Olsen ODVB Series Leitfaden

USER'S
INFORMATION
MANUAL
P/N 37616001, Rev. B [3/2011]
SERIES O
DVB
GAS FIRED HOT WATER HEATING BOILER
WARNING: If the information in this manual is not
followed exactly, a re or explosion may result causing
property damage, personal injury or loss of life.
Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.•
Do not touch any electrical switch; do not use•
any phone in your building.
Immediately call your gas supplier from a •
neighbor's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the •
re department.
Installation and service must be performed by a
qualied installer, service agency or the gas
supplier.
Do not use this boiler if any part has been under water. Immediately call a qualied service technician to
inspect the boiler and to replace any part of the control system and any gas control which has been under
water.
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to
the pump. Instead, shut off the gas supply at a location external to the appliance.
ECR International
2210 Dwyer Avenue, Utica NY 13504-4729
Phone: (315) 797-1310 • Fax: (866) 432-7329
e-mail: [email protected]
web site: www.ecrinternational.com

2
USERS INFORMATION MANUAL
INSTRUCTIONS FOR OPERATION AND MAINTENANCE
OF GAS FIRED HOT WATER HEATING BOILER
RETAIN FOR FUTURE REFERENCE
SAFETY SYMBOLS & WARNINGS
The following dened symbols are used throughout
this manual to notify the reader of potential hazards of
varying risk levels.
DANGER
!
DANGER
Indicates a hazardous situation which, if
not avoided, WILL result in death or serious
injury.
NOTICE
Indicates information which should be
followed to ensure proper installation and
operation.
!
WARNING
Indicates a hazardous situation which, if
not avoided, could result in death or serious
injury.
!
CAUTION
Indicates a hazardous situation which, if not
avoided, may result in minor or moderate
injury.
Olsen Boilers recommends all boiler maintenance be
performed by a trained heating technician.
Before any procedures are attempted on this appliance,
it is necessary to determine if the ignition system is a
electric or standing pilot system. If you are uncertain,
contact the manufacturer before proceeding.

3
LIGHTING INSTRUCTIONS
!
WARNING
Before lighting any type of pilot burner
(standing or intermittent), make certain the
hot water boiler and system are full of water
to minimum pressure of 12 lbs. per square
inch in the system, and also make certain
that the system is vented of air. Refer to the
following appropriate lighting instruction.
LIGHTING PROCEDURE FOR BOILER WITH
INTERMITTENT PILOT SYSTEM
!
WARNING
If you do not follow these instructions exactly,
a re or explosion may result causing property
damage, personal injury or loss of life.
This appliance is equipped with an ignition device which A.
automatically lights the pilot. Do not try to light the
appliance by hand.
Before operating, smell all around the appliance area B.
for gas. Be sure to smell next to the oor because
some gas is heavier than air and will settle on the oor.
Read "What To Do If You Smell Gas" on front page of
this manual.
Use only your hand to push in or turn the gas control C.
knob. Never use tools. If the knob will not push in
or turn by hand, don’t try to repair it, call a qualied
service technician. Force or attempted repair may
result in a re or explosion.
Do not use this appliance if any part has been under D.
water. Immediately call a qualied service technician
to inspect the appliance and to replace any part of the
control system and any gas control which has been
under water.
E.
F.
Operating Instructions For Intermittent Pilot
System
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to
light the pilot by hand.
5. Remove jacket front panel.
6. Turn gas control knob clockwise to “OFF.”
See Figure 1.
7. Wait (5) minutes to clear out any gas. If you then
smell gas, STOP! Follow “What To Do If You Smell
Gas” on front cover of this manual. If you don’t smell
gas, go on to the next step.
8. Turn gas control knob counterclockwise to
“ON.”
9. Replace jacket front panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the
instructions “To Turn Off Gas To Appliance” on page
5 and call a qualied service technician or your gas
supplier.
Figure 1 - Intermittent Pilot

4
LIGHTING INSTRUCTIONS
To Turn Off Gas To Appliance
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if
service is to be performed.
3. Push in gas control knob slightly and turn
clockwise to "OFF." DO NOT FORCE.
GENERAL INSTRUCTIONS
Before seasonal start-up, have a qualied service agency
check the boiler for soot and scale in the ues, clean
the burners and check the gas input rate to maintain
high operating efciency.
!
CAUTION
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation.
Verify proper operation after service.
The service agency or owner should make certain the
system is lled with water to minimum pressure and
open air vents, if used, to expel any air that may have
accumulated in the system. Check the entire piping
system and, if any leaks appear, have them repaired.
Figure 2 - Circulator
Many circulators like the one pictured in Figure 2
(above) require periodic servicing. The motor usually
has openings at each end to lubricate the bearings.
Put about one half teaspoon of SAE 20 or 30 non-
detergent motor oil in each opening twice a year.
!
CAUTION
Do Not Over Oil!!
Many circulators have an oil opening for the shaft
bearing. This should be oiled at the same time for quiet
operation. Follow the manufacturer's instructions for
oiling the shaft bearing.
The venting system should be inspected at the start
of each heating season. Check the vent pipe from the
boiler to the chimney for signs of deterioration by rust
or sagging joints. Repair if necessary. Remove the
vent pipe at the base of the chimney or ue and using
a mirror, check vent for obstruction and make certain
the vent is in good working order.
Figure 3 - Boiler Flue Gas Passageways
BURNERS
ORIFICES
GAS VALVE
HOLD DOWN
BOLT
FLUE
COLLECTOR
VENTER
ASSEMBLY
A1795
Note Some gas control knobs cannot be turned
from "PILOT" to "OFF" unless knob is pushed in
slightly. DO NOT FORCE.
4. Replace access panel.

