Regency GFi750 Gas Inbuilt Fireplace | 9
installation
Flueing
This appliance is designed to be attached to two
co-linear aluminium ex pipes running the full length
of the chimney. The ue length must be a minimum
length of 2.44 m and a maximum of 10.7 m. See
chart for minimum distances from roof. Periodically
check that the vent is unrestricted.
Masonry chimneys may take various contours which
the exible liner will accommodate. However, keep
the exible liner as straight as possible, avoid
unnecessary bending.
The Air Intake pipe must be attached to the inlet
air collar of the adaptor.
Gas Connection
GAS CONNECTION WARNING:
Only persons licensed to work
with gas piping may make the
necessary gas connections
to this appliance.
1) If the appliance is to be installed into an existing
chimney system, thoroughly clean the masonry
replace.
2) The appliance is provided with an opening on
the right hand side of the control compartment.
The 9.5 mm exible gas hose provided needs
to be brought in from behind this opening.
Ensure all gas connections are tight.
3) Locate the center point where the vent will pass
through the chimney above the appliance. Move
the appliance into the exact location where it is
to be installed. Ensure that the Insert is level.
305 mm Mantel
89 mm
Mantel
535 mm
560 mm
to floor
Top
Faceplate
51
0
305 152 102
203
254
51
0
305
152
406
102
356
203
457
254
Side View
330 mm
508
559
Mantel Clearances
Clearances to Combustibles
Minimum Clearances to Combustibles
From Unit
Sides A 180 mm
Ceiling B 1205 mm
Mantel C 330 mm
Max. Mantle Depth E 305 mm
(see Dia. 2)
Min. Alcove Width F 1220 mm
Max. Alcove Depth G 915 mm
*No hearth required.
WARNING
DO NOT USE AN UNLINED
MASONRY CHIMNEY AS THE
FLUE FOR THIS APPLIANCE.
THE APPLIANCE MUST NOT
CONNECT TO A CHIMNEY
FLUE SERVING A SEPARATE
SOLID FUEL BURNING
APPLIANCE AND MUST BE
TERMINATED TO THE
OUTDOORS.
Note: When installing the ueing, identify the
ues. Mark one exhaust and one intake
as indicated on the top of the unit.
Part # Description
948-305 76mm Flex - 10.7m
948-336 102mm Flex - 10.7m
46DVA-VCH Termination Cap High Wind
46DVA-34CLTA Adaptor & Chimney Plate
Flue Restrictor Settings:
29 mm x 2 (Factory Set)
NOTE: Shut o valve must be installed in an
accessible location.
6Regency IG34 Gas Inbuilt Fireplace
INSTALLATION
Flashing
#46DVA-VCH
#948-305
#948-336
#46DVA-34CLTA
#948-305
946-773 Vertical Flue Kit
The ue kit contains the following:
NOTES
• A non-combustible mantel may be in-
stalled at a lower height if the framing
is made of metal studs covered with a
non-combustible board.
• The non-combustible mantle when
installed at a lower overall height may
not be lower than 152 mm from the
top of the replace opening.