Pytes V Series Bedienungsanleitung

User Manual
V Series
Information Version: 1.0
LITHIUM ION BATTERIES

Pytes V Series LFP Battery
User Manual
Dear valued customer,
Thank you for purchasing our Pytes V series LFP battery for home energy storage system.
Our V series battery pack is designed to provide safe, high-performance energy storage
solutions for a variety of applications. The compact and easy-to-install battery pack can be
used as a basic building block in an energy storage system by connecting in parallel. It is
widely used in residential, small commercial, and industrial energy storage systems, as well
as telecommunication stations.
We strongly recommend that you carefully read this manual before using the product. This
manual provides all the necessary information on installation, usage of the V series battery
pack. Please be advised that only qualified personnel(such as an electrician) should install
and perform maintenance on the battery pack.
It is important to keep in mind the boundaries of use, as described in this manual. The V series
battery pack is not intended for use in medical or aviation-related applications, and should
only be used for its intended purpose as described in this manual. Improper use of the battery
pack will void the warranty of the product, and Pytes cannot be held responsible for any
damage caused by improper or incorrect use of the product.
For your safety and the safety of others, please follow all user safety instructions during the
use of this product. This manual is intended for the installers and users of the V series battery
pack.
Please keep this manual in a safe location, as it is the original manual. For the latest version
of all manuals, please visit our website at http://www.pytesgroup.com.
Thank you again for choosing Pytes, and please do not hesitate to contact us if you have any
questions or concerns about your V series battery pack.
Best regards,
Pytes
Shanghai Pytes Energy CO., LTD.
Add: No.3492 Jinqian Road, Fengxian District, Shanghai, China.
Website: http://www.pytesgroup.com
Email: [email protected]
2

Before Using
Warning
Caution
Please read and follow these instructions carefully:
This equipment should only be installed, operated by qualified personnel (electricians).
The local safety regulations and relevant operating procedures must be followed during the installation,
operation and maintenance of the equipment, otherwise the equipment may be damaged. The safety
precautions mentioned in this manual are supplementary to the local safety regulations.
Do not short-circuit the Li-ion battery.
Follow the positive (+) and negative (-) marks on the Li-ion battery and equipment and ensure correct
use. Do not reverse the Li-ion battery.
Do not dismantle, crush, puncture, open, or shred the Li-ion battery.
Before removing or reconnecting with the running system, make sure to turn off the power and shut
down the system to avoid the risk of electric shock.
Do not expose the Li-ion battery to heat or fire. In case of fire, use a dry powder fire extinguisher.
Do not dismantle any part of the system without contacting PYTES or PYTES authorized technical
engineers. System failure caused by such actions will not be covered by the warranty.
Before operating the inverter, ensure that all batteries have been started up.
The following precautions should be taken when working on batteries:
a) Shut down the power and loads before connecting or disconnecting battery terminals.
b) Do not wear any metal objects such as watches and rings.
c) Use tools with insulated handles.
d) Do not lay tools or metal parts on top of batteries.
e) Wear personal protective equipment.
f) Make sure the battery is well grounded. Contact with any part of a poorly grounded or ungrounded
battery can cause electric shock and burns by high short-circuit current.
Do not dispose of batteries in fire, as the batteries may explode.
Keep the Li-ion battery away from water, dust, and contamination to avoid explosion or other harmful
conditions that may even lead to personal injury.
Do not open or mutilate batteries. Released electrolyte can be harmful to the skin and eyes and may be
toxic.
A battery can pose a risk of electric shock and burns due to high short-circuit current.
A malfunctioning battery can reach temperatures that exceed the safe contact level.
Danger
3

Symbols
Read the instruction manual before starting installation and operation.
Caution, do not dispose of batteries in a fire, the battery may explode.
caution, a battery can present a risk of electric shock and burns by high
short-circuit current. do not short-circuit the Li-ion battery.
Caution, do not dispose the product with household wastes.
Danger, keep the Li-ion battery away from water, dust and contamination,
otherwise it may cause explosion or lead to personal injury.
Danger, do not place near open flame or flammable materials.
Danger, do not place at children or pets touchable areas.
Recyclable.
LI-ION
4

