York 110 Bedienungsanleitung

WATER SYSTEMS
Features
• 6 speed fan
• Cabinet factory tted
• Valve factory tted
• Electrical heater factory tted
• Thermal or modulating valve
• Service valve
Dimensions indicated next page
(1) Cooling capacities based on 7ºC EWT ∆t 5ºC indoor temperature 27ºC DB / 19ºC WB - (2 pipes - high speed fan)
(2) Heating capacities based on 70ºC EWT ∆t 10ºC indoor temperature 20ºC - (2 pipes - high speed fan)
(3) In cooling mode 2 rows
For other conditions contact York international
Technical features
YLVR - YLIVR
Model 110 112 114 216 218
Cooling capacity (1) 2 rows W 832 1054 1493 2041 2356
Cooling capacity (1) 3 rows W 913 1266 1790 2327 2714
Heating capacity (2) 1 row W 1167 1691 2319 3029 3552
Pressure drop (3) kPa 7 1.7 3.8 9 11.7
Power supply V/Ph/Hz 230 / 1 / 50 + E
Sound power level (3) dB(A) 49 50 53 53 55
Sound pressure level at 3 m dB(A) 31 32 35 35 37
Water connections inch 1/2 “
Thermostats
CSL00 (Built in)
CSR00 (Wall mounted)
Fan speed selector
CML00 (Built in)
CMR00 (Wall mounted)
Thermostat with manual fan speed and S/W
change over
CEL00 (Built in)
CER00 (Wall mounted)
Thermostat with manual fan speed and automatic
change over
CEL20 (Built in)
CER20 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over
CEL30 (Built in)
CER30 (Wall mounted)
Thermostat with auto. fan speed and automatic
change over for modulating valve
Fan Coil Unit
LOW BODY (2 & 4 pipe system)
A complete range from 0.8 kW up to 2.7 kW
Selection
software

E-COM-H0702
Fan Coil Unit LOW BODY
0.8 to 2.7 kW
Compatibility table / Codes
Model 110 112 114 216 218
With Cabinet
YLVR 2 rows l l l l l
3 rows l l l l l
4 rows l l l l l
Without Cabinet
YLIVR 2 rows l l l l l
3 rows l l l l l
4 rows l l l l l
Options (Factory fitted)
Coil and heaters
1 row heating BA1 l l l l l
Kit electrical heater (with relay and safety switch) KREL l l l l l
Built in thermostat
Fan speed selector CSL00 l
Thermostat with manual fan speed and S/W change over CML00 l
Thermostat with manual fan speed, dead band, automatic
change over CEL00 l
Thermostat with automatic fan speed, dead band, automatic
change over CEL20 l
Thermostat with automatic fan speed, dead band, automatic
change over for modulating valve CEL30 l
Parallel connection
For ON/OFF valve one/FCU CBL20 l
For modulating valve one/FCU CBL30 l
3 way valve factory fitted
For 2 pipe systems ON/OFF J3A2 (2p) l
For 4 pipe systems ON/OFF J3A2 (4p) l
3 way modulating valve factory fitted
For 2 pipe systems Modulating J3AM (2p) l
For 4 pipe systems Modulating J3AM (4p) l
Shut off valves factory fitted
For 2 pipe systems DT (2p) l
For 4 pipe systems DT (4p) l
Condensate pump PC l
WS sensor change over for CEL/CER WS l
Minimum temperature thermostat TM l
Accessories (Supplied loose)
Remote controllers and thermostat (wall mounted)
Fan speed selector CSR00 l
Thermostat with manual fan speed and S/W change over CMR00 l
Thermostat with manual fan speed, dead band, automatic
change over CER00 l
Thermostat with automatic fan speed, dead band, automatic
change over CER20 l
Thermostat with automatic fan speed, dead band, automatic
change over for modulating valve CER30 l
(1) for check compatibility with the models of FCU see compatibility table

