SMA DATA MANAGER L Bedienungsanleitung

Operating manual
SMADATAMANAGERL
EDML-10-BE-en-13 | Version 1.3ENGLISH

Legal Provisions SMA Solar Technology AG
Operating manualEDML-10-BE-en-132
Legal Provisions
The information contained in these documents is the property of SMA Solar Technology AG. No
part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or
by any means, be it electronic, mechanical, photographic, magnetic or otherwise, without the prior
written permission of SMA Solar Technology AG. Internal reproduction used solely for the purpose
of product evaluation or other proper use is allowed and does not require prior approval.
SMA Solar Technology AG makes no representations or warranties, express or implied, with
respect to this documentation or any of the equipment and/or software it may describe, including
(with no limitation) any implied warranties of utility, merchantability, or fitness for any particular
purpose. All such representations or warranties are expressly disclaimed. Neither SMA Solar
Technology AG nor its distributors or dealers shall be liable for any indirect, incidental, or
consequential damages under any circumstances.
The exclusion of implied warranties may not apply in all cases under some statutes, and thus the
above exclusion may not apply.
Specifications are subject to change without notice. Every attempt has been made to make this
document complete, accurate and up-to-date. Readers are cautioned, however, that product
improvements and field usage experience may cause SMA Solar Technology AG to make changes
to these specifications without advance notice or per contract provisions. SMA Solar Technology
AG shall not be responsible for any damages, including indirect, incidental or consequential
damages, caused by reliance on the material presented, including, but not limited to, omissions,
typographical errors, arithmetical errors or listing errors in the content material.
SMA Warranty
You can download the current warranty conditions from the Internet at www.SMA-Solar.com.
Software licenses
The licenses for the installed software modules (open source) can be found in the user interface of
the product.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. Missing designations do not
mean that a product or brand is not a registered trademark.
SMA Solar Technology AG
Sonnenallee 1
34266 Niestetal
Germany
Phone +49 561 9522-0
Fax +49 561 9522 100
www.SMA.de
E-mail: [email protected]
Status: 9/7/2022
Copyright © 2022 SMA Solar Technology AG. All rights reserved.

Table of Contents
SMA Solar Technology AG
Operating manual EDML-10-BE-en-13 3
Table of Contents
1 Information on this Document................................................. 5
1.1 Validity ........................................................................................................................ 5
1.2 Target Group.............................................................................................................. 5
1.3 Content and Structure of this Document ................................................................... 5
1.4 Levels of warning messages ...................................................................................... 5
1.5 Symbols in the Document .......................................................................................... 6
1.6 Typographical Elements in the Document................................................................. 6
1.7 Designations in the Document................................................................................... 6
1.8 Additional Information ............................................................................................... 6
2 Safety ........................................................................................ 8
2.1 Intended Use .............................................................................................................. 8
2.2 IMPORTANT SAFETY INSTRUCTIONS.................................................................... 8
2.3 Supported Products.................................................................................................... 11
3 Scope of Delivery..................................................................... 13
4 Product Overview.................................................................... 14
4.1 Product Description .................................................................................................... 14
4.2 Symbols on the Product ............................................................................................. 15
4.3 LED Signals................................................................................................................. 16
4.4 Sunny Portal................................................................................................................ 17
4.5 Interfaces and Functions ............................................................................................ 17
5 Mounting .................................................................................. 21
5.1 Requirements for Mounting ....................................................................................... 21
5.2 Mounting the Product on the DIN Rail...................................................................... 23
5.3 Mounting the Product on the Wall............................................................................ 25
6 Connection................................................................................ 27
6.1 Overview of the Connection Area ............................................................................ 27
6.2 Preparing the Connection Cable............................................................................... 27
6.3 Connecting Signal Source to Digital Input ............................................................... 28
6.4 Connecting RS485 Devices....................................................................................... 29
6.5 Connecting the network............................................................................................. 30
6.6 Connecting the Voltage Supply ................................................................................ 32
7 Commissioning ......................................................................... 35
7.1 Establishing a Direct Connection via Ethernet.......................................................... 35

Table of Contents SMA Solar Technology AG
Operating manualEDML-10-BE-en-134
7.2 Establishing a Connection via Ethernet in the local network................................... 35
7.3 Commissioning the Product........................................................................................ 36
7.4 Registering in Sunny Portal ........................................................................................ 37
8 Operation ................................................................................. 40
8.1 Design of the User Interface...................................................................................... 40
8.2 User Groups and User Rights.................................................................................... 41
8.3 Configuring Limitation of Active Power Feed-In........................................................ 43
8.4 Configuring Reactive Power as a Function of Grid Voltage.................................... 44
8.5 Configuring Modbus Devices.................................................................................... 45
8.6 Configuring a System with several Data Managers................................................ 46
8.7 Speedwire Encryption of the System Communication ............................................. 47
8.8 Switching Digital Outputs Based on Thresholds....................................................... 48
8.9 Creating and importing a backup file....................................................................... 49
8.10 Resetting the Product.................................................................................................. 50
8.11 Deleting the Admin Account...................................................................................... 50
9 Firmware Update..................................................................... 51
9.1 Updating the Product Firmware ................................................................................ 51
9.2 Updating the Firmware of Connected SMA Products ............................................. 51
10 Troubleshooting ....................................................................... 53
11 Decommissioning the Product................................................. 55
12 Technical Data.......................................................................... 57
13 Accessories ............................................................................... 59
14 Contact...................................................................................... 60
15 EU Declaration of Conformity................................................. 61
16 UK Declaration of Conformity ................................................ 62
17 Compliance Information.......................................................... 63

