Standard protection system
Flexible explosion-proof tube protection system
Cable protection system
In order to avoid the liquid flowing
along with the cable to flow into the
terminal box or result in waterproof
joint effusion, an U-shaped ring
needs to be configured between
pull box and temperature
transmitter as the picture shows,
and please ensure the U-shaped
bottom is under the temperature
transmitter. Considering the
maintenance and replacement,
enough cable length needs to be
Using flame proof temperature
transmitter in dangerous situations,
please use metal flexible explosion-
proof tube to connect the signal
cable into pull box and lead to the
safety zone.
Maintenance
Requires no maintenance
External cleaning
Please notice the following when cleaning:
Use washing agent which will not damage to the instruments
surface and seal ring.
Transportation / storage
Do not store at outside
Keep dry and dust-free
Do not expose to the corrosive medium
Avoid solar radiation
Avoid mechanical shock and vibration
Storage temperature: -40~100°C
Maximum relative humidity: 95%
EMC statement
EMC equipment instructions 2014/30/EU.
CE mark suggests the instruments are in line with EU standards
Users need to ensure the whole equipment conform to all the
applicable standards.
Depot repair
Please finish the following steps before the depot repair:
Removal of all the residues which would be harmful to human
health, such as inflammable, poisonous, cancerigenic and
radioactive substances.
Warning! Do not return the instruments if can not ensure the
dangerous residues are removed, eg: the dangerous residues
permeate into cracks or spread to the plastic.
!
Discard disposal
The instrument is not restrained of WEEE instruction 2002/96/EG
and laws of relevant countries.
Please pass the instrument to specialized recycling companies
other than local recycling points.
Retransport
Keep clean of the temperature transmitter. Stay away from any
Please adopt proper package to avoid damage in transportation.
dangerous medium!
Power supply
Independent linear direct-current power supply is suggested to be adopted for
the power supply of temperature transmitter, over large resistive load will result
in a large pressure drop, so it requires to calculate the all-in resistance of
signal cable, display meter and other record and display equipment, to ensure
the voltage provided to the temperature transmitter accord with normal
operating requirements.
Standard current signal output: 12-30VDC,
1~5VDC voltage output: 12-30VDC.
Grounding
Using cable with shielded twisted-pair signal has the best effect. To avoid
ground loop, shielded layer adopts single-end grounded.
Transient resistance built-in module is effective only in the case of good
grounding. Metal shell and internal grounding terminals are used to the nearest
Measurement signal is abnormal which should judge the process pressure is
abnormal, measuring system error or influence of installation environment or
abnormal in the pressure transmitter, then analyze the reason and take
corresponding measures.
No signal output, process pressure changes but no measurement
corresponding change, or , it may be an abnormalchange does not correspond
pressure transmitter, it needs to check the power supply voltage, wiring, power
consumption and load resistance whether they meet normal operating
requirements. Also need to check if there is leaks and pressure impulse line
blockage, shut-off valve not turned on, etc.
Signal output error is too big or it exceeds need to checkthe normal range,
the power supply voltage, power consumption and load resistance whether
they meet normal operating requirements, the measuring range setting, if
adjustment is correct. Also need to check if there is leaks and pressure impulse
line blockage, shut-off valve not turned on, rapid temperature fluctuations, etc.
Exception handing
Temperature transmitter / Quick installation manual
202