WATER SYSTEMS
LOW BODY: YLVR
Dimensions
(All dimensions in mm)
DIMENSIONS AND WEIGHTS
Dim 110 112 114 216 218
A 648 773 898 1023 1148
B 374 499 624 749 874
C 254 254 254 254 254
D 174 174 174 174 174
E 100 100 100 100 100
G 170 170 170 170 170
H 101 101 101 101 101
J 430 430 430 430 430
N 245 245 245 245 245
O 154 154 154 154 154
P 31 31 31 31 31
Q 47 47 47 47 47
R 304 304 304 304 304
S 88 88 88 88 88
T 87 87 87 87 87
U65 65 65 65 65
V 47 47 47 47 47
W 84 84 84 84 84
X 214 214 214 214 214
Z 109 109 109 109 109
ø 20 20 20 20 20
kg 15 17 22 23 26
YLVR
wR= low body
wV= vertical
YLIVR
wR= low body
wV= vertical
wI= without cabinet

LOW BODY: YLIVR
(All dimensions in mm)
DIMENSIONS AND WEIGHTS
Dim 110 112 114 216 218
A 555 680 805 930 1055
B 374 499 624 749 874
C 230 230 230 230 230
D 108 108 108 108 108
E 73 73 73 73 73
G 170 170 170 170 170
H 101 101 101 101 101
J 395 395 395 395 395
K61 61 61 61 61
L349 474 599 724 849
M127 127 127 127 127
N 245 245 245 245 245
O 154 154 154 154 154
P 31 31 31 31 31
Q 47 47 47 47 47
R 304 304 304 304 304
S 88 88 88 88 88
T 87 87 87 87 87
U65 65 65 65 65
V 47 47 47 47 47
W 84 84 84 84 84
X 214 214 214 214 214
Y201 201 201 201 201
Z 109 109 109 109 109
ø 20 20 20 20 20
kg 9 11 14 16 19
Fan Coil Unit LOW BODY

WATER SYSTEMS
Compatibility tables for FCU
LASER and LOW BODY
FEATURES CEL/CER
• Dead band for change over 5°C or 2°C
(factory set 2°C for 4 pipes and 5ºC for 2 pipes)
• Manual fan speeds or automatic
(models 20 and 30)
• Thermostated fan control or continuous
fan running
• Option water sensor WS for change over
on coil (for 2 pipes)
• Led indicated status summer,
winter or dead band
• Temperature setting for 7 to 30°C
(comfort 20-25°C)
• Plastic pins for limiting temperature range
• Input for window contact
• Input for Economy/ occupancy mode
• Output for remote alarm
• Filter alarm 600 or 1200 running hours
(factory set 1200 hours)
• With electrical heater post ventilation
• With Air sensor in the air intake destratication
function (CEL only)
lCompatible
Not compatible
Compatibility table Thermostats / Valves / Heaters / Parallel connection / Water sensor /
Minimum temperature thermostat
Factory fitted thermostat (built in) Valves for 2 pipes Valves for 4 pipes Heaters Parallel connection Water Min. Temp.
Thermostat
ON/OFF
Modulating
sensor
J3A2 (2p) J3AM (2p) J3A2 (4p) J3AM (4p) KREL CBL20 CBL30 WS TM
CSL00 Fan speed selector l l
CML00 Thermostat with manual fan speed and S/W
change over l l l l
CEL00 Thermostat with manual fan speed, dead band,
automatic change over l l l l l l
CEL20 Thermostat with automatic fan speed, dead band,
automatic change over l l l l l l
CEL30 Thermostat with automatic fan speed, dead band,
automatic change over for modulating valve l l l l l
Remote controllers and thermostats (wall mounted)
CSR00 Fan speed selector a l l
CMR00 Thermostat with manual fan speed and S/W
change over l l l l
CER00 Thermostat with manual fan speed, dead band,
automatic change over l l l l l l
CER20 Thermostat with automatic fan speed, dead band,
automatic change over l l l l l l
CER30 Thermostat with automatic fan speed, dead band,
automatic change over for modulating valve l l l l l
CSL00 (Built in)
CSR00 (Wall mounted)
Fan speed selector
CEL00 (Built in)
CER00 (Wall mounted)
Thermostat with manual
fan speed and automatic
change over
CEL20 (Built in)
CER20 (Wall mounted)
Thermostat with auto.
fan speed and automatic
change over
CEL30 (Built in)
CER30 (Wall mounted)
Thermostat with auto.
fan speed and automatic
change over for
modulating valve
CML00 (Built in)
CMR00 (Wall mounted)
Thermostat with manual
fan speed and S/W
change over

