Please read this user guide carefully before attempting to install, operate or service
the MICRODAM pump. Know the pump application, limitations and potential hazards.
Protect yourself and others by observing all safety information. Failure to comply
with instructions could result in personal injury and/or propefty damage. Retain
this user guide for future reference. lnstallation, connections, and after-sale service
are to be made by a qualified person.
www.microdam.co.kr
USER GUIDE
Centrifugal Pump Series
Apollo Pump
- MD2OOW, MD3OOW, &
a
- ,, ,, ,,a[P

,Tl1E l- tr El t m condensate removal pumps are designed to automatically remove the drainage
liquid produced by air-conditioner evaporative coil. Our pumps can be also used for other types of fresh
water removal from refrigeration equipments, dehumidifiers, water dispensers, etc. where gravity drainage
is impossible.
Cover
MainPrate i''
rll Hanger
Check Valve
of Drain Hose
Reservoir
- Fully Automatic Operation
- Flame Retardant & High lmpact Plastic Construction
- Low Noise Motor with Thermal Protector
- Stainless Steel Shafts Adopted
- 90'Turn Check Valve for Easy Servicing
- Various Design for Various lnstallation Site
A WARNING A
1. DO NOT USE TO PUMP FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, ALCOHOL, ETC.
2. DO NOT USE IN EXPLOSIVE ATMOSPHERES.
3. DO NOT USE TO PUMP HOT WATER OVER 4Ob.
4. DO NOT HANDLE PUMP WITH WET HANDS OR WHEN STANDING ON A WET OR DAMP SURFACE, OR IN
WATER.
5. TO REDUCE THE RISK OF ELECTRICAL SHOCK, BE CERTAIN THAT THE PUMP IS CONNECTED TO A
PROPERLY GROUNDED GROUNDING TYPE RECEPTACLE.
6. CONNECT THE PUMP ONLY TO THE POWER SUPPLY SPECIFIED ON THE NAMEPLATE OF THE PUMP.
7. IN ANY INSTALLATIONS WHERE PROPERry DAMAGE AND/OR PERSONAL INJURY MIGHT RESULT FROM
AN INOPERATIVE PUMP, A BACKUP SYSTEM AND/OR ALARM SHOULD BE USED.
8. DO NOT TWIST THE DRAIN HOSE AND THE DISCHARGE HOSE.
9. BEFORE ANY MAINTENANCE OR REPAIR OF THE PUMP, PLEASE DISCONNECT THE PUMP FROM THE
TPOWER SUPPLY TO AVOID AN ELECTRICAL SHOCK.
10. PLEASE AVOID CHILDREN'S APPROACH TO THE PUMP.
11. PLEASE KEEP IN MIND THAT THE PUMPS ARE NOT SUBMERSIBLE PUMPS.
12. EVERY INSTALLATION OR AFTER-SALES SERVICE SHOULD BE DONE BY QUALIFIED SERVICE TECHNICIAN.
13. THE INTERMITTENT RATINGS OF THESE PUMPS ARE NOT LONGER THAN 5 MINUTES.
-2-
fTIlEf- trIETFI N1 "
Condensate Removal Pump
NAME OF EACH COMPONENT
-
GENERAL FEATURES OF mlEr-o=,rarn'