CONTENTS
1 Specifications 6
1.1 Product standard configuration 7
1.2 BMS function 8
2 Interface and protection functions 8
2.1 Battery front panel schematic 8
2.2 Components 9
3 Operating Environment 10
4 Packaging, transportation, storage requirements 10
4.1 Transportation 10
4.2 Storage 10
5 Installation and configuration 10
5.1 Installation preparation 10
5.2 Unpacking 11
5.3 The preparatory work 11
5.4 Installation 14
6 Communication 14
6.1 RS232 port 15
6.2 RS485 port and CAN port 15
7 Troubleshooting 15
7.1 Unable to start 16
7.2 Unable to charge 16
7.3 Unable to discharge 16
7.4 ALM constantly on 17
5

1 Specifications
Table 1-1 Battery Pack Specifications
Battery Model V5° V5°α
Power Terminal PHOENIX M6 Bolt Amphenol SurLok Plus 8.0mm
Chemistry LFP
Nominal Voltage 51.2V
Voltage Range 47.5V~57.6V
Nominal Capacity 100Ah
Nominal Energy 5.12kWh
L440mm*W530mm*H140mm(3.2U)
L17.32in*W20.87in*H5.51in(3.2U)
Unit Weight 44KG / 97lbs
Recommended Charge/
Discharge Current
Max Continuous Charge/
Discharge Current
Peak Charge/
Discharge Current
Round-Trip Efficiency ≥95%
Communication Protocol RS485, CAN, WiFi (W/ Optional Device)
Cycle Life ≥6000cycles
Calendar Life ≥10years
Within 1month: -20°C~50°C(-4℉~122℉)
1-3months: -10°C~40°C(14℉~104℉)
3-12months: 20°C~25°C(68℉~77℉)
75A
100A
101A~120A (3min);
121A~180A (15sec)
Charge: 0°C~45°C(32℉~113℉)
Discharge: -10°C~50°C(14℉~122℉)
Operating Temperature
UN38.3, CE, UL1973, UL9540A, UL9540, IEC62619, CEC, SGIPCertificates
Storage Temperature
Heating System Temperature Rise 10°C(18℉)/Hour,
Operation Temperature -18°C~10°C(-0.4℉~50℉)
[1], [2]: The recommended and Max continuous charge and discharge current is for a battery cell temperature within
10°C~40°C(50℉~104℉)to consider. It will result in a derating on current if out of the temperature range.
[3]: Test conditions 0.2C Charging/Discharging, @25°C(77℉), 80% DOD.
[4]: Integrated with some inverters, heating system may consume enengy from battery when there's voltage difference among
system modules, between 0°C/32°F to 5°C/41°F. Follow 5.3.3 of this manual for multiple batteries power cable connection to
minimize influence of the circular current, thus decrease battery energy loss.
Unit Dimension
[3]
[2]
[1]
6

Items Quantity Specifications Pictures
V5° Version
1.1 Product standard configuration
LFP battery pack
Voltage: 51.2V
Capacity: 100Ah
Energy:5.12kWh
Power Terminal:
PHOENIX C-ES-FTB 25-70
V5° Battery 1pc
Function: cascade communication
between batteries
Length: 350mm
Communication protocols:
CAN / RS485
Cascade
Communication
Cable
Grounding Cable 1pc 10AWG/1000mm/SC10-6
Busbar for parallel
connection between
batteries:
Length: 190mm/Ampacity: 300A
Flexible Busbar
1pc
2pc
Items Quantity Specifications Pictures
V5°α Version
LFP battery pack
Voltage: 51.2V
Capacity: 100Ah
Energy:5.12kWh
Power Terminal:
Amphenol Surlok 8.0mm Socket
V5° Battery 1pc
Function: cascade communication
between batteries
Length: 350mm
Communication protocols:
CAN / RS485
Cascade
communication
Cable
Grounding Cable 1pc 10AWG/1000mm/SC10-6
Cable for parallel connection
between batteries; UL10269-
0AWG / 200mm / Amphenol
Surlok 8.0mm; Ampacity: 200A
Flexible Busbar
1pc
1set
7

1.2 BMS Functions
2 Interface and protection functions
2.1 Battery front panel schematic
Protection and Alarm Management and Monitor
Charge / Discharge End Cut-off Cells Balance
Charge over Voltage Protection Intelligent Charge
Charge / Discharge over Current Protection Charge/Discharge Current Limitation
Short Circuit Protection Administrator Monitoring
Power Cable Reverse Protection Log Record
High / Low Temperature Warning
Over / Under Temperature Protection Remaining Power Calculation
Power Button
Ground
CAN/RS485 communication Port
DIP Switch IoT Port Positive
Power Terminal
V5°
V5°α
Dry Contact
SOC Indicator
Alarm Indicator
Running Light
Start Switch
Negative
Power Terminal
8

