1. Introduction
Overview
Product coverage
This manual covers the MTS4-outdoor enclosure with all options including power back-
up supplied by batteries (product no. 352894) The MTS4-outdoor enclosure is based
on the Dantherm ICS 2000 platform.
Should you have required the Fuel Cell power backup solution with the MTS4-outdoor
enclosure (product no. 352895), the fuel cell and hydrogen handling and storage is not
covered in this manual, but is described in the IPSM-A1600 power backup module for
installation in the MTS4-outdoor enclosure manual (product no. 046234), 6866600D34,
which is a supplement to this manual (product no. 045893 –Motorola product no.
6866588D43).
WARNING
It is the responsibility of the operator to read and understand this service manual
and other information provided, and to use the correct operating procedures.
Read the entire manual before the initial start-up of the installation of the MTS4-outdoor
enclosure. It is important to know the correct operating procedures for the unit and all
safety precautions to prevent the possibility of property damage and/or personal injury.
Safety
The MTS4-outdoor enclosure including the IPSM-A1600 power backup system should
be protected against traffic accidents by a fence or a concrete barrier and obey all other
legal requirements for installation and storage of hydrogen high pressure bottles which
are not listed in this manual.
Ventilation re-
quirement
In case the MTS4-outdoor enclosure is placed indoor in
a closed room, the ventilation capability of the room
should minimum be in accordance with the battery
standard and battery manufactures recommendations.
This can be found on a label situated next to the batter-
ies (when installed).
The requirement is 0.19 m3/h.
When the cabinet is installed outdoor, no additional
ventilation is required with required degassing kit in-
stalled (tube system from battery valve to exterior)
through retaining grommet. Always check if this tube
has not been damaged or removed.
Left bay of the enclosure above the power distribution panel offers a 19” rack system
with 12RU available for auxiliary equipment.
It is important that any active component in the rack, including those components that
will be installed later in addition to Dantherm’s deliverable, must have a self-protecting
mechanism, which switches off the component in case of an overheat situation.
Further it is important that the heat dissipation of equipment installed do not exceed
200 W or max. permitted ambient temperature will have to be de-rated.
Continued overleaf

4
1.1 General information, continued
Table of contents
This installation manual covers the following main topics:
Topic
See page
1.1 General information
6
2. Product and functional description
8
2.1 MTS4-outdoor enclosure
9
2.2 Optional equipment
11
2.3 Power distribution panel
13
2.4 Heat exchanger –MHX 85
17
2.5 Door stop
20
3. Get ready for use
21
3.1 How to unpack and mount the MTS4-outdoor enclosure
22
3.2 How to install power to the MTS 4-outdoor enclosure
26
3.3 How to install the battery pack (backup power)
30
3.4 How to install the MTS4 into the outdoor enclosure
34
3.5 How to power up the MTS4-outdoor enclosure (cold start)
38
4. Service guide
41
4.1 Preventive maintenance
42
4.2 Spare parts
44
4.3 Fault finding
56
4.4 Service agreement
57
5. Technical information
58
5.1 Technical data, MTS4-outdoor enclosure
59
5.2 Technical data, MHX 85 heat exchanger
61
5.3 Wiring diagram, MHX 85 heat exchanger
64
5.4 Wiring diagrams MTS4-outdoor enclosure –power
distribution panel
65
5.5 References for the wiring diagrams
73
Appendix A - Mounting template
75
Appendix B - MTS4-outdoor enclosure check list
76
Continued overleaf

5
045893 •Version 2.3 • 16.03.2012
1.1 General information, continued
Revisions
This is the revision history of this manual:
Date
Section
Change
11/2-10
20/5-10
16/3-12
1
2.3
2.3
2.3
2.4
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
5.4
2
2.1
2.1
2.3
5.5
5.5
2.3
3.5
4.2
Changed number
Changed alarm names, new column 4 and 1st row added
Alarm pin layout changed
Operation of Generator switch, added
Control system, “max.” added
Dantherm part 046392, description changed/added
Dantherm part 046398, description changed/added, new illustr.
Dantherm part 046400, description changed/added
Dantherm part 046496, description changed/added
Dantherm part 060575, description changed/added
Dantherm part 062905, added
Dantherm part 064624, added
Dantherm part 064627, added
Dantherm part 064628, added
Dantherm part 064629, added
Dantherm part 064630, added
Dantherm part 064631, added
Dantherm part 064632, added
Dantherm part 064633, added
Dantherm part 064634, added
Dantherm part 064635, added
Dantherm part 064636, added
Wiring diagrams changed, and new added
Illustration changed
Illustration changed
New text in line 1 on page 10
Minor text changes page 15
Minor text changes page 72
Wire colors added
Illustrations with generator switch updated
Illustrations with generator switch updated
Illustrations with generator switch updated. Added new supply
switch kit.

