TECHNICAL DATA
Dimensions (W x D x H) 1200 x 950 x 630 mm
Weight (*1) 101/75 kg
Plate type casing Aluzinc steel plate
Heat loss casing (*2) 59 W/-59 W
Heat exchanger type Polyethylenterephthalat
counterflow heat exchanger
Fan type EC, constant volume
Filter class ISO Coarse >90% (G4)
Duct connections Ø 200 mm
Condensate drain PVC, Ø 20×1,5 mm
External leakage (*3) < 0.1 %
Internal leakage (*4) < 3.6 %
Supply voltage 230 V (±10 %), 50/60 HZ
Max. input/power (*5) 1145 W/7.1 A
Tightness class IP31
Standby power 4 W
Power consumption (*5&6) 1220 kWh/år
Ambient temperature -20/+40 °C
* 1 75 kg is without side plates and exchanger.
* 2 59 W: Outdoor air temperature -12 °C. Fitting location -12 °C.
Extract air temperature 20 °C (room).
-59 W: Outdoor air temperature -12 °C. Fitting location 20 °C.
Extract air temperature 20 °C (room).
* 3 At ± 250 Pa and 600 m3/h according EN 308/EN 13141-7.
* 4 At ± 100 Pa and 600 m3/h according EN 308/EN 13141-7.
* 5 Input without heating element (accessory).
* 6 Power consumption on comtinuous operation for system
with SFP value 1000 J/m3ved 500 m3/h.
Technical specifications
Trade mark Nilan
Model Comfort 600
Type Two-way ventilation unit not for residential
Type of drive Variable speed drive VSD
Type of heat recovery system Counterflow heat exchanger
Thermal efficiency of heat recovery 79.6%
Reference flow rate (supply air) 0.1594 m3/s
Reference flow rate (extract air) 0.1404 m3/s
Effective electric power input (kW) (supply air) 0.209 kW
Effective electric power input (kW) (extract air) 0.214kW
SFPint 413 W/(m3/s)
Velocity at design flow rate 0.022 m/s
Nominal external pressure 250 Pa
Internal pressure drop of ventilation components (supply air) 123 Pa
Internal pressure drop of ventilation components (extract air) 137 Pa
Static efficiency of fans (supply air) 57.4 %
Static efficiency of fans (extract air) 57.4 %
Maximum external leakage rate 1.5 % v/400 Pa
Maximum internal leakage rate 3.6 % v/250 Pa
Energy classification of M5 bag filters (extract air) E
Energy classification of F7 bag filters (outdoor air) C
Visuel filter warning An alarm on the user panel appears when filters need
changing
Sound power level (LWA) 56 dB(A)
Unit data for ecodesign