GENERAL INSTRUCTIONS
1) Begin the installation process by
determining mounting options.
2) The slotted, circular keyways can be used to
secure the housing to a standard junction
box. The junction box must be secured
sufficiently to handle the weight of the unit.
3) Additionally, two slotted vertical keyway
slots (Figure 1) may be used to attach the
housing to independent anchor supports.
Use three #8 toggle bolts (supplied by
others) for securing to wallboard or hollow
concrete walls. If the wiring is wall
recessed, run wires through center hole of
housing in preparation for unit wiring.
Figure 1
HOOKUP INSTRUCTIONS
Standard Units:
Connect A.C. service to unit charger leads:
Blue = 277 VAC
Black = 120 VAC
White = Common
Green = Ground
1. Connect remote lamps, if applicable.
Connect orange lead to RL+ and yellow lead
connected to RL-. Ensure total unit load
(including internal lamps) does not exceed
unit rating.
2. Install battery(ies). Refer to next section and
illustrations.
3. Adjust head(s) to illuminate desired area(s).
4. Close cover. Ensure electrical wires and
membrane switch cable remain inside unit
and do not interfere with cover closure.
INSTALLING BATTERIES
1. Units may ship without batteries installed
depending on the wattage of the unit. For
lead units, battery wiring harnesses are
already connected to PCB assembly and
connection to the batteries is required. In
the case of Nicad units, connection of
battery harness to the PCB is required.
2. Install and wire batteries as appropriate.
(See Page 3-4 for battery configurations)
3. Tighten straps to secure batteries inside unit.
OPERATING INSTRUCTIONS
1. Normal Power-Up Sequence
At power-up, the green LED indicators will
illuminate if the unit is properly connected.
2. Press and hold the ‘TEST’ button. The
lamps should illuminate and the green
indicator lamp should extinguish while the
lamps are on.
3. Release ‘TEST’ button. Lamps should
extinguish and the green indicator lamp
should be steady green.
WARNING –Shut off AC power to branch
circuits to which units will be connected. All
wiring should be per N.E.C. Articles 501-4(b)
and local codes.
To maintain warranty, equipment with batteries
must be installed or placed on charge within
prescribed period after shipment.