1 Information on this Document
SMA Solar Technology AG
Operating manual EDML-10-BE-en-13 5
1 Information on this Document
1.1 Validity
This document is valid for:
• EDML-10 (SMA Data Manager L) from firmware version 1.8
1.2 Target Group
The tasks described in this document must only be performed by qualified persons. Qualified
persons must have the following skills:
• Training in the installation and configuration of IT systems
• Training in how to deal with the dangers and risks associated with installing, repairing and
using electrical devices and installations
• Training in the installation and commissioning of electrical devices and installations
• Knowledge of all applicable laws, standards and directives
• Knowledge of and compliance with this document and all safety information
• Knowledge of operation and control of PV power plants on medium-voltage grids and high-
voltage grids
1.3 Content and Structure of this Document
This document describes the mounting, installation, commissioning, configuration, operation,
troubleshooting and decommissioning of the product as well as the operation of the product user
interface.
You will find the latest version of this document and further information on the product in PDF format
and as eManual at www.SMA-Solar.com. You can also call up the eManual via the user interface
of the product.
Illustrations in this document are reduced to the essential information and may deviate from the real
product.
1.4 Levels of warning messages
The following levels of warning messages may occur when handling the product.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

1 Information on this Document SMA Solar Technology AG
Operating manualEDML-10-BE-en-136
NOTICE
Indicates a situation which, if not avoided, can result in property damage.
1.5 Symbols in the Document
Icon Explanation
Information that is important for a specific topic or goal, but is not safety-rele-
vant
☐
Indicates a requirement for meeting a specific goal
☑
Desired result
Example
1.6 Typographical Elements in the Document
Typographical ele-
ment
Use Example
bold • Messages
• Terminals
• Elements on a user interface
• Elements to be selected
• Elements to be entered
• Connect the insulated
conductors to the terminals
X703:1 to X703:6.
• Enter 10 in the field
Minutes.
>• Connects several elements to be
selected
• Go to Settings > Date.
[Button]
[Key]
• Button or key to be clicked on or
pressed down
• Select [Enter].
# • Placeholder for variable
components (e.g., parameter
names)
• Parameter WCtlHz.Hz#
1.7 Designations in the Document
Complete designation Designation in this document
SMA Data Manager L Data Manager, product
1.8 Additional Information
For more information, please go to www.SMA-Solar.com.

1 Information on this Document
SMA Solar Technology AG
Operating manual EDML-10-BE-en-13 7
Title and information content Type of information
"Direct Marketing Interface" Technical information
"SMA Modbus® Interface - SMA DATA MANAGER" Technical Information
"PUBLIC CYBER SECURITY - Guidelines for a Secure PV System
Communication"
Technical Information
"RS485 Cabling Plan" Installation Manual
"SMA COM GATEWAY / SMA DATA MANAGER M - Compatibil-
ity and Application Options"
Technical Information
"SMA DATA MANAGER / SUNNY PORTAL powered by ennexOS
- Functions"
Technical Information
"SMASPEEDWIRE FIELDBUS" Technical information
"SUNNYPORTAL powered by ennexOS" User Manual
"SMA GRID GUARD 10.0 - Grid Management Services via Inverter
and System Controller"
Technical Information
"WAGO-I/O-SYSTEM 750 with SMA DATA MANAGER M" Installation Manual
"SMA DATA MANAGER M / SMA DATA MANAGER M Lite - Stor-
age of active power limitation and reactive power setpoint"
Technical Information
"SMA DATA MANAGER M / SMA DATA MANAGER L - Fault ride-
through (FRT) behavior"
Technical Information
Answers to frequently asked questions FAQ on product page
For questions on the implementation of grid management services Netzsystemdienstleistun-
User information on the operation and features of the product User information on the user
interface

