not properly terminated. Open circuit terminals of a
CT monitoring a live circuit may develop a lethal voltage across the secondary wires.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN SERIOUS INJURY OR DEATH.
Once all the power and signal connections have been made to the DPM, the electrical service can be
re-established to the node. The DPM should have its disconnect switch turned off when it is first
installed and the power is re-established.
3.2.2 CUSTOMER RELAY CONTACTS
A description of the customer relay contacts is available in the status connections section 4.3 of this
manual. The customer can choose to utilize these contacts for remote monitoring of the system. Refer
to section 4.3 of this manual and the installation diagram in appendix B for relay contact description
ratings and location.