Xtreme SNMP-R90 Leitfaden

Web/SNMP Cards
SNMP-1PMINI, SNMP-1PIN, SNMP-R90, SNMP-USB, SNMP-3PEX, SNMP-2P3 models
User & Installaon Manual
www.xpcc.com | © 2015 Xtreme Power Conversion Corporaon. All rights reserved. (Rev 12/20/18)

Xtreme Power Conversion Corporaon
Web/SNMP Cards
Page 2
UPS Management
Table of Contents
Introducon.................................................................................................4
Features...........................................................................................................................................4
Applicaons.....................................................................................................................................4
NetAgent Models............................................................................................................................6
NetAgent UPS Installaon..........................................................................10
NetAgent, UPS and Network Connecon....................................................11
Install the NetAgent with UPS and Network..................................................................................11
Using Nelity Setup IP. Update Firmware....................................................13
Install Nelity.................................................................................................................................13
Using Nelity..................................................................................................................................13
UPS Web Management by NetAgent..........................................................17
Introducon...................................................................................................................................17
NetAgent UPS Web Interface.........................................................................................................17
Telnet (Remote Conguraon)....................................................................48
Introducon...................................................................................................................................48
Telnet Conguraon......................................................................................................................48
Telnet Conguraon......................................................................................................................50
ClientMate - Windows Shutdown Ulity.....................................................51
Install ClientMate..........................................................................................................................51
Using ClientMate...........................................................................................................................51
SNMPView – Windows Based UPS Management System............................57
Introducon...................................................................................................................................57
System Requirements....................................................................................................................58
Install SNMPView..........................................................................................................................58
Using SNMPView...........................................................................................................................58
SNMPView Buons.......................................................................................................................59
Appendix A: Update the Firmware of NetAgent UPS...................................75
Appendix B: 3 Ports NetAgent II with SMS Modem.....................................78

Xtreme Power Conversion Corporaon
Web/SNMP Cards
Page 3
UPS Management
Appendix C: SMS Server with SMS Modem.................................................81

Xtreme Power Conversion Corporaon
Web/SNMP Cards
Page 4
UPS Management
Introducon
Features
NetAgent is a new generaon SNMP (Simple Network Management Protocol) monitoring product. Not only
can you remotely control the UPS and get the current status of it, the SNMP-3PEX also can provide other func-
ons, such as connecng via Modem or GSM Modem to make monitoring possible when there is no permanent
internet connecon and send SMS nocaon . The SNMP-3PEX can also bee used to connect to SNMP-EMP, to
get the temperature, humidity and water condions. Smoke detector, gas detector, door and window detector
opons are also available.
This product is compable with Contact Closure and RS232 interface UPS. The communicaon protocol includes
the Contact Closure, RS232 [MegaTec], RS232 [Phoenixtec], SEC 2400, SEC 9600, Three Phase, Powerware, Smart
APC, EMERSON. User could also provide their own protocol to build in. NetAgent provides a simple and easy
installaon procedure. The CD included with the NetAgent cards oer several soware programs to allow the
user to congure IP address; central monitoring and mul client shutdown on dierent operang systems. Other
advance conguraons can be accomplished via a Web browser.
Features:
• Provide SNMP MIB to monitor & control UPS
• Auto-sense 10M/100M Fast Ethernet
• Manage and congure via Telnet, Web Browser or NMS
• Support TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP, SMTP Protocol
• Providing easy setup and upgrade tools via MS-Windows, just a few seconds to nish IP seng, about
1.5 minutes to upgrade rmware.
• Send SNMP TRAP; E-mail and SMS for events nocaon.
• Auto email daily UPS history report
• Client shutdown soware for computer’s le saving and graceful shut down.
• SNMP-3PEX: Environment Measurement (Oponal Kits), External modem dial in/out via PPP protocol or
GSM/GPRS Modem
Applicaons
NetAgent Connects your UPS to the Network
When the UPS is equipped with a NetAgent Web/SNMP card, the system manager can monitor and check the
state of each and every UPS via a Web browser. The manager can monitor and control the UPS by simply brows-
ing the IP address of the NetAgent Web/SNMP card in to the UPS. When an abnormal power condion happens,
the NetAgent can also send trap informaon or an email to the system manager to take proper acon.
NetAgent Provides Shutdown Ulies
When a computer on the network has the NetAgent ulity installed, it can locate all of the NetAgent Web/SNMP
cards on the network. When the registered UPS of this NetAgent is in AC failure condion or Baery Low condi-
on, the operang system can close all the les on the system, and perform a gracefully shutdown. This could
avoid system corrupon when the UPS baery runs low.
NetAgent for Surrounding Monitoring
SNMP-3PEX can be used to connect the environmental monitoring ulity, SNMP-EMP, to get the temperature/
humidity/smoke/re indicaons. This informaon can also be displayed on the NetAgent Web page. When an
abnormal condion happens, it can also be sent as a trap to the system manager.

