Produal RT Series Bedienungsanleitung

RT - Room transmitter
User Guide

Published: 22.01.2024 2 (26)
Contents
1 Introduction.............................................................................. 3
1.1 About this user guide.................................................................................................3
1.2 Intended use.............................................................................................................3
2 Safety precautions.................................................................... 4
3 Main components...................................................................... 5
4 Functional description...............................................................6
4.1 Multifunctional outputs............................................................................................... 6
4.2 Indicator lights.......................................................................................................... 6
5 Commissioning.......................................................................... 7
5.1 Mounting room transmitters........................................................................................ 7
5.2 Wiring.......................................................................................................................7
5.3 Configuring transmitter using MyProdual®.....................................................................8
5.3.1 Configuring measurement settings.................................................................. 10
5.3.2 Configuring output settings............................................................................ 16
5.3.3 Saving and uploading configurations................................................................17
5.4 Updating device firmware..........................................................................................18
6 Modbus....................................................................................19
6.1 Modbus properties....................................................................................................19
6.2 Modbus function codes............................................................................................. 19
6.3 Modbus registers......................................................................................................19
6.3.1 Input registers.............................................................................................. 19
6.3.2 Holding registers........................................................................................... 21
7 Disposal.................................................................................. 26
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 53022W0000ug

Published: 22.01.2024 3 (26)
1 Introduction
RT transmitters are versatile room temperature and CO₂ transmitters for simple measuring
applications in building automation.
The transmitters can be equipped with following options:
• relative humidity measurement (-RH models)
• Modbus communication (-MOD models)
The -MOD models have Modbus RTU communication via the RS-485 connection.
Note: -MOD models don't include any other outputs.
The device commissioning is done by using MyProdual® smartphone application and MyTool® Connect
commissioning tool. Some of the basic settings can be also configured via bus in -MOD models.
1.1 About this user guide
This user guide contains important information about the installation, wiring, configuration and use of
the product. Read this guide carefully before you install the product, connect the wires, or operate the
product. Make sure that you fully understand all instructions before you start work. If you are not sure
what the instructions mean, contact the seller or the manufacturer.
Follow all instructions in this user guide carefully. Always obey the applicable local rules and
regulations.
The original instructions were written in English. If there are differences between the English
instructions and the translations, refer to the English instructions.
If you find a mistake in the English instructions or in the translations, please send the details to the
manufacturer.
1.2 Intended use
Versatile RT room transmitters are intended to be used for measuring temperature, humidity and CO₂
in room environment.
These transmitters are intended to be connected to building automation systems in the HVAC/R
industry.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 53022W0000ug

Published: 22.01.2024 4 (26)
2 Safety precautions
The product is developed, manufactured and tested according to high quality standards. However,
instructions for safe use shall be taken account when installing, using or disposing the product or parts
of product.
Read this user guide carefully before commissioning, using or servicing this device. To avoid any kind
of damage to people or property, follow the instructions carefully. Produal is not liable for any hazards
or damages to people or property which are caused by ignoring the using or installation instructions.
To avoid electrical shock or damage to equipment, disconnect power before installing or servicing the
product. Use only a proper wiring rated for the full operating voltage and maximum current in the
system even in the event of a fault.
To avoid potential fire and/or explosion, do not use the product in potentially flammable or explosive
atmosphere.
The product condition must be checked before installation. Do not drop the product or use excessive
force during installation. Do not use the product if any damages are visible.
After installation the product will be part of a system whose specifications and performance
characteristics are not designed or controlled by Produal. Refer to national and local authorities to
ensure that the installation is functional and safe.
The product should only be used in professionally designed applications. Unauthorised modifications
are not allowed. The product must not be used in relation with any equipment that in case of a failure
may threaten, directly or indirectly, human health or life or result in danger to human beings, animals
or property.
In this document, there are different kind of warnings and notes. The warning and note types are
defined in the following table.
Sign Description
WARNING: The warning symbol indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION: The caution symbol indicates a potentially hazardous situation which, if not avoided,
could result in minor or moderate injury.
Important: The important symbol indicates a potentially hazardous situation which, if not
avoided, could result in damage to the device or property.
Note: The note symbol indicates a useful tip or a recommended way to complete a task.
These notes also provide information that is useful but not critical to the user.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 53022W0000ug

Published: 22.01.2024 5 (26)
3 Main components
1
2
3
6
4
5
1 Terminal block 2 Temperature sensor / Temperature and humidity
sensor (-RH models)
3 CO2 sensor 4 Communication indicator light (-MOD models)
5 Modbus termination jumper (-MOD models) 6 MyTool® Connect connector
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 53022W0000ug

Published: 22.01.2024 6 (26)
4 Functional description
4.1 Multifunctional outputs
The device has three configurable outputs. The outputs can be configured for the following purposes:
• analogue measurement output (freely scalable inside 0...10 Vdc)
• two-state output (e.g. 0/10 Vdc)
• control the output via communication bus
You can use the two-state output for a simple thermostat type control by setting the wanted
measurement value contact settings and selecting the measurement contact to control the output.
Configuration can be done via communication bus or by using MyTool® Connect and MyProdual®.
4.2 Indicator lights
The -MOD models have an indicator light on the circuit board. The indicator light can be set for
following functions:
• off
• data transmit indication
• data receiving indication
• data transmit and receiving indication
CAUTION: When the power supply is connected, be extra careful when handling the product
without the cover.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 53022W0000ug

