wattstopper LMCT-100 Bedienungsanleitung

The LMCT-100 Wireless IR
Configuration Tool is a handheld
tool for setup and testing of
WattStopper Digital Lighting
Management (DLM) devices.
It provides wireless access
to occupancy and daylighting
sensors for setup and parameter
changes, WattStopper Push n’ Learn™ (PnL)
technology for load configuration, switch and
dimmer assignment and operating parameter
changes. The LMCT-100’s display shows menus
and prompts to lead you through each process.
The navigation pad provides a familiar way to
navigate through the customization fields. The
LMCT-100 allows modification of the system
without requiring ladders or tools; simply with a
touch of a few buttons.
User Guide
LMCT-100
Digital Configuration Tool
Patents Pending
Sensor Configuration............... 4
Load Configuration (PnL) ..... 13
Daylighting Configuration...... 17
Button Configuration ............. 78
Dimming Configuration ......... 85
Adjust Light Level.................. 90
Network Settings................... 91
Utilities................................... 70
Troubleshooting..................... 73
CONTENTS

2Operation
OPERATION
The LMCT-100’s IR transceiver allows bidirectional
communication between DLM devices and the
LMCT-100. Simple menu screens let you see the
current status of the system and make changes.
It can change any of the DLM occupancy sensor
parameters such as sensitivity, time delay and
more. With the LMCT-100 you can also change load
configurations, without any new wiring. For systems
including the LMLS-305 daylighting sensor the
LMCT-100 can also set or change the daylight level
parameters. The LMCT-100 can change dimming
system options such as scene assignments, fade
rates and other options not available through the
standard user interface.
BATTERIES
The LMCT-100 operates on three
standard 1.5V AAA Alkaline
batteries or three rechargeable
AAA NiMH batteries.
The battery status displays in the upper right
corner of the display. Three bars next to BAT=
indicates a full battery charge. A warning appears
on the display when the battery level falls below a
minimum acceptable level.
To conserve battery power, the
LMCT-100 automatically shuts off 10
minutes after the last key press.

3
Navigation
NAVIGATION
You navigate from one field to another using (up)
or (down) arrow keys. The active field is indicated
by flashing (alternates between yellow text on black
background and black text on yellow background).
Once active, use the Select
button to move to a menu
or function within the active
field.
Value fields are used
to adjust parameter
settings. They are shown in
“less-than/greater-than”
symbols: <value>. Once
active, change them using
(left) and(right) arrow
keys. In general thekey
increments and the key
decrements a value. Selections wrap-around if
you continue to press the key beyond maximum or
minimum values. Moving away from the value field
(using /keys) overwrites the original value.
The button takes you
to the main menu.
The button can
be thought of as an
un-do function. It takes
you back one screen.
Changes that were in
process prior to pressing
the key are lost.
Sensor Configuration
Load Config (PnL)
Daylighting Config
Button Configuration
Dimming Configuration
Adjust Light Level
Home/
Main Menu
Up
Select
Down
Right/Next
Left
Back
Power
On/Off
IR Window
BAT=
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Value FieldsParameters
Function Fields (on Home Menu)
Sensor Configuration
Load Config (PnL)
Daylighting Config
Button Configuration
Dimming Configuration
More
=
BAT

4Sensor Configuration - Current Settings
Home Menu
The Home (or Main) menu
displays after the power-
up process completes. It
contains information on
the battery status and six
menu choices.
Press /to locate the
desired function then press Select.
SENSOR CONFIGURATION CURRENT SETTINGS
Sensor Configuration
Current Settings
Test Mode
Saved Configurations
Point to desired
Occupancy Sensor
Press ‘Select’
Press
Select
Press
Select
Point and
Press Select
Sensor Configuration
Load Config (PnL)
Daylighting Config
Button Configuration
Dimming Configuration
More
=
BAT
This action enables com-
munication between the
sensor and the LMCT-100.
The sensor immediately
sends its current
parameter settings.
The screen changes to
show the current sensor settings where you can
adjust sensor parameters. “AH” next to Sensor
Config indicates that the sensor is currently in After
Hours mode. Changes made while AH is displayed
only affect After Hours operation.
Select
Button
Up or Down
Button
Sensor Configuration
Load Config (PnL)
Daylighting Config
Button Configuration
Dimming Configuration
More
=
BAT

5
Adjusting Sensor Parameters
ADJUSTING SENSOR PARAMETERS
Using Current Settings, you can view all parameters
applicable to the type of sensor that is currently
communicating with the LMCT-100. You can modify
settings, send them to the sensor, and/or store them
in the LMCT-100.
Time Delay
Step 1: push or to
adjust the value.
Options:
<1 to 30 minutes>,
and <Override> to disable
the sensor
.
Step 2: push to activate
the next field.
Detection Sensitivity
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Adjust PIR
Sensitivity
Adjust
Ultrasonic
Sensitivity
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Press the
Down Arrow
for Ultrasonic
Step 1: push or to adjust the value. PIR and
Ultrasonic sensitivities vary from 0% to 100% in 10%
increments.
Note: Only sensitivity of technology that is present
can be changed.
Step 2: push to activate the next field.
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Adjust
Time Delay
Minutes