2 Safety SMA Solar Technology AG
Operating manualEDML-10-BE-en-138
2 Safety
2.1 Intended Use
The SMADataManager L is the central communication unit for monitoring, control and grid-
compliant output regulation of large-scale PV power plants with central or string inverters. The
following is included into the SMA infrastructure via the Ethernet interface of the
SMADataManager L: system components and systems including energy generators and loads, I/
O systems and meters. At the same time, the SMADataManager L supports communication with
up to 200 devices.
The product is designed for indoor use only.
All components must remain within their permitted operating ranges and their installation
requirements at all times.
Use SMA products only in accordance with the information provided in the enclosed
documentation and with the locally applicable laws, regulations, standards and directives. Any
other application may cause personal injury or property damage.
Alterations to the SMA products, e.g., changes or modifications, are only permitted with the express
written permission of SMA Solar Technology AG. Unauthorized alterations will void guarantee and
warranty claims and in most cases terminate the operating license. SMA Solar Technology AG
shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as
appropriate.
The enclosed documentation is an integral part of this product. Keep the documentation in a
convenient, dry place for future reference and observe all instructions contained therein.
This document does not replace any regional, state, provincial, federal or national laws, regulations
or standards that apply to the installation, electrical safety and use of the product. SMA Solar
Technology AG assumes no responsibility for the compliance or non-compliance with such laws or
codes in connection with the installation of the product.
The type label must remain permanently attached to the product.
2.2 IMPORTANT SAFETY INSTRUCTIONS
Keep the manual for future reference.
This section contains safety information that must be observed at all times when working.
The product has been designed and tested in accordance with international safety requirements. As
with all electrical or electronical devices, there are residual risks despite careful construction. To
prevent personal injury and property damage and to ensure long-term operation of the product,
read this section carefully and observe all safety information at all times.

2 Safety
SMA Solar Technology AG
Operating manual EDML-10-BE-en-13 9
DANGER
Danger to life due to electric shock from touching an ungrounded product in
the event of an error
A product that is not grounded may be energized in the event of an error. Touching an
ungrounded product results in death or serious injury due to electric shock in the event of an
error.
• Ensure that the product is integrated in the existing surge protection.
• Ground the enclosure of the product.
• Ensure that the voltage of the digital input does not exceed 30VDC with respect to ground
potential.
WARNING
Danger to life due to electric shock
Under fault conditions, when working on the power supply circuit there may be dangerous
voltages present on the product. This can result in death or serious injury.
• For power supply units with a fixed connection, make sure that a disconnection unit (e.g.
miniature circuit breaker) is present outside the power supply unit.
• For power supply units with a plug connection, make sure that the electrical outlet for the
power supply unit is close to the power supply unit.
• The disconnection unit and the electrical outlet for the power supply unit must be freely
accessible at all times.
CAUTION
Risk of burns due to hot enclosure parts
Some parts of the enclosure can get hot during operation. Touching hot enclosure parts can
result in burn injuries.
• Do not touch the enclosure during operation.
• Wear suitable personal protective equipment.
NOTICE
Damage to the product due to condensation
If the product is moved from a cold environment to a warm environment, condensation may form
in the product. This can damage the product or impair its functionality.
• When there are large temperature differences, wait until the product has reached room
temperature to connect the voltage supply.
• Make sure the product is dry.

2 Safety SMA Solar Technology AG
Operating manualEDML-10-BE-en-1310
NOTICE
Manipulation of system data in networks
You can connect the supported SMA products to the Internet. When connected to the Internet,
there is a risk that unauthorized users can access and manipulate the data of your system.
• Set up a firewall.
• Close unnecessary network ports.
• If absolutely necessary, only enable remote access via a virtual private network (VPN).
• Do not use the port forwarding feature. This also applies to the used Modbus ports.
• Disconnect system components from other network components (network segmentation).
NOTICE
Failure and damage of product and system by interrupting the supply voltage
If the supply voltage of the product is interrupted during operation or a firmware update, a
failure of the product or the entire system may occur. This may result in loss of external setpoints
and a non-permitted starting behavior of the system. In addition, the device can be irreversibly
damaged.
• Ensure that the supply voltage of the product is never interrupted during operation. To do
this, use an uninterruptible power supply with 7 minutes bridging time.
Electrical installations (for North America)
All installations must conform with the laws, regulations, codes and standards applicable in the
jurisdiction of installation (e.g. National Electrical Code® ANSI/NFPA 70 or Canadian
Electrical Code® CSA-C22.1.).
• Before connecting the product to the utility grid, contact your local grid operator. The
electrical connection of the product must be carried out by qualified persons only.
• Ensure that the cables or conductors used for electrical connection are not damaged.
IP addresses of Modbus devices
In systems with Modbus devices, static IP addresses must be assigned to all Modbus devices.
Suitable IP addresses can be assigned to the Modbus devices from the free address supply of
the network segment either manually or dynamically via DHCP.
If the IP addresses are to be assigned dynamically, DHCP must be activated in the router (see
the router manual). Make sure that the Modbus devices do not contain variable IP addresses
but always the same IP addresses (static DHCP).
This also applies to data managers that are used as subordinated devices (slaves).