Published: 22.01.2024 7 (26)
5 Commissioning
5.1 Mounting room transmitters
The device can be installed in dry surroundings (IP20) by screws on the wall surface or on the standard
flush mounting box. The recommended installation height is 150...180 cm.
The device position should be selected carefully. All the error factors that can affect to the
measurements should be eliminated as well as possible. The following list defines the typical
measurement error factors.
• direct sun light
• occupant proximity
• air flow coming from windows or doors
• air flow coming from ventilation nozzles
• air flow coming from the flush mounting box
• differential temperature caused by external wall
5.2 Wiring
WARNING: Device wiring and commissioning can only be carried out by qualified
professionals. Always make the device wirings in de-energised electricity network.
WARNING: External power sources and power wiring must be protected with a fuse or circuit
breaker. Rating depends on the overall system load, but the maximum rating for the external
circuit breaker is 16 A (limited by internal structure of the product).
WARNING: The minimum power rating for the external power source must be 170 VA / 170 W
to ensure proper operation of the internal fusing of the product in case of a failure condition.
Otherwise, the overall system power consumption shall be less than 15 W also in the failure
condition.
WARNING: This product is appliance class III product according to IEC 60664‑1. The product
may only be connected to SELV (separated extra low voltage) electricity network.
Important: This product has no capability to detect an abnormal condition of output ports.
External supervising (automated/human) may be needed depending on the application where
this product is used.
CAUTION: The product may only be connected to overvoltage category I, II or III electricity
network according to IEC 60664‑1.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 53022W0000ug

Published: 22.01.2024 8 (26)
GSupply, 24 Vac/dc, < 1 VA
G0 0 V
A+
B-
SS
A+
B-
Modbus RTU, RS-485 (-MOD models).
Note: Connector S can only be used for chaining the cable shield
pair.
AO1 Voltage output 1, 0...10 Vdc, < 2 mA (freely scalable within this range). Not available in -MOD models.
AO2 Voltage output 2, 0...10 Vdc, < 2 mA (freely scalable within this range). Not available in -MOD models.
AO3 Voltage output 3, 0...10 Vdc, < 2 mA (freely scalable within this range). Not available in -MOD models.
GND Ground
The nominal wire terminal screw tightening torque is 0.4 Nm.
Important: Do not use excessive force when tightening the wiring terminal screws.
CAUTION: Ensure that all covers are closed before connecting supply voltage to the product.
Don't remove the covers when the supply voltage is connected.
5.3 Configuring transmitter using MyProdual®
To configure the device, you first need to connect it to MyProdual® application. When the device is
connected to application, you can make changes to the configuration.
Note: You need MyTool® Connect for connecting MyProdual® to the device.
1. Connect the supply voltage to the device.
Note: You can also power the device by connecting a USB cable to MyTool® Connect.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 53022W0000ug

Published: 22.01.2024 9 (26)
2. Insert the MyTool® Connect to the connector.
A
B
A. MyTool® Connect connector
B. MyTool® Connect
The indicator light in MyTool® Connect flashes when the Bluetooth is ready for connecting.
3. Start MyProdual®.
4. Tap the Quick access button.
5. Tap the Bluetooth connection button.
The device list shows the devices that have Bluetooth activated.
6. Tap the device to from the list to connect.
The indicator light in MyTool® Connect is illuminated continuously when MyProdual® is connected
to the device.
7. Tap the Configuration button.
8. Tap the Component setup button.
Component setup view is divided in sections:
Measurements Set up measurements.
Outputs Set up outputs.
See more information about the settings from the following chapters.
9. Make the changes to configuration.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 53022W0000ug

Published: 22.01.2024 10 (26)
10. In -MOD models, press the General communication settings button to configure communication
settings
The following parameters are available for configuration:
Parameter
name
Values Default Description
Communication
mode
Off / Modbus RTU Modbus RTU Communication mode.
RS485 baud rate 9600 / 14400 /
19200 / 38400 /
56000 / 57600 /
76800 / 115200
9600 Bus speed.
Parity None / Even / Odd None Bus parity.
Stop bits 1 bit / 2 bits 1 bit Stop bits.
Communication led
mode
Off / Tx / Rx / Tx
+ Rx
Tx + Rx Communication indicator light function.
Off Indicator light is off
Tx Indicator light is on when the
device transmits data to bus.
Rx Indicator light is on when the
device receives data from bus.
Tx + Rx Indicator light is on when the
device transmits data to bus or
receives data from bus.
When this option is selected,
the transmit hold on time is ten
times the hold on time setting.
Communication led
hold on time
5…1000 ms 25 ms Communication indicator light hold on time.
Modbus slave ID 1...247 1 Modbus address.
Modbus broadcast Disabled / Enabled Enabled Modbus broadcast.
11. Tap Install to device button to write the changes to the device.
Note: The changes can also saved to device in each configuration view tapping the Save
button.
12. Tap the button.
13. Tap the connection info button to disconnect the device.
14. Remove the MyTool® Connect.
5.3.1 Configuring measurement settings
All device models include temperature and CO2 measurements. Other measurements available for
configuration depend on the model.
1. Tap the Component setup button on the Configuration page to open the Component setup page.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 53022W0000ug
Inhaltsverzeichnis
Andere Produal Sender Handbücher
Beliebte Sender Handbücher anderer Marken

Dejero
Dejero EnGo 3x Bedienungsanleitung

Rosemount
Rosemount 4600 Bedienungsanleitung

Speaka Professional
Speaka Professional 2342740 Bedienungsanleitung

trubomat
trubomat GAB 1000 Bedienungsanleitung

Teledyne Analytical Instruments
Teledyne Analytical Instruments LXT-380 Bedienungsanleitung

Rondish
Rondish UT-11 Bedienungsanleitung