FlexStat 10 Operation Guide, Rev. K
(Advanced) Security Levels and Passwords
SECURITY
ACCESS LEVELS
PASSWORDS
ACCESS LEVELS
SETPOINT ADJ:
MAIN MENU: ADMIN
SYSTEM MODE: OPER
OCC OVERRIDE: USER
FAN OCC/UNOCC: OPER
NONE PASSWORDS
USER:
OPERATOR:
ADMIN:
1 0 0 0
1 2 3 4
5 6 7 8
AccesstotheMainMenu,SetpointAdjust,and
System/Occupancy/Fanseingshaveadefault
passwordlevelofUser.Thislevelcanbechangedfor
eachfunctiontoNone,Operator,orAdministrator
throughtheAccessLevelsmenu.Passwordsareset
inthePasswordsmenu.
Anypersoncanviewthedisplaybutmightnotbe
abletochangeanyseingswithoutlogginginwith
oneofthethreelevelsofpasswords:
• None(Level“0”):Nopasswordisrequired
(everyonehasaccess).(Forexample,anyonecan
adjustasetpointwithAccessLevelNoneevenif
allotherfunctionsrequireapassword.)
• User(Level1):SeetheMenuItemsAccessLevels
chart.
• Operator(Level2):SeetheMenuItemsAccess
Levelschart.
• Administrator(Level3): Canaccessallmenus
andchangealleditablevalues.DO NOT
FORGET THIS PASSWORD!
NOTE: Seing a password to (the default) 0000
eliminates the password prompt and
allows full access for that level. If no
password is set for ADMIN, no password
prompt will occur. If any password is set
for ADMIN, the menu items accessible
at the various levels are shown in the
following chart.
NOTE: Changes in security levels and/or
passwords take eect when the current
Administrator log-in has timed out. Log-
inslastuntil60seconds(default)aer
thelastbuonpress.Desiredlengthof
inactivitytime-outcanbechangedinthe
Systemssubmenu.
NOTE: Whenseingapassword,theUpbuon
increasesthealphanumericvalue(0
through9andthenAthroughZ).The
Downbuondecreasesthevalue.DO NOT
FORGET THE ADMIN PASSWORD!
Toenteranalphanumericpasswordattheprompt:
1. Up/Downtomove.
2. Entertoselect.
3. Up/Downtoincrement/decrementvalue.
Therequiredpasswordlevelisspeciedinthe
prompt.
Tolock the buonsaercongurationiscomplete
(anddisablefurtherchanges),selectLockedUI
mode.See(Advanced) User Interface (UI) Modes on
page 12.
Foradditional physical security and protection
from vandalism,installtheFlexStatinsideathird-
partylockingthermostatguard/cover(butproper
airowmustbemaintained).
Menu Items Access Levels
Menus User Operator Administrator
Home Screen * = Selectable, Default is User
Setpoint Adjust (Up/Down) x* x* x*
System Mode (Auto/Heat/Cool/Off) x* x* x*
Occupancy Override (On/Off) x* x* x*
Fan Modes (Auto/On/Off) x* x* x*
Main Menu* (Default is User)
About x x x
Advanced x x
Alarm x x
Date/Time x x
Schedule x x
Setpoints x x
System x x
Trend Viewer x x x
Advanced Menu
Application x
Additional Setup x
Control Basic Programs x x
Communication x
Date/Time x x
Device x
Inputs x x
Limits x x
Motion Sensor x x
Security x
Trend Logs x x
Test x x
This chart shows conditions in which an administrator password is set
(is not 0000) and default password levels are used.
NOTE!
To erase a forgotten password:
1. Connect to the FlexStat using TotalControl (BACstage won’t work).
2. Open File Object [FILE133001] ui.cfg.
3. Change File Size to 0 and Save Changes.
4. Restart the FlexStat.