PR PReasy 4114 Bedienungsanleitung

4114
SIGNALS THE BEST
Universal
transmitter
No. 4114V104-UK
From ser. no. 121524001

1347
PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere m. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturud-
sving, og alle produkter opfylder de strengeste internationale stan-
darder. Vores motto »Signals the Best« er indbegrebet af denne
loso – og din garanti for kvalitet.
PR electronics A/S offers a wide range of analogue and digital
signal conditioning devices for industrial automation. The product
range includes Isolators, Displays, Ex Interfaces, Temperature
Transmitters, and Universal Devices. You can trust our products
in the most extreme environments with electrical noise, vibrations
and temperature uctuations, and all products comply with the
most exacting international standards. »Signals the Best« is the
epitome of our philosophy – and your guarantee for quality.
PR electronics A/S offre une large gamme de produits pour le
traitement des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux afcheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et uctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.
PR electronics A/S verfügt über ein breites Produktprogramm
an analogen und digitalen Signalverarbeitungsgeräte für die in-
dustrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Übereinstimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
DK
UK
FR
DE

4114V104-UK 1
UNIVERSAL TRANSMITTER
4114
CONTENTS
Warning .............................................................................. 2
Symbol identification.......................................................... 3
Safety instructions.............................................................. 3
Declaration of conformity................................................... 5
How to demount system 4000........................................... 6
When front LED lights red / display shows AO.ER............ 6
Advanced features ............................................................. 7
Application ......................................................................... 7
Technical characteristics.................................................... 7
PR 4501 display / programming front................................ 8
Applications........................................................................ 9
Order codes ....................................................................... 10
Electrical specifications...................................................... 10
Display readout on the 4501 of sensor error detection
and input signal outside range........................................ 13
Sensor error detection limits ........................................... 14
Error indications .............................................................. 14
Connections ....................................................................... 15
Block diagram .................................................................... 16
Configuration / operating the function keys ...................... 17
Routing diagram................................................................. 20
Routing diagram, Advanced settings (ADV.SET)................ 22
Scrolling help text in display line 3 .................................... 23

2 4114V104-UK
WARNING
This device is designed for connection to hazardous electric
voltages.
Ignoring this warning can result in severe personal injury or
mechanical damage.
To avoid the risk of electric shock and fire, the safety
instructions of this manual must be observed and the guidelines
followed. The specifications must not be exceeded, and the
device must only be applied as described in the following.
Prior to the commissioning of the device, this manual must be
examined carefully.
Only qualified personnel (technicians) should install this device.
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.
WARNING
SYSTEM 4000 must be mounted on a DIN rail according to DIN
46277.
WARNING
Until the device is fixed, do not connect hazardous voltages to
the device.
The following operations should only be carried out on a
disconnected device and under ESD safe conditions:
General mounting, connection and disconnection of wires.
Troubleshooting the device.
Repair of the device and replacement of circuit breakers
must be done by PR electronics A/S only.
HAZARD-
OUS
VOLTAGE
INSTAL-
LATION
GENERAL
WARNING
Do not open the front plate of the module as this will cause
damage to the connector for the display / programming front
PR 4501. This module contains no DIP-switches or jumpers.

4114V104-UK 3
SYMBOL IDENTIFICATION
Triangle with an exclamation mark: Warning / demand.
Potentially lethal situations.
The CE mark proves the compliance of the device with the essential
requirements of the directives.
The double insulation symbol shows that the device is protected by
double or reinforced insulation.
SAFETY INSTRUCTIONS
DEFINITIONS
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and
50 to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and
also troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate
the knobs or potentiometers during normal operation.
RECEIPT AND UNPACKING
Unpack the module without damaging it. The packing should always follow the
module until this has been permanently mounted.
Check at the receipt of the module whether the type corresponds to the one
ordered.
ENVIRONMENT
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
as well as rain and heavy moisture. If necessary, heating in excess of the stated
limits for ambient temperatures should be avoided by way of ventilation.
All devices fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
MOUNTING
Only technicians who are familiar with the technical terms, warnings, and
instructions in the manual and who are able to follow these should connect the
device.
Should there be any doubt as to the correct handling of the device, please
contact your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com

4 4114V104-UK
Mounting and connection of the device should comply with national legislation
for mounting of electric materials, i.e. wire cross section, protective fuse, and
location. Descriptions of input / output and supply connections are shown in
the block diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power
switch, it should be easily accessible and close to the device. The power
switch should be marked with a label indicating that it will switch off the
voltage to the device.
Year of manufacture can be taken from the first two digits in the serial number.
UL INSTALLATION REQUIREMENTS
Use 60/75°C copper conducters only
For use only in pollution degree 2 or better
Max. ambient temperature..................... 60°C
Max. wire size......................................... AWG 26-14
UL file number........................................ E231911
CALIBRATION AND ADJUSTMENT
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
NORMAL OPERATION
Operators are only allowed to adjust and operate devices that are safely fixed
in panels, etc., thus avoiding the danger of personal injury and damage. This
means there is no electrical shock hazard, and the device is easily accessible.
CLEANING
When disconnected, the device may be cleaned with a cloth moistened with
distilled water.
LIABILITY
To the extent that the instructions in this manual are not strictly observed, the
customer cannot advance a demand against PR electronics A/S that would
otherwise exist according to the concluded sales agreement.