Poseidon Pump - Standard Medium Size Model
1 15V 60Hz I 230Y 60Hz
I I 5V 60Hz / 230V 60Hz
1 I 5V 60Hz / 230V 60Hz
Titan Pump - Medium Size Model with Low Profile Reservoir
0.8,
0. B,
0.8r
Apollo Pump - Compact Model for Wall Split Air Conditioner Only
1 1 5V 60Hz / 230V 60Hz
l l 5V 60Hz / 230V 60Hz
I 15V 60Hz / 230V 60Hz
Hercules Pump - Jumbo Size Model
1 1 5V 60Hz / 230V 60Hz
1 1 5V 60Hz / 230V 60Hz
1 1 5V 60Hz / 230V 60Hz
A fne above models and specifications can be changed without a notice for functional improvements.
-3-
mlE/- trtEIFtnl,,
Condensate Removal Pump
SPECIFICATIONS OF EACH MODEL
Model Power Sumly Performance (l/hr@Height in Meter) Maximum
Head Amps Watts lank Capacity
024b
[/D400 240 213 195 4.5m 0.724 74 1.8r
230V 50Hz lJt 207 192 4.0m 1.01A B5
MD6OO 282 249 234 1Ca 6.0m O.B9A 87 1.8!.
230V 50Hz 264 222 207 5.5m 1.604 117
MDEOO 324 279 261 159 159 8.0m 1.25A 125 1.8t
230V 50Hz 276 240 ooE oo 6.6m 2.48A 195
Model Power Supply Performance (l/hr@Height in Meter) Maximum
Head Amps Watts fank Capacity
024
MD600C 1 1 5V 60Hz / 230V 60Hz 285 249 228 120 6.0m O.B9A B5
MDBOOC 1 15V 60Hz I 230Y 60Hz 312 272 255 t5J 148 8.0m 1.25A 117
MD6OOCE 230V 50Hz 258 t)q 207 B4 6.0m 0.644
Model Power Supply Performance (z/nr@Heignt in Meter) Maximum
Head Amps Watts Tank Capacity
01234
MD2OOW 168 157 150 2.5m 0.29A 0.8r
[/D300w 177 166 162 60 3.0m 0.35A 34 0.Br
230V 50Hz 147 137 1aa 2.4m 0.444 42
N/D4OOW 198 190 186 tht 114 4.Om 0.664 43 0.Br
230V 50Hz 186 165 150 I r0 3.0m 1.124 71
Model Power Supply Performance (r/hr@Heisht in Meter) Maximum
Head Amps Watts Tank Capacity
0t10 12 15
MD1000 400 308 171 10.0m 0.91A 240 3.8r
230V 50Hz Jbt 280 160 9.0m 0.724 150
MD1 200 426 342 190 170 12.0m 0.91 A240 3.8t
230V 50Hz 402 312 165 130 I 1.0m 0.724 150
MD1500
t
486 399 aae 190 170 15.0m 0.99A Z3U 3.Br
230V 50Hz 432 328 171 162 14.0m O.9BA 180

(1) Carefully unpack the unit and check for damage. Make sure that all of the required parts are included.
The units are thoroughly tested before packing to insure safe delivery and operation. lf there is any
sign of damage due to shipment, return it to the place of purchase for repair or replacement.
(2) Select a mounting location near the appliance. The pump must be mounted horizontally. Run flexible
tubing or pipe from evaporator drain into the inlet hole of pump. Be sure inlet piping is sloped downward
to allow gravity flow.
(3) Connect outlet piping (3/8" l.D)with the check valve. From condensate unit, extend outlet piping straight
up as high as necessary, but not higher than the maximum head of the pump. Be sure that the outlet
piping is not twisted or clogged.
.Tip, How to Use the Check Valve
O For Un-installation
-' Turn an angle of 90' to the anti-clockwise direction
-' Take the check valve off from the hole
@ For lnstallation
--- Put the check valve into the hole
--' Turn an angle of 90' to the clockwise direction
(4) ln order to avoid siphoning action & running the pump dry, always connect the outlet piping to a drain
at a higher level than the pump itself.
.Tip, To Avoid the Siphoning Action
[\\sl!ss\
(ArB)
Min. 150mm :
t
Level of Outlet
Piping End
Pump Level
I
PVC Pipe(Min. 20mm 6;.....*
(5) A Make sure that the power source voltage matches with the pump's requirement. Connect the
pump's power cord to a constant source of power (not a fan or other device that runs intermittently).
Do not connect or link the air conditioner's power cable directly to the pump's power cable. Use the
power plugs respectively. lf the pump's power cable should be extended, use a cable of same
specification. All wiring should be done by qualified service technician.
(6)When all the above tasks are done, please perform a trial operation. Pour water into the pump's
reservoir and check if the pump works properly.
.Tip> About Safety Switch
,- The purpose of the safety switch is to prevent an overflow while the pump is not properly working
due to various reasons.
t
'- The lead wires of safety switch originally coming from our factory are set to shut down the
Heating/AC circuit. For this, the lead wires should be connected in series with the Low Voltage
Thermostat Circuit.
,. All wiring should be done by qualified service technician. Please refer to local codes in your area.
-4-
rfll El- trt=IHn1 ,,
Condensate Removal Pump
INSTALLATION GUIDE
---l

