Quick Start Manual Rev 2.45 - Software Versions 3.xx
003R-620-245 Page 21
GROUP
(GRP)
ITEM
(ITM)
SELECT
(SEL)
EDIT
(EDT)
Underline = Defaults
OK
CAL
(continued) ED.LIN⊗
(K302 only)
Edit Linearisation Points
Set between zero and full
scale
L1. - - - Select Linearisation
point 1 to 10 (L1, L2, L3, L4,
L5, L6, L7, L8, L9, L10).
(Approx. % of full scale)
<SEL> to step through list of points.
<OK> to change selected point or <ITM> to exit.
After <OK> current weight displays.
Add test weight.
<OK> to enter corrected weight. <SEL> changes position,
<EDT> changes digit.
<OK> starts routine (L.in P displays).
<ITM> key to exit, <OK> to repeat routine.
CLR.LIN⊗
(K302 only)
Clear Linearisation Points
L1. - - - Select Linearisation
point 1 to 10 (L1, L2, L3, L4,
L5, L6, L7, L8, L9, L10)
<SEL> to step through list of points.
<OK> to select point to clear or <ITM> to exit.
After <OK> press <ITM> to choose Cont. Y (Yes) or Cont. N
(No).
<ITM> to return to CLR.LIN.
DIR.ZER⊗
Direct Zero Calibration
(Current weight displays)
<OK> key to start. Current weight displays.
<OK> to enter direct zero setting (in mV/V).
<SEL> changes position, <EDT> changes digit.
<OK> key to store new zero calibration.
<ITM> to exit or <OK> to repeat operation.
DIR.SPN⊗
Direct Span Calibration
(Current weight displays)
<OK> key to start. Current weight displays.
<OK> to enter direct span setting (in mV/V).
<SEL> changes position, <EDT> changes digit.
<OK> key to store new span calibration.
<ITM> to exit or <OK> to repeat operation.