3-2. How to Fix Installation Plate
The mounting wall is strong and solid enough to prevent it from
vibration.
Washer
Wall
Wall
Installation
plate a
Installation
plate c
Indoor
unit
body
Wall
745
71 160 200
6
6
1550 from
ground
More than 551 More than 551
(Unit: mm)
Bolt-size M8
Bolt-
size
M8
Appropriate
Plugs (M8)
The centre of installation plate should be at more than 551 mm
at right and left of the wall.
The distance from installation plate edge to ground should more
than 1550 mm.
●
Always mount the installation plate horizontally by aligning
the marking thread and using a level gauge.
●
Mount the installation plate on the wall with 6 sets of plug,
bolt and washer (all non-supply) with size M8.
CAUTION
Also avoid areas where electrical wiring or conduits are
located.
The above precautions are also applicable if tubing goes
through the wall in any other location.
(1) Using a sabre saw, keyhole saw or hole-cutting drill
attachment, cut a hole in the wall.
N OT E
Hole should be made at a slight downward slant to the outdoor
side.
Hole Dia. (mm)
70
3-3. To Drill a Hole in the Wall and Install a Piping
Sleeve
(1) Insert the piping sleeve to the hole.
(2) Fix the bushing to the sleeve.
(3) Cut the sleeve until it extrudes about 15 mm from the wall.
CAUTION
When the wall is hollow, please be sure to use the Piping
sleeve assembly to prevent dangers caused by mice biting the
connection cable.
(4) Finish by sealing the sleeve with putty or caulking
compound at the final stage.
15 mm
Wall
Indoor Outdoor
Approx. 5 ~ 7 mm
Bushing for tube
Assembly
Putty or caulking compound
Sleeve for tube
assembly
ø70 mm
through hole
3-4. Indoor Unit Installation Installation
plate a
Slots
Hooks
Wall
Indoor unit (back)
Installation
plate c
Screws b
1. Engage the slots on the
indoor unit to the hooks of
installation plate a. Ensure
the hooks are properly
seated on the installation
plate by moving it left and
right.
2. Fix the screws bto the
holes on the hooks of
installation plate c, as
illustrated at right.
3-5. Water Piping Installation
●
The minimum requirement of water in the system is 50 litres.
If this value could not be achieved, please install additional
buffer tank (field supply).
●
Water inlet and water outlet in indoor unit are used for
connection to water circuit.
Please request a licensed technician to install this water
circuit.
●
This water circuit must comply with all relevant European and
national regulations, i.e. IEC/EN 61770.
●
Be careful not to deform the piping with excessive force when
doing piping connection job.
●
Use Rp 1-1/4” nut for both water inlet and outlet connection
and clean all pipings with tap water before connecting to the
indoor unit.
●
Cover the piping end to prevent dirt and dust when inserting it
through a wall.
●
Choose proper sealer which can withstand the pressures and
temperatures of the system.
●
If an existing tank is to be connected to this indoor/outdoor
unit, ensure the pipings are clean before water piping
installation is carried out.
●
An external filter (30 mesh or more, field supplied) must
be installed before the water inlet of the indoor unit (with
“WATER IN” indication).
●Water operating temperatures (Minimum ~ Maximum) : 5 °C
~ 65 °C
●Water operating pressures (Minimum ~ Maximum) : 0.05 MPa
~ 0.3 MPa
Indoor side Outdoor side