(1) A Before attempting to service or disassemble any component, make sure that the unit is
disconnected from the power source.
(2) Take off the drain hose from the inlet hole. Uninstall the check valve from the main plate. Disassemble
the outlet piping from the check valve with care not to spill the water inside of the outlet piping over
the floor or the pump. Clean the check valve and be sure that the ball inside of check valve moves
freely.
(3) Disassemble the cover and reservoir from the main plate.
(4) Be sure the floats move freely. Clean as necessary.
(5) Clean the reservoir with warm water and mild soap.
(6) Check the inlet and outlet piping. Clean as necessary. Be sure there are no kinks in the line that would
inhibit flow.
(7)After the servicing, assemble the unit by the reverse order.
(8) ln case of a long-term break, remove water from the outlet piping and the reservoir.
The unit does not run.
a) Check the power supply.
b) Check the appliance to see if the condensation is actually
being produced.
c) Make sure the inlet piping is not clogged. lf it is clogged,
the appliance may eventually be damaged.
The unit makes loud noises
when running. a) Make sure the inside of reservoir is clean.
b) Make sure there is no siphoning action.
The unit runs but does not pump
the liquid out.
a) Check the highest point of the outlet piping does not exceed
the maximum delivery head of the pump.
b) Check the inside of outlet piping is clean.
c) lnspect the check valve following the maintenance instructions.
Liquid drains back into the pump
from the outlet piping. a) The check valve may have debris in it. Clean the check
valve following the maintenance instructions.
Liquid leaks from around the
check valve.
I
a) Make sure the outlet piping is tightly connected with the
check valve.
b) Make sure the check valve is fastened properly.
c) lf the o-ring under the check valve is damaged, replace with
a new one.
-5-
fTllE/- trI=It= Jn"
Condensate Removal Pump
SERVICE & MAINTENANCE INSTRUCTIONS
TROUBLESHOOTING

MICRODAM condensate removal pump is warranted against defective materials and workmanship for
a period of 12 months. Any product that should fail for either of the above two reasons and is still within
the warranty period will be repaired or replaced at the option of Sungshin Hasco, Ltd. as the sole remedy
of buyer.
For our customers located outside of Korea (R.O.K), please return the defective unit to any authorized
local distributor or dealer with a brief written explanation of the problem. lf there are no apparent signs
of customer abuse, unit will be repaired or replaced. lf dispute arises over replacement of the pump, the
distributor or dealer is to segregate such items and hold for inspection by a representative of Sungshin
Hasco, Ltd. or notify factory with details of the problem for factory disposition and settlement of warranty
claim.
DISCLAIMER : The foregoing warranty is an exclusive warranty in lieu of any other express warranties.
Any implied warranties (including, but not limited to any implied warranty of merchantability or fitness
for a particular purpose) to the extent either applies to a pump shall be limited in duration to the periods
of the express warranties given above.
Warranty will be VOID if any of the following conditions are found :
1. Sealed motor housing opened.
2. Product connected to voltage other than indicated on nameplate.
3. Cord cut off to a length less than three feet.
4. Pump allowed to operate dry (fluid supply cut off).
5. Pump used to circulate anything other than fresh water at approximately room temperature.
6. Any type of product abuse by customer.
Any oral statements about the product made by the seller, the manufacturer, the representatives or any
other parties, do not constitute warranties, shall not be relied upon by the user and are not part of the
contract for sale. Seller's and manufacturer's only obligation, and buyer's only remedy, shall be the
replacement and/or repair by the manufacturer of the product as described above. Neither seller nor the
manufacturer shall be liable for any injury, loss or damage, direct, incidental or consequential (including,
but not limited to incidental or consequential damages for lost profits, lost sales, injury to person or
property, or any other incidental or consequential loss), arising out of the use or the inability to use the
product and the user agrees that no other remedy shall be available to it. Before using, the user shall
determine the suitability of the product for the intended use, and user assumes all risk and liability
whatsoever in connection therewith. We recommend each pump be used with a GFCI (Ground Fault
Circuit lnterrupter).
No MoRE BUCKET !
I'=t-trrE Ftrn'" CoNDENSATE REMOVAL PUMPS ARE HERE FOR YOU.
6I SUNGS}IIN
$ nf,5(o Lrmrteo
Tel: +82.53.853.8826, 8827
Fax: +82.53.853.8828
E-mail: [email protected]
www.microdam.co.kr MADE IN KOREA
,7fIE/-trIETHN-\*
Condensate Removal Pump
LIMITED WARRANTY
Dieses Handbuch passt für folgende Modelle
15
Inhaltsverzeichnis
Beliebte Wasserpumpe Handbücher anderer Marken

Sykes AmeriPumps
Sykes AmeriPumps GP100M Fehlerbehebungshandbuch

DUROMAX
DUROMAX XP WX Series Bedienungsanleitung

BRINKMANN PUMPS
BRINKMANN PUMPS SBF550 Bedienungsanleitung

Franklin Electric
Franklin Electric IPS Bedienungsanleitung

Xylem
Xylem e-1532 Series Bedienungsanleitung

Milton Roy
Milton Roy PRIMEROYAL Bedienungsanleitung