8. ACCESSORIES
(order separately)
Batteries:
Two batteries of the same AH rating are
required.
12V 7 Amp-Hour Viking PN 07920
12V 12 Amp-Hour Viking PN 07921
Plug-inconnectorisprovidedwiththe
Panel.
See POWER CALCULATIONS to
determine which batteries meet
standby battery requirements.
Zone Relay Module (4XZM): Model B-1
panels can accommodate a second
4XZM Zone Relay Module (one in-
cluded in each panel) or one of the
following two Modules:
Transmitter Module (4XTM) (Viking PN
07909) provides a supervised output
for local energy municipal box trans-
mitter and alarm and trouble reverse
polarity circuits.
LED Interface Module (4XLM) (Viking
PN 07910) for Remote Annunciator
(RZA-4X)describedbelow(Required
for NYC approval).
Remote Annunciator (RZA-4X) (Viking
PN 07911) Mounts on standard sin-
gle-gang box. (LED Interface Module
(4XLM)describedaboveisrequired).
Provides "System Trouble" LED
Local Piezo Sounder
Silence Switch (for local sounder)
Alarm/Waterflow Bell LED
Waterflow/Supervisory Bell LED
Releasing Circuit 1 LED
Supervisory Bell/Release Circuit 2
LED.
End-of-Lineresistor:4.7K,1/2Watt,with
terminal connector both ends, (for
two-wire supervised circuits) Viking
PN 07913
Power Supervisory Relay Coil (for four-
wire smoke detector circuits) (Viking
PN 07919)
Voltage & Current Meters (4XZMM) (Vi-
kingPN07917)mountinsidecabinet.
Digital Communicator NOTI-FIRE 911
(Viking PN 07918) Kit For Central
Station service.
9. INSTALLATION
Prior to installation, review the Par-3
Owners Manual and Viking Field Wiring
Diagrams. (See package inside Panel.)
Observe all instructions provided in the
Par-3 Owners Manual.
Field wiring must be according to VI-
KING FIELD WIRING DIAGRAMS for
the specific mode of operation required.
See TABLE 1.
All wiring should be done in accordance
with National and/or Local codes for fire
alarm systems.
The Authority Having Jurissdiction may
have additional requirements.
A. Mount the cabinet in a clean, dry,
vibration-free area where tempera-
ture and humidity conditions do not
exceed limitations indicated in
TECHNICAL DATA.
B.Verifythatallinitiatingdevices(detec-
tors) indicating appliances, and re-
leasing devices are compatible with
the Model B-1 Release Control
Panel.
ContacttheVikingDistributorforalist
of compatible devices. Also, refer to
appropriate Fire Protection Equip-
ment Approval Guides.
C. Wire all alarm initiating devices se-
quentially for proper supervision.
D. Pull required conductors through the
knockouts provided.
E.Priortoconnectingtothepanel,verify
continuity of all circuitry.
F.Priortoconnectingtothepanel,check
for, and correct any short circuits.
G.Makeelectricalconnectionstocontrol
panel for the detection,supervisory,
alarm, trouble, and release circuits,
according to appropriate VIKING
FIELD WIRING DIAGRAMS for the
systemusedandtheOwnersManual
provided with the panel.
1:WhereindicatedonVIKINGFIELD
WIRING DIAGRAMS, install the
4.7 K Ohm 1/2 Watt End of Line
Resistor(providedinpanel)at the
remote end of circuit. End Of
Line Resistors should NOT be in-
stalled across Release Circuits.
2: On all un-used circuits, leave the
4.7 K Ohm 1/2 Watt End of Line
Resistor (provided in panel) in
place.
3: Maintainpolarity onalarmbelland
trouble bell circuits.
Do not energize the panel until all asso-
ciated, modules, and interconnecting
cables have been connected.
H. Prior to energizing the panel:
1: Verifythatdipswitchescontrolling
panel operation are in the proper
position for the system used. Re-
fertoTABLE1andVIKINGFIELD
WIRING DIAGRAMS.
2:Verifythatallmodulesaresecurely
and properly positioned on their
pins. If a module is loose, care-
fully align all pins and press firmly
into position.
I. Connect non-energized AC power to
the panel. Refer to Figure 1 and VI-
KING FIELD WIRING DIAGRAMS.
1:Connectthewireprovidingin-com-
ing voltage to the trminal marked
"H".
2: Connect the neutral wire to the
terminal marked "N".
3: Connect the groung wire to the
terminal mrked "G".
J. Procedure for connecting Batteries:
Note: Two Battery plug/wire assem-
blies (long leads with plug) and
jumper (short) wires are provided
with each panel. Connectors on one
plug/wire assembly fit 7.0 AH Batter-
ies. Connectors on the other
plug/wire assembly fit 12.0 AH Bat-
teries.
1: Position batteries end to end with
terminals adjacent. Select the
proper plug/wire assembly for the
batteries used.
2: Connect the long RED lead to the
positive terminal of one battery,
and the long black lead to the
negative terminal of the other.
3: Place batteries inside the battery
compartment of the Par-3 Panel
with the unused terminals toward
the open door. Install batteries in
the upright position only.
4: Plug the plug-in connector to J9
on the main board of the panel.
(refer to Figure 1 and VIKING
FIELD WIRING DIAGRAMS). Do
NOT install jumper at this time.
To energize the panel and place the
system in service:
K. Energize the AC power supply to the
panel. The Piezo will sound, and the
"System Trouble" and "Power
Trouble" LEDs will flash.
L. Use the jumper (short) wire to con-
nect the unused negative terminal of
one battery with the unused positive
terminal of the other battery. The
Piezo should silence, and the "Sys-
tem Trouble" and "Power Trouble"
LEDs should stop flashing.
M. Perform appropriate tests to verify
proper operation of the system.
N. After placing the system in service,
close and lock the panel to prevent
tampering with the unit.
Wheninstallingoptionalcards,modules,
inter-connectingcables,or otherassoci-
ated equipment, refer to MAINTE-
NANCE, technical data for the optional
equipment, and Owners Manual pro-
vided with the panel.
TECHNICAL DATA
June 21, 1993
MODEL B-1
RELEASE CONTROL
PANEL
Panel 210 c
R