4.2 Possible parameters and factory presets
Description Adjustment range Factory presets
Primary voltage transformer
Identification plate, 400 V AC 1 V ... 999 kV 400 V
Identification plate, 110 V AC 1 V ... 999 kV 400 V
Secondary voltage transformer
Identification plate, 400 V AC 400 V, 110 V, 100 V400 V
Identification plate, 110 V AC 400 V, 110 V, 100 V400 V
Primary current transformer
Identification plate, 1 A1 A ... 999 kA 5 A
Identification plate, 5 A1 A ... 999 kA 5 A
Secondary current transformer
Identification plate, 1 A1 A, 5 A5 A
Identification plate, 5 A1 A, 5 A5 A
Integration time 5; 10; ... 870; 900 sec 900 sec
Switching output 1 (LIMIT 1)
Measured value U, I, f, P, Q, cos f,
Psum, Qsum, cos fsum,Wh, varh, h,
Channel L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1
L1-N/L2-N/L3-N, L1-L2/L2-L3/L3-L1
Response time 0 ... 60 sec
Limit value freely programmable
Alarm type min, max
Deactivation„AUS“
Switching output 2 (LIMIT 2)
Measured value U, I, f, P, Q, cos f ,
Psum, Qsum, cos fsum,Wh, varh, h,
Channel L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1
L1-N/L2-N/L3-N, L1-L2/L2-L3/L3-L1
Response time 0 ... 60 sec
Limit value freely programmable
Alarm type min, max
Deactivation „AUS“
Impulse output (optional)
Energy type active energy Wh active energy Wh
Energy flow direction received received
Impulse rate 1Wh ... 999 kWh / Impulse 100 Wh / Impulse
Delete functions Umin, Imax, Imean max, Pmax, Qmax, h,
Wh, varh, ALL
User password „000“ = no password
RS 485 (optional)
Baud rate 9.6 kBaud
Address
000 ... 999
9.6 ... 57.6 kBaud
0 ... 31 0