Xtreme Power Conversion Corporaon
Web/SNMP Cards
Page 5
UPS Management
When do we need the NetAgent Web/SNMP Card?
1. When we need to remote monitor and control the UPS condions. For example, the system manager could
use the network to control all the UPS condions all over the country. When the shutdown ulity is installed,
the shutdown ulity could close all the les and shutdown the system when a abnormal power condion
happened.
2. When we need to monitor environmental condions of the machine room, warehouse, oce, …etc. For ex-
ample, the system manager could know the temperature, humidity, smoke and water condion by using the
SNMP-3PEX and SNMP-EMP. The system manager could connuously monitor these environmental condi-
ons over a Web browser.
NetAgent Connecon Soware
SNMP-3PEX Diagram

Xtreme Power Conversion Corporaon
Web/SNMP Cards
Page 6
UPS Management
NetAgent Models
P/N Package Contents Internal/External
SNMP-1PIN
1. 1 Port Internal card
2. NetAgent Ulity CD
3. User Manual
Internal
SNMP-3PEX
1. 3 Port External Agent
2. NetAgent Ulity CD
3. User Manual
4. M2501 Cable (for Contact Closure UPS)
5. M2502 or M2505 Cable (for RS232 UPS)
6. M2506 Cable (for Modem)
7. 9V DC adapter
External
SNMP-1PMINI
1. Internal NetAgent Mini
2. NetAgent Ulity CD
3. User Manual
Internal
SNMP-R90
1. Internal NetAgent Mini
2. NetAgent Ulity CD
3. User Manual
4. 5.3V DC adapter
External
SNMP-USB
1. Internal NetAgent Mini with LCD Display
2. NetAgent Ulity CD
3. User Manual
4. 5.3V DC adapter
External
Pictures of NetAgent Web/SNMP Cads
SNMP-1PIN
SNMP-3PEX

Xtreme Power Conversion Corporaon
Web/SNMP Cards
Page 7
UPS Management
SNMP-1PMINI
SNMP-R90
SNMP-USB
NetAgent Package Contents
• NetAgent Ulity CD, includes:
»Nelity: Congure NetAgent IP address, update rmware
»ClientMate:Windows, Linux, FreeBSD shutdown ulity.
»SNMPView: Windows plaorm mulple NetAgent UPS management soware.
»SMS Server: SMS Nocaon
»UPS MIB: MIB le for the Network Management System
»Time Server:Time adjustment ulity
»And NetAgent Installaon/User’s Manual
• M2502 (or M2505) Cable: For external NetAgent II connecon to RS-232 UPS.
• M2506 Cable: For connecon SNMP-3PEX and Modem.
• 9V DC Adapter: For SNMP-3PEX
• 5.3V DC Adapter: For SNMP-R90 or SNMP-USB
NetAgent Outlook
SNMP-1PIN

Xtreme Power Conversion Corporaon
Web/SNMP Cards
Page 8
UPS Management
SNMP-3PEX
LED Table
Yellow Red Green Status
Solid O Solid O Solid ON Power ON
Flashing Solid ON Solid ON System inial
Solid ON Solid O Solid ON Normal operaon
Solid ON Flashing Solid ON No connecon to UPS
Flashing Flashing Solid ON Wring data to ash
memory
Green light: Power state
Red light: Connecon state with UPS
SNMP-1PMINI
SNMP-R90

Xtreme Power Conversion Corporaon
Web/SNMP Cards
Page 9
UPS Management
SNMP-USB
LED Table
Yellow Red Green Status
Solid O Solid O Solid ON Power ON
Flashing Solid ON Solid ON System inial
Solid ON Solid O Solid ON Normal operaon
Solid ON Flashing Solid ON No connecon to UPS
Flashing Flashing Solid ON Wring data to ash memory
Green light: Power state
Red light: Connecon state with UPS
Light signal applicaon - Status LED
Light color Signal denion Condion descripon
Green Power state On: Normal power
Red Connecon state with UPS Flash: no connecon with UPS
Orange Correspondence state Light ashes when Netagent transmits command to UPS
Light signal applicaon - LAN Port LED
Light color Condion descripon
Green On: Internet correspond speed is 100M
Flash: Data transming
Yellow On: Internet correspond speed is 10M
Flash: Data transming

Xtreme Power Conversion Corporaon
Web/SNMP Cards
Page 10
UPS Management
NetAgent UPS Installaon
Before using the NetAgent, the proper hardware and soware conguraon is necessary. Hardware installaon
connects the NetAgent and UPS and network. Soware conguraon includes the IP address. Firmware upgrade.
Or using the Browser or Telnet for conguraon.
You could also install the shutdown ulity – ClientMate to protect your Windows operang system. And also
could use the UPS management soware – SNMPView, to control and manage mulple UPS on the network.
NetAgent UPS installaon owchart
Dieses Handbuch passt für folgende Modelle
5
Inhaltsverzeichnis
Andere Xtreme Computerhardware Handbücher
Beliebte Computerhardware Handbücher anderer Marken

EMC2
EMC2 VNX Series Betriebsanleitung

Panasonic
Panasonic DV0PM20105 Bedienungsanleitung

Mitsubishi Electric
Mitsubishi Electric Q81BD-J61BT11 Bedienungsanleitung

Gigabyte
Gigabyte B660M DS3H AX DDR4 Bedienungsanleitung

Raidon
Raidon iT2300 Bedienungsanleitung

National Instruments
National Instruments PXI-8186 Bedienungsanleitung