setting
. Turn off thermostat, long press for -5 seconds to enter into advanced setting
C
1 Confirm key: use it with
2 Only short press it to set time
Turn on thermostat,
long press
“
”
for -5seconds, the “OFF” and “ ” will
flashing in the same time, short press “ ” to holiday mode
.
B
2 Long press to lock /unlock
D
2 Long press to inquire external sensor temperature
In the Auto model, press or
enter to
temporary manual mode
Programmable
5+2 (factory default),6+1 and 7 models 6 times period setting for user choose. In the advanced options
choose model of you need, under power on state, long press for -5 seconds enter into programming
mode setting, then short press choose: hour, minute, time period, and press and to adjust
data, finished setting, about 10 seconds will automatic save and exist.
Out door Back home Out door Back home Sleep
6:00 20℃ 8:00 15℃ 11:0 15℃ 1 :0 15℃ 17:00 15℃ 22:00 15℃
The optimum comfort temperature is 18℃-22℃.
Advanced options
Under turn off state, long press for -5 seconds to access advanced setting.
From A1 to AE, short press to choose the option, and adjust data by , , short press to switch
next option. Remain about 5 seconds after finish setting will quit setting.
NO Setting Options Data Setting Function Factor
Default
A1 Measure Temperature
Calibration -9-+9℃
0.5℃
Accuracy
Calibration
A2 Temperature control
return difference setting
0.5-2.5℃ 1℃
A3 Children lock setting 0:half lock 1:full lock
0:half lock
A4
Power with memory
function
0:Power with memory function
1:Shutdown power after power off
2:Shutdown power after power on
0
A5 Backlight Sleep time
time 5- 0 Sec 10 Sec
A6
Weekly programming
selection
0: 5+2
1: 6+1
2: 7
0
A7 Setting temperature
lowest limit
1-10℃ 5℃
A8 Setting temperature
highest Limit
20-70℃ 5℃
A9
Limit value of low
temperature for external
sensor(anti-freeze
protection)
1. 1-10℃
2. Exceed 10℃, screen display【--】, Low temperature
protection was cancelled.
5℃
AA
Limit value of high
temperature for external
sensor
1. 5℃-70℃
2. Under 5℃, screen display【--】, high temperature
protection was cancelled
45℃
AB
External sensors limit
temperature control
return difference
1-9℃
2℃
AC
Window ventilation
function setting
Press ,display 10℃,when temperature 10℃ turn on
window ventilation function, stop heating mode, press
display -- , turn off Window ventilation
Disabled ---
AD Window ventilation
running time
10-20 mins
15mins
AE Restore factory defaults Long press key ,Display A , press OK key whole
show
BN
Options of sensor
control
N1:Built-in sensor (high temperature protection close)
N2:External sensor (high temperature protection
close)
N :Built-in sensor control temperature ,external
sensor limit temperature (external sensor detect the
N1