5
a) Measured pressure shall not be beyond the scope of transmitter
pressure range;
b) Media should be compatible with the contacting parts of transmitter;
c) Be sure the pressure hole shall not be blocked by media.
3.2.2 Installation procedure for Pressure transmitter
The transmitter usually is installed upward and perpendicular to the
horizontal direction. If the condition is limited, it is allowed to install the
transmitter at most 30 degrees angel with the horizontal direction. a
shut-off valve is suggested to mounted between the flange and pipe for
easier installation and maintenance. The hexagonal nut at the
connection between the housing and the base of the MPM4760 can be
used to adjust the face orientation of the meter. H is high pressure
interface, L is low pressure interface. Three valves manifold are
recommended for differential pressure products to protect the transmitter.
Notes: Pushing or poking the pressure hole with iron wire, steel pin and
other hard objects, and pushing diaphragm by hand are forbidden to
keep diaphragm from damage or deformation. Note the interface of
differential pressure transmitter.
Installation (suggested) as below:
Figure 3.1