Compatibility Options / Accessories / Models
STANDARD LOW BODY
LASER CONCEALED
Code designation YLV YLH YLV-AF YLH-AF YLIV YLIH YLIV-AF YLIH-AF YLVR YLIVR
Coils and heaters**
BA1** Additionnal 1 row heating llllllllll
KREL** Kit electrical heater with safety thermostat and relay llllllll
Factory fitted thermostat
CSL00 Fan speed selector (buit in) llllllllll
CML00 Thermostat with manual fan speed and S/W change
over (buit in) l l
CEL00 Thermostat with manual fan speed, dead band,
automatic change over (buit in) Compatible with electrical heaters l l
CEL20 Thermostat with automatic fan speed, dead band,
automatic change over (buit in) Compatible with electrical heaters l l
CEL30 Thermostat with automatic fan speed, dead band,
automatic change over for modulating valves (buit in) l l
Remote controllers and thermostats
CSR00 Fan speed selector (wall mounted) llllllllll
CMR00 Thermostat with manual fan speed and S/W change
over (wall mounted) l l
CER00 Thermostat with manual fan speed, dead band,
automatic change over (buit in) Compatible with electrical heaters l l
CER20 Thermostat with automatic fan speed, dead band,
automatic change over (buit in) Compatible with electrical heaters l l
CER30 Thermostat with automatic fan speed, dead band,
automatic change over for modulating valves (buit in) l l
CBL20 Parallel connection for ON/OFF valve llllllllll
CBL30 Parallel connection for modulating valve llllllllll
Valves / Condensate pump / Water sensor / Minimum temperature thermostat (Factory fitted)
J3A2 (2p) 3-way 4-ports on/off valves for 2-pipe systems llllllllll
J3A2 (4p) 3-way 4-ports on/off valves for 4-pipe systems llllllllll
J3AM (2p) 3-way 4-ports modulating valves for 2-pipe systems llllllllll
J3AM (4p) 3-way 4-ports modulating valves for 4-pipe systems llllllllll
DT (2p) Shut-off valves for 2-pipe systems
(in addition to J3A2/J3AM valves) llllllllll
DT (4p) Shut-off valves for 4-pipe systems
(in addition to J3A2/J3AM valves) llllllllll
PC Condensate pump llllllllll
WS Water sensor Compatible with CEL/CER
TM Minimum temperature thermostat llllllllll
Feets and panels
CP1 Set of painted feet l l
ZL1 Set of feet + frontal socle l l
PPV1 Vertical painted back panel l l l
PPH1 Horizontal painted back panel l l
External air intake
PA Air intake plenum l
PAS Air intake plenum collars l
PA90° 90° air intake plenum l
RCA Air intake duct fitting l
PM Air delivery plenum with collars llll l
PM90 90° air delivery plenum llll l
lCompatible
Compatible with conditions
Not compatible
** Maximum of rows is indicated in the documentation, the maximum number of rows includes the heating row or electrical heater.
Compatibility tables for FCU
LASER and LOW BODY
Andere Handbücher für 110
1
Dieses Handbuch passt für folgende Modelle
14
Andere York Wassersystem Handbücher
Beliebte Wassersystem Handbücher anderer Marken

Spirotech
Spirotech SPIROVENT SUPERIOR S250 Bedienungsanleitung

Culligan
Culligan Aqua-Cleer Aqua-Cleer Advanced Drinking Water... Bedienungsanleitung

A.O. Smith
A.O. Smith Dura-Max AJH - 1000A - P Bedienungsanleitung

Microline
Microline T.F.C.-4 Handbuch

Eureka Forbes
Eureka Forbes Aquaguard Select Bedienungsanleitung

Cetetherm
Cetetherm AquaEfficiency Bedienungsanleitung