4114V104-UK 5
DECLARATION OF CONFORMITY
As manufacturer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hereby declares that the following product:
Type: 4114
Name: Universal transmitter
is in conformity with the following directives and standards:
The EMC Directive 2004/108/EC and later amendments
EN 61326-1
For specification of the acceptable EMC performance level, refer to the
electrical specifications for the device.
The Low Voltage Directive 2006/95/EC and later amendments
EN 61010-1
Rønde, 20 August 2009 Kim Rasmussen
Manufacturer’s signature

6 4114V104-UK
HOW TO DEMOUNT SYSTEM 4000
First, remember to demount the connectors with hazardous voltages.
Picture 1:
Detach the device from the DIN rail
by lifting the bottom lock.
When front LED lights red / display shows AO.ER
PR 4114 is designed as a SIL 2 device with a high safety level. Therefore, a
continuous measurement of the outgoing current is carried out on a 4...20 mA
and 20...4 mA output signal. If the current output signal is different from the
internal calculated output value or the current output is 0 (due to e.g. an open
circuit breakage), an error mode switches on the red front LED.
This function is not a default option but must be actively selected via the
programming menu (S4-20 & S20-4).
The error mode can only be reset by switching off and then switching on the
supply voltage to the device.

4114V104-UK 7
UNIVERSAL TRANSMITTER
PReasy 4114
• Input for RTD, TC, Ohm, potentiometer, mA and V
• 2-wire supply > 16 V
• FM-approved for installation in Div. 2
• Output for current and voltage
• Universal AC or DC supply
Advanced features
• Programmablebywayofdetachabledisplayfront(4501),processcalibration,
signal simulation, password protection, error diagnostics and help text
available in several languages.
Application
• Linearised,electronictemperaturemeasurementwithRTDorTCsensor.
• Conversionoflinearresistancevariationtoastandardanaloguecurrent/
voltage signal, i.e. from solenoids and butterfly valves or linear movements
with attached potentiometer.
• Powersupplyandsignalisolatorfor2-wiretransmitters.
• Processcontrolwithstandardanalogueoutput.
• Galvanicseparationofanaloguesignalsandmeasurementoffloatingsignals.
• The4114isdesignedaccordingtostrictsafetyrequirementsandisthus
suitable for application in SIL 2 installations.
Technical characteristics
• When4114isusedincombinationwiththe4501display/programmingfront,
all operational parameters can be modified to suit any application. As the
4114 is designed with electronic hardware switches, it is not necessary to
open the device for setting of DIP-switches.
• Agreen/redfrontLEDindicatesnormaloperationandmalfunction.
• Continuouscheckofvitalstoreddataforsafetyreasons.
• 3-port2.3kVACgalvanicisolation.

8 4114V104-UK
PR 4501 DISPLAY / PROGRAMMING FRONT
Functionality
The simple and easily understandable PReasy menu
structure and the explanatory help texts guide you
effortlessly and automatically through the configuration
steps, thus making the product very easy to use. Functions
and configuration options are described in the section
”Configuration / operating the function keys”.
Application
• Communicationsinterfaceformodificationofoperationalparametersin4114.
• Canbemovedfromone4114devicetoanotheranddownloadthe
configuration of the first transmitter to subsequent transmitters.
• Fixeddisplayforreadoutofprocessdataandstatus.
Technical characteristics
• LCDdisplaywith4lines;Line1(H=5.57mm)showsinputsignal,line2
(H=3.33mm)showsunits,line3(H=3.33mm)showsanalogueoutputortag
no. and line 4 shows communication status.
• Programmingaccesscanbeblockedbyassigningapassword.The
password is saved in the transmitter in order to ensure a high degree of
protection against unauthorised modifications to the configuration.
Mounting / installation
• Click4501ontothefrontof4114.
Andere Handbücher für PReasy 4114
1
Inhaltsverzeichnis
Andere PR Sender Handbücher

PR
PR 2914 Bedienungsanleitung

PR
PR PRetrans 6333 Bedienungsanleitung

PR
PR 5331A Bedienungsanleitung

PR
PR PReasy 4114 Bedienungsanleitung

PR
PR PRetrans 6335 Bedienungsanleitung

PR
PR 5114 Bedienungsanleitung

PR
PR PRetrans 5131 Bedienungsanleitung

PR
PR 4104 Bedienungsanleitung

PR
PR 5350 Merkblatt

PR
PR PRetop 5331 Bedienungsanleitung
Beliebte Sender Handbücher anderer Marken

Dejero
Dejero EnGo 3x Bedienungsanleitung

Rosemount
Rosemount 4600 Bedienungsanleitung

Speaka Professional
Speaka Professional 2342740 Bedienungsanleitung

trubomat
trubomat GAB 1000 Bedienungsanleitung

Teledyne Analytical Instruments
Teledyne Analytical Instruments LXT-380 Bedienungsanleitung

Rondish
Rondish UT-11 Bedienungsanleitung