FlexiSmoke™ - Utilization examples –1507 EN ©WindowMaster 2013, 2015 ®WindowMaster is a registred trademark used under the license by WindowMaster Group
FlexiSmoke™
WSC 520 / 540 / 560
Utilization examples

2/47
Table of contents
1Example A - 1 WSC 520, 4 motor groups in 1 smoke zone.................................................................... 3
1.1 Description................................................................................................................................... 3
1.2 Hardware connection diagrams..................................................................................................... 3
1.3 Configuration................................................................................................................................ 5
1.3.1 Start-up of the FlexiSmoke™ .................................................................................................... 5
1.3.2 Configuration of motor lines ...................................................................................................... 6
1.3.3 Configuration of motor Groups.................................................................................................. 9
1.3.4 Configuration of break glass unit..............................................................................................10
1.3.5 Configuration of smoke zones..................................................................................................15
1.3.6 Configuration of local input.......................................................................................................16
2Example B –1 WSC 520, 4 motor groups in 1 smoke zone –KNX.......................................................24
2.1 Description..................................................................................................................................24
2.2 Hardware connection diagram .....................................................................................................24
2.3 Configuration...............................................................................................................................25
2.3.1 Configuration of motor lines .....................................................................................................25
2.3.2 Configuration of break glass unit..............................................................................................30
2.3.3 Configuration of smoke zone....................................................................................................33
2.3.4 KNX configuration....................................................................................................................35
3Example C –1 WSC 520, 3 motor groups in 1 smoke zone and rain sensor.........................................38
3.1 Description..................................................................................................................................38
3.2 Hardware configuration diagram..................................................................................................38
3.3 Configuration...............................................................................................................................39
3.3.1 Configuration of local output.....................................................................................................39
3.3.2 Configuration of local input.......................................................................................................40
4Example D –1 WSC 540, 5 motor groups in 1 smoke zone, rain, wind direction and wind speed sensors,
configured for wind direction dependent smoke ventilation ..........................................................................41
4.1 Description........................................................................................................................................41
4.1 Hardware configuration diagram..................................................................................................41
4.2 Configuration...............................................................................................................................42
4.2.1 Configuration of the CAN bus...................................................................................................42
4.2.2 Configuration of Smoke area 1.................................................................................................42
4.2.3 Configuration of wind direction dependent smoke ventilation....................................................43
4.2.4 Configuration of weather station sensors..................................................................................43
5Example E –2 WSC 540, 4 motor groups in 3 smoke zones, Master-Slave and Controlling/Controlled
smoke zone configuration...........................................................................................................................44
5.1 Description..................................................................................................................................44
5.2 Hardware connection diagram .....................................................................................................44
5.3 Configuration...............................................................................................................................45
5.3.1 Configuration of the CAN bus...................................................................................................45
5.3.2 Basic configuration ..................................................................................................................45
5.3.3 Configuration of smoke area 1.................................................................................................46
5.3.4 Configuration of Controlling/Controlled smoke zone relation.....................................................46
6List of abbreviations.............................................................................................................................47

3/47
1 Example A - 1 WSC 520, 4 motor groups in 1 smoke
zone
1.1 Description
Using one WSC 520 0ISS to control 4 Motor Groups in one Smoke Zone.
8 MotorLines, ±24V (standard) motors, in all. 2 motor lines are associated with each motor group.
All 4 motor groups are associated with the same smoke zone and each motor group is controlled by a
comfort push-button.
2 comfort push buttons are connected to the break glass units and 2 are connected to input terminals on the
WSA 5IO module.
The smoke zone fire alarm can be triggered from 2 break glass units and from a signal from the BMS
system.
Smoke detectors are connected to the break glass unit.
Set-up overview:
- 1 Smoke zone
- 4 motor groups with 16 standard motors
oe.g. 12 x WMX 823-3 (1A motor) max total 12A and 4 x WMU 862-1 (2A motor) max total
8A.
- 2 Break glass units
- 4 Keypads for comfort
- 2 smoke detectors
1.2 Hardware connection diagrams
Figure 1 overview of the smoke zone and how the different components are connected to the smoke panel

4/47
Figure 2 overview of the smoke zone, motor groups and motor lines.
Figure 3 overview of the smoke panel and how the different components are connected it.

5/47
1.3 Configuration
1.3.1 Start-up of the FlexiSmoke™
In order to configure the FlexiSmoke™it must be logged onto with third level rights.
Warning icon appears since motors, break glass units and
comfort keypads have been connected but the panel is not yet
configured.
Press the “key” button
Enter the PIN code (4321) for level 3.
Level 3 allows you to configure the smoke panel.
Confirm the PIN code with check mark
Confirmation of which level you have logged on too.

6/47
Press “Configuration” in order to start the configuration.
1.3.2 Configuration of motor lines
Press “Motor line”.
Select the motor line to configure. In this example we select the
S5:X1 (Slot 5, motor output #1) motor line.
Set the “Motor Configuration”
Select the cable monitoring type.

7/47
In this set-up, select “no cable monitoring”.
Confirm with check mark.
Set the stroke time (the “time to open” of the actuators
connected on the motor line).
Enter the stroke time in seconds.
In this set-up, the stroke time is set to 50 seconds.
Confirm with check mark.
Associate the motor line with a motor group.

8/47
Select the motor group the motor line is to be associated with.
In this set-up, the motor line is associated with motor group 1.
Confirm with check mark.
Press the arrow down to get further options.
If required, change the “Retry during alarm” parameter to Yes.
Selecting yes will prompt the motor line to repeatedly attempt to
reach the ”Max stroke Alarm” position if it failed to do so in the
first attempt.
In this set-up, we select “No”.
Confirm with check mark.

9/47
The first motor line has been configured and the warning icon
has disappeared from the configured motor line.
Continue to configure all motor lines.
Note:
Motor lines not in use must be configured with "Motor
configuration" = "None" to clear the warning icons.
1.3.3 Configuration of motor Groups
Press “Motor group”.
Select the motor group to be configured.
Associate the motor group no. 1with a smoke zone.
Press “Return” to return to the motor group overview.

10/47
Select the smoke zone.
In this set-up, smoke zone 1 is selected.
Confirm with check mark.
Continue to associate all 4 motor groups with smoke zone 1.
Press “Return” to return to the main menu.
1.3.4 Configuration of break glass unit
Press “Break glass unit”.