6Adjusting Sensor Parameters
Trigger/Retrigger Mode (Dual Tech Sensors only)
Step 1: push or to cycle through selections of
technology(ies) for the initial occupancy trigger:
PIR Only US (ultrasonic) Only PIR or US
PIR & US
Step 2: push to activate the next field.
Step 3: push or to cycle through technology
activations required to keep the load ON after the
initial occupancy is triggered.
Walk Through Mode
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Walk
Through
Mode
On or Off
Press the
down arrow to
choose Send,
Save or Receive
Walk-through mode
turns the load off three
minutes after the area
is initially occupied if no
motion is detected after
the first 30 seconds. If
motion continues
beyond the first 30
seconds, the selected
time delay applies.
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Adjust
Trigger
Mode
Adjust
Retrigger
Mode
Press the
Down Arrow
for Retrigger

7
Adjusting Sensor Parameters
Send
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Press
Select
Point and
Press Select
Configuration
Sent
Point to desired
Occupancy Sensor
Press ‘Select’
This sends the settings to the sensor.
The LEDs on the sensor blink to confirm the
message has been sent. To double-check that the
new settings were sent to the sensor, see “Receive.”
Save
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Choose
Save
Press
Select
Point and
Press Select
Saved Sensor Config
in Memory Slot 1
Press ‘Select’
This saves the settings in the LMCT-100 “Saved
Configurations” menu function for future use.
Each time you save a configuration the “Memory
Slot” number increases. You can save up to 9
configurations. Saved configurations are listed in the
LMCT-100’s “Saved Configurations” function in the
Sensor Configuration menu (for more details, see
page 12).

8Sensor Configuration - Test Mode
Receive
Important: Selecting Receive before sending new
settings to the sensor or saving them to LMCT-100
memory clears any value changes that you made.
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Point to desired
Occupancy Sensor
Press ‘Select’
Choose
Receive
Press
Select
Point and
Press Select
This retrieves the current settings from the sensor.
SENSOR CONFIGURATION TEST MODE
Sensor Testing - Individual Sensor
Sensor Configuration
Current Settings
Test Mode
Saved Configurations
Press
Select
Press
Select
Press the
Down Arrow
for Test Mode
Point to desired
Occupancy Sensor
Press ‘Select’
Sensor Test Mode
Individual Sensor
All Sensors on bus
Point and
Press Select
Press
Select
Sensor Configuration
Load Config (PnL)
Daylighting Config
Button Configuration
Dimming Configuration
More
=
BAT
The individual sensor goes into test mode.

9
Sensor Configuration - Test Mode
Adjusting Sensitivity during Test
For dual technology sensors, both technologies
appear on the screen, otherwise the screen only
presents the applicable technology.
PIR Sens = passive infrared sensitivity
US Sens = ultrasonic sensitivity
Adjust
PIR
Sensitivity
Adjust
Ultrasonic
Sensitivity
Press down
arrow for
Ultrasonic
Sensor Test
PIR Sens: <90%>
US Sens: <70%>
Detection : <PIR Only>
SEND RECEIVE EXIT
Sensor Test
PIR Sens: <90%>
US Sens: <70%>
Detection : <PIR Only>
SEND RECEIVE EXIT
You can adjust sensitivity values while inside the Test
Mode. Values are 0 to 100%, in 10% increments.
Detection Criteria (Dual Technology Sensors only)
Select
Detection
technology
Press
down arrow
for Detection
Sensor Test
PIR Sens: <90%>
US Sens: <70%>
Detection : <PIR & US>
SEND RECEIVE EXIT
You can select to test one
or the other technology,
or both technologies
together. Selections cycle
through:
PIR US PIR or US
PIR &US

10 Sensor Configuration - Test Mode
Send
Press
Select
Point and
Press Select
Point to desired
Occupancy Sensor
Press ‘Select’
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Sensor Test
PIR Sens: <90%>
US Sens: <70%>
Detection : <PIR Only>
SEND RECEIVE EXIT
Configuration Sent
Test Mode starts using
the settings you sent.
Receive
Choose
Receive
Press
Select
Point and
Press Select
Point to desired
Occupancy Sensor
Press ‘Select’
Sensor Config
Time Delay: <20 min>
PIR Sens: <90%>
US Sens: <70%>
Trigger : <PIR Only>
Retrigger: <PIR Only>
Walkthru: <Off>
SEND SAVE RECEIVE
Sensor Test
PIR Sens: <90%>
US Sens: <70%>
Detection : <PIR Only>
SEND RECEIVE EXIT
Retrieves settings from the sensor so you can view
or modify them for further testing.