5
GENERAL INSTRUCTIONS
Before seasonal start up it is advisable to have a certied
service agency check the boiler for soot and scale in the
ues, clean the burners and check the gas input rate to
maintain high operating efciency. The service agency
should make certain the system is lled with water to
minimum pressure and open air vents - if used - to expel
any air that may have accumulated in the system. The
entire piping system should also be checked and if any
leaks appear, they should be repaired immediately.
The venting system should also be inspected at the start
of each heating season. The vent pipe from the boiler
should be checked for signs of deterioration or sagging
joints. Repair if necessary.
The following procedure should be followed to clean and
check the ue gas passageways:
Remove the burners from the combustion chamber 1.
by raising the burners 1. up from the manifold
orices and pulling toward the front of the boiler,
(See Figure 4)
Disconnect the vent pipe from the vent adapter.2.
Remove the jacket front panel. (See Figure 5)3.
Check venter assembly suction pressure.4.
Connect a slope manometer between the venter •
and the pressure switch with a tee and additional
tubing and connectors.
Turn the boiler on and read suction pressure on •
the manometer. Reading should be negative (-)
.55 ± .05 inches of water column or higher for
the DV50 thru 150 and negative (-) .65 ± .05
inches of water column or higher for the DV200.
If this reading is not attainable, contact a certied
service agency.
Remove the ue collector and venter assembly 5.
from the boiler castings by loosening the hold-down
bolts located on each side of the ue collector. (See
Figure 3)
Visually inspect the venter assembly for any unusual 6.
wear or dirt build up.
If venter has oil cups lubricate venter motor once a 7.
month during the heating season with a few drops
of nondetergent motor oil (SAE 20 or 30). Do not
over oil.
Place a sheet of heavy paper or similar material in 8.
the bottom of the combus8. tion chamber and brush
down the ue passageways. The soot and scale will
collect on the paper and is easily removed with the
paper.
A visual check of the main burner and pilot ames
should be made at the start of the heating season and
again in mid-season.
The main burner ame should have a well dened inner
blue mantel with a lighter blue outer mantel. (See
Figure 6) If the ame does not appear this way, check
the burner throats and burner orices for lint or dust
obstructions.
The pilot ame should envelop 3/8 to 1/2 inch of the
tip of the ignition electrode. To adjust the pilot ame,
remove the pilot adjustment cover screw on the gas valve
and turn the inner screw clockwise to decrease
or counterclockwise to increase the pilot ame.
See Figure 1. Be sure to replace the cover screw after
adjustment to prevent possible gas leakage.
The burners and pilot should be checked for signs of
corrosion, rust or scale build-up, and cleaned with a
nylon bristle brush.
The area around the boiler must be kept clear and free
of combustible materials, gasoline and other ammable
vapors and liquids.
The free ow of combustion and ventilating air to
the boiler and boiler room must not be restricted or
blocked.
In the event the ow of combustion products through
the ueways or the boiler venting system becomes
blocked, a ame roll-out safety switch will shut off the
main burner gas. See Figure 5. If this condition occurs,
do not attempt to place the boiler in operation. Contact
a qualied service agency.
It is suggested that a certied service agency be
employed to make an annual inspection of the boiler
and heating system. They are experienced in making
the inspection outlined above and in the event repairs
or corrections are necessary, they can make the proper
changes for safe operation of the boiler.

6
GENERAL INSTRUCTIONS
Figure 6 - Burner Flame
Figure 4 - Burners, Burner Orices
GAS VALVE
ORIFICES
BURNERS
Figure 5 - Boiler Front with Safety Switch
COMBUSTION
BURNER
(REMOVED)
BURNERS GAS
VENT PIPE
CHAMBER
DOOR
VALVE
ADAPTER
ROLL-OUT SAFETY
BURNER
SWITCH
JACKET
FRONT
PANEL
Figure 7 - Burners Pilot Flame
IGNITION ELECTRODE
3/8” TO 1/2”
IN FLAME

7
NOTES

8
NOTES
Date of Installation:
Boiler Model #:
Installed By:
ECR International
2210 Dwyer Avenue, Utica NY 13504-4729
Phone: (315) 797-1310 • Fax: (866) 432-7329
e-mail: [email protected]
web site: www.ecrinternational.com
Inhaltsverzeichnis
Andere Olsen Kessel Handbücher

Olsen
Olsen OBC II Series Gebrauchsanweisung

Olsen
Olsen ODV-B Bedienungsanleitung

Olsen
Olsen OLSSC-075 Gebrauchsanweisung

Olsen
Olsen OBC Series Technisches Dokument

Olsen
Olsen OLSSC-050 Gebrauchsanweisung

Olsen
Olsen OSW Bedienungsanleitung

Olsen
Olsen OMGC-8D Gebrauchsanweisung

Olsen
Olsen OQ95M-200 Bedienungsanleitung
Beliebte Kessel Handbücher anderer Marken

Vaillant
Vaillant uniSTOR VIH SW GB 500 BES Bedienungsanleitung

Radijator
Radijator BIO max 23.1 Bedienungsanleitung

Brunner
Brunner BSV 20 Bedienungsanleitung

Buderus
Buderus Logamax GB062-24 KDE H V2 Bedienungsanleitung

Potterton
Potterton 50e Datenblatt

UTICA BOILERS
UTICA BOILERS TriFire Bedienungsanleitung