2.2 Components
No. Name Label Functions description
1 Ground Connection for ground cable
2 Power button POWER
3 Soft start switch SW
4 DIP Switch ADD
Running Light RUN
Alarm Indicator ALM
SOC indicator SOC
6 CAN
7 RS485
9 Negative Power Terminal “-” Negative input and output interface
10 Positive Power Terminal “+” Positive input and output interface
When switched to "ON", the system can be activated by
the "SW" key or external power supply; when switched to
"OFF", the system is off.
When the on/off button is "ON", press and hold this button
for 1 second to enter the startup or sleep mode.
Set according to inverter brand, see checking list
Green light. The light flashes when Standby. The light is
constantly on when charging. The light blinks when
discharging.
Red light. The light flashes when Alarming. The light is
continuously on when protected.
Light bar shows current remaining capacity.
1 way input and 3 ways output dry contact signal.
Real-time monitoring of battery status and remote upgrade
RJ45 ports, connect Port 1 of the previous battery to Port
0 of the next one. The Port 0 of the master battery is
vacant.
External CAN
communication port
Cascade
communication port
Dry Contact
LoT port
IN1-/IN1+
COM2/NO2
COM3/NO3
COM4/NO4
External RS-485
communication port
Warning: 6,7,8,9,10,11,12is DVC-A circuit, they shall not be connected to DVC-B/C circuit when installed, or hazard shock
will occur.
5
RJ45 port, follows CAN protocol, for outputting battery
information.
RJ45 port, follows RS485 protocol, for outputting battery
information.
Prot 1/0
8
11
12
9

3 Operating Environment
4 Packaging, transportation, storage requirements
5 Installation and configuration
Battery operating environment requirements:
Operating Temperature: -10℃~50℃(14℉~122℉)
Relative Humidity: 20%-80%, no condensation
Altitude: <4000m
Site environment requirements: Away from heat source, avoid direct sunlight, no corrosive gases, no
explosive gases, no insulating gases, no insulating conductive dust.
Install in cabinet which shall not be opened without dedicated tools
Install in a restricted access area.
Always check all applicable local, national, and international regulations before transporting Li-ion
Batteries.
During transportation, protect the battery from severe vibration, shock or squeezing, and from
exposure to sunlight and rain.
During the loading and unloading process, the battery should be handled gently to prevent it from
falling, rolling and being subjected to heavy pressure.
Relative humidity: 20%-80%, no condensation
Altitude: <4000m
Store the battery in a cool, dry place, away from heat sources and no direct sunlight.
Keep away from conductive substances such as conductive dust
For long-term storage (>6 months), charge the LFP battery to more than 90% of its rated capacity. The
battery needs to be charged to more than 90% of its rated capacity every 6 months.
Keep the SOC of the battery at 40%-60% during storage. The Self-discharge of the LFP battery
pack is 1-2% per month. If there is no power left when checking the LFP battery, do not charge or use it
without permission, contact your installer for the next step.
Follow the storage instructions in this section and refer to Table 1-1 Battery Pack Specifications for
storage temperature to optimize the battery lifespan during storage. Any failure or damage to the battery
caused by failure of following these instructions is not covered by the warranty.
Only those who have received training in the power system and possess a comprehensive understand-
ing of the same are allowed to install the equipment. It is imperative to follow the safety regulations
defined by local authorities and adhere to the safety requirements listed below during the installation
process.
Before installing or removing the battery, make sure that the system is disconnected from any power
4.1 Transportation
5.1 Installation preparation
5.1.1 Safety Requirements
4.2 Storage
10
Dieses Handbuch passt für folgende Modelle
2
Inhaltsverzeichnis
Andere Pytes Batteriepack Handbücher
Beliebte Batteriepack Handbücher anderer Marken

IOGear
IOGear GBP24V Series Bedienungsanleitung

Inventus Power
Inventus Power PROTRXion S-12V100-TRX-HD Bedienungsanleitung

Clas Ohlson
Clas Ohlson PW-290A Bedienungsanleitung

EINHELL
EINHELL MULTI-Ah Power X-Change Plus Bedienungsanleitung

Samsung
Samsung EB-U3300 Bedienungsanleitung

ECTIVE
ECTIVE LC Series Bedienungsanleitung