6
1.1 General information
Introduction
This section gives the general information about this service manual and about the
MTS4-outdoor enclosure.
Manual,
part number
Part number of this service manual is 045893.
For Fuel Cell power backup option: please see the manual IPSM-A1600 power backup
module for installation in the MTS4-outdoor enclosure (product no. 046234).
Target group
The target group for this service manual is the technicians who install, maintain, and
exchange parts on the unit.
Copyright
Copying of this service manual, or part of it, is forbidden without prior written permis-
sion from Dantherm Air Handling A/S.
Reservations
Dantherm Air Handling A/S reserves the right to make changes and improvements to
the product and the service manual at any time without prior notice or obligation.
MTS4-outdoor en-
closure
Dantherm Air Handling A/S, Marienlystvej 65, DK-7800 Skive hereby declare that the
product mentioned below:
Product No.: 352894 MTS4 outdoor enclosure basis
and the 2 versions below with enclosure extensions for storage
352895 MTS4 outdoor FC-5
352896 MTS4 outdoor FC-3
are in conformity with the following directives covering the provisions of the normative
European Council Directives:
2006/42/EC Directive on the safety of machines
2006/95/EC Low Voltage Directive
2004/108/EC EMC Directive
Description: MTS4 outdoor enclosure is a 2 door steel based outdoor enclosure
equipped for accommodating and servicing an MTS4 radio base station. The enclosure
has multiple configurations ranging from a standard configuration with only a basic set-
up up to a full integrated option list as defined in the service manual no 045893. Basis
is equipped with a door mounted heat exchanger (CE marked), a power distribution
panel (CE-marked) and internal cables, cabin lights, a backup installation (battery pack
using VRLA size batteries (optional)), battery charger, surge arrestors etc. Items not
listed in the service manual are not covered by this declaration.
The versions 352895 and 352896 with enclosure extensions for storage also offers a
power backup system (IPSM-A1600) based on fuel cell technology using hydrogen as
energy source. This backup system is CE-marked and further described in manual p/n
046614.
and Manufactured in conformity with the following harmonised standard:
EN60529:2001 IP55 (Degree of protection provided by enclosures)
EN 12000-1:2005 Safety of machinery –Part 1: Basic terminology
EN 12000-2:2005 Safety of machinery –Part 2: Technical principles
EN 60 950-1:2006 Installation safety (CB by Intertek, ref: 714719-01)
EN 60 950-22:2006Information technology equipment - Safety - Part 22:
Equipment installed outdoors
EN50272-2:2001 Battery installation
Continued overleaf

7
045893 •Version 2.3 • 16.03.2012
1.1 General information, continued
MTS4-outdoor en-
closure
, continued
EN 61 000-2:2005 Immunity
EN 61 000-3:2007
+A11:2004 Emission (EN 55022 version:
1998+A1:200+A2:2003_Class B)
ETSI EN 300 019-2-1 v2.1.4
Storage: not temperature controlled storage locations:
T 1.2
ETSI EN 300 019-2-2 v2.1.2
Transportation: public transportation. T2.3
ETSI EN 300 019-2-4 v2.2.2
In use: non-weather protected locations T 4.1 (or T4.1E)
ETSI ETS 300 753 october 1997
Acoustic noise
It is further declared that the installation and commissioning of MTS4 base station and
site installation are not covered by to this declaration.
Skive, 11.06.2008
Recycling
The MTS4-outdoor enclosure is designed to last for many years. When the time
comes for the unit to be recycled, the unit should be recycled according to national
rules and procedures to protect the environment.

8
2. Product and functional description
Overview
Introduction
This section will give you a product and functional description of the MTS4-outdoor en-
closure.
A detailed description of the MTS4-outdoor enclosure is to be found on the following
pages.
Illustration
This illustrates the MTS4-outdoor enclosure with the MHX 85 (heat exchanger unit)
hanging on the right door:
Content
This section covers the following topics:
Topic
See page
2.1 MTS4-outdoor enclosure
9
2.2 Optional equipment
11
2.3 Power distribution panel
13
2.4 Heat exchanger –MHX 85
17
2.5 Door stop
20

9
045893 •Version 2.3 • 16.03.2012
2.1 MTS4-outdoor enclosure
Introduction
This section will give you a description of the MTS4-outdoor enclosure and its function-
ality.
The MTS4-outdoor enclosure is designed to accommodate a Motorola MTS4 base sta-
tion, which is further described by Motorola, part number 6802800U74 “MTS2 and
MTS4 configuration, installation and service manual”. For more information please con-
tact Motorola.
The MTS4-outdoor enclosure is designed to withstand rough environment and many
years of service. Basis is a welded steel frame with dismountable side panels with pro-
tected double gaskets for protecting the sealed environment inside.
Illustration
This illustrates where the basic parts are installed in the MTS4-outdoor enclosure:
Continued overleaf

10
2.1 MTS4-outdoor enclosure, continued
Parts
This table gives information about the basic parts installed in the MTS4-outdoor enclo-
sure:
Part
1
Plinth with removable painted cover panels including front access to generator
cable
2
Drain system
3
Shelf for storing battery pack
4
Basic cable routing for specified equipment
5
Double 19” rack system in left bay
6
Door stop system
7
Internal insulation panels
8
Dismountable painted protection roof
9
RF protection cover
10
Heat Exchanger mounted on right door
11
Cabinet with 2 doors with 3 position swing lock system with stainless steel
swing handle with key system
12
Air divider plate for MTS4
13
Mounting system for MTS4
14
Cable glands in bottom plate
15
Power distribution panel with protection cover
Inhaltsverzeichnis