4.4 System 2
1 collector array – 2 storage tanks – 2 pump
Description:
If the switch – on temperature difference between the
collector array (T1) and one of the two storage tanks (T2,or
T5) is exceeded, then the appropriate solar circuit pump
(P1) or (P0) is switched on. According to the priority
switching, both storage tanks ( T2, T5) are loaded one after
the other, until either the relevant switch-off temperature
difference between the collector array ( T1) and storage
tank (T2, T5) falls below the threshold, or the maximum
storage temperature is reached.
T1: Temperature sensor for collector 1
T2: Temperature sensor in the bottom part of tank 1
T5: Temperature sensor in the tank 2
T4: Temperature sensor on hot water pipe
P1: Solar circuit pump 1
P0: Solar circuit pump 2
Note: the default priority tank is tank 1.
System 2 display
4.5 System 3
1 collector array – 2 storage tanks – 1 pump- 1
valve
Description:
If the switch – on temperature difference between the
collector array (T1) and one of the two storage tanks (T2,
T5) is exceeded, then the solar circuit pump (P1) is
switched on and the switching valve ( R1) is set to the
correct position depending on the storage tank to be
loaded. According to the priority switching, both storage
tanks ( T2, T5) are loaded one after the other, until either
the relevant switch-off temperature difference between the
collector array ( T1) and two storage tanks (T2, T5) falls
below the threshold, or the maximum storage temperature
of T2 or T5 is reached.
T1: Temperature sensor for collector 1
T2: Temperature sensor in the bottom part of tank 1
T5: Temperature sensor in the tank 2
P1: Solar circuit pump 1
R1: 3-way switching valve ( Ports 17,18 are shut off, Ports
17,19 are turned on )
Note: When no voltage is on the system, the switching
valve ( R1) must be set to storage tank 1( T2)
•The default priority tank is tank 1.