Selec PIC352 Bedienungsanleitung

Process Indicator
Selec Controls Pvt. Ltd., India
Tel.: +91-22-4141 846 / 452, Fax: +91-22-41418 408
Website: www.selec.com
Email: [email protected]
PIC352
OPERATING INSTRUCTIONS
Doc. name: OP INST PIC352 OP3023-V01

CONTENTS
Page no.
8. Level 5-lockout module 20
E) CALIBRATION CERTIFICATE 21
7. Level 4-Communication module 19
6. Level 3-Analog o/p & special function module.... 17
5. Level 2-Alarm module (Alarm 2) 15
2. Terminal connections 8
A) OVERVIEW.
1. Features 1
2. Ordering information 2
3. Level 0-Input parameters 13
2. Key's description 12
B) SPECIFICATIONS 3
1. Function menu 11
D) PROGRAMMING.
1. Safety Information 6
4. Level 1 Alarm Module (Alarm 1) 14
C) INSTALLATION.
3. Sensor input wiring 9
4. Output wiring 9

www.selec.com
1
OVERVIEW
96x96mm
SALIENT FEATURES
vOutputs:
0 to 20mA, 4 to 20mA, 0 to 10V & 0 to 5V for Retransmission & Manual output
vUniversal I/O:
Inclusion of all possible inputs and outputs in a single product with high precision sensing & low temperature
drift
vSpecial Features:
vCustomized Upper 4 Digit Alpha-Numeric Display:
User can edit each digit as per requirements
ŸProgrammable backlight as per Alarm
Ÿ24V, 100mA sensor supply for transmitter modules
Ÿ2 SPDT Relays for Alarm Actuation
ŸSingle key Auto / Manual switching
vSensor break indication
vDigital filtering
v90 to 270 VAC/DC supply
vDual 4 digit display
Others
vSensor error compensation
vProgrammable parameter lockouts
vIP65 front panel protection
vRS485 MODBUS communication
Optional Features
vCompliance -

OVERVIEW
2. ORDERING CODE
PIC352-11-U-C-1
1) Universal Input
2) 2 Number of SPDT Relays
3) Analog Output Current & Voltage
4) RS485 Slave Communication
PIC352-11-U-X-1
1 85-270 VAC/DC
2 12-24 VAC/DC
C RS485 Slave Communication
0 No RS485 Slave Communication
0 LED
1 LCD
0 Standard
1 Precision I/O
PIC352-11-U-0-1
1) Universal Input
3) Analog Output Current & Voltage
2) 2 Number of SPDT Relays
1. TECHNICAL SPECIFICATIONS
1. DISPLAY
Display
PIC352 - 96X96- 4 digit Alphanumeric and 4 digit 7-Seg LCD with Selectable Multicolor Backlight as per user
requirements.
Led Status Annunciators OUT1, OUT2, MAN (Manual)
www.selec.com
2

SPECIFICATION
www.selec.com
3
Input
Thermocouple : J, K, T, R, S, C, E, B, N, L, U, W, Platinel II.
RTD : PT100, PT1000
Signal inputs : -5 to 90mV,0 to 10VDC,0 to 20mA DC
(Programmable scale type)
Sampling time 60 ms.
Resolution 1 / 0.1° for TC / RTD.
1 / 0.1 / 0.01 / 0.001 for Analog input. (Decimal point position)
Indication accuracy
Current : 0.1% at 25°C
TC Input : 0.1% of span at 25°C
R&S Input : 0.25% of span at 25°C
RTD Input : 0.1% at 25°C
Voltage : 0.1% at 25°C
Digital filtering OFF, 1 to 99 sec.
Relay contact output Relay 1, Relay 2 : 10A@250VAC or 28VDC
Life expectancy : 50000 cycles at maximum load rating
2. INPUT
3. ALARM OUTPUT
3.1. RETRANSMISSION OUTPUT
Resolution 2uV approx for AOV and 2uA approx for A01
Current output
Range : 0 / 4-20mA
Action : Retransmission
Update rate : 100ms,Maximum output load resistance : 500E
Voltage output
Range : 0-5 / 10V
Action : Retransmission
Update rate : 100msec
Minimum output load resistance : 10k
1. TECHNICAL SPECIFICATIONS
1. DISPLAY
Display
PIC352 - 96X96- 4 digit Alphanumeric and 4 digit 7-Seg LCD with Selectable Multicolor Backlight as per user
requirements.
Led Status Annunciators OUT1, OUT2, MAN (Manual)

SPECIFICATION
www.selec.com
4
Interface standard RS485
Communication address 1 .... 99, maximum of 32 units per line
Transmission mode Half duplex
Transmission protocol MODBUS RTU
Transmission distance 500m maximum
Transmission speed 115200,57600,38400,19200,9600,4800,2400 bits/sec.
Parity None, Odd, Even
Stop bits 1 or 2
Response time 100ms (max and independent of baud rate)
5. SERIAL COMMUNICATION
Operating range
Storage range
Storage humidity
0.....55°C
-20.....75°C
85% max. RH (non condensing) from 0 to 50°C
6. ENVIRONMENTAL CONDITIONS
Power supply 90.....270VAC / DC
Frequency 50 / 60Hz
Power consumption 8VA max
7. POWER SUPPLY
Auto / Manual Concept
User can switch from manual analog 0/P to retransmission mode
by pressing A/M key for 5sec. when in online mode.
NOTE : User must feed the manual output % in HAND level 3
4. FUNCTION
Alarms
Modes : Alarm high, Alarm Low, Band, Serr
Hystersis : Programmable
Annunciator : Programmable
Reset Action : Programmable-Automatic or latched
Standby(Hold) : Programmable-Enable or disable
Pdly : Power ON delay
Rdly : Restart time delay

SPECIFICATION
www.selec.com
8
Sensor type Range
J -200 to 750°C E -200 to 750°C
K -200 to 1350°C B +149 to 1820°C
T -200 to 400°C N -200 to 1300°C
R 0 to 1750°C L -200 to 600°C
S 0 to 1750°C U -200 to 900°C
C 0 to 2300°C W 0 to 2300°C
Platinel II 0 to 1390°C PT100 -200 to 850°C
PT1000 -200 to 850°C
Signal inputs:
WEIGHT : PIC352-11-U-X-1 : 200gms
10. HOUSING : Flame retardant engineering plastic
11. INPUT SENSOR RANGES (for 1°C resolution)
Sensor type Range
Input type Range
Linear mV -5 to 90mV
Voltage 0 to 10VDC
Current 0 to 20mA
Compliance CE
LVD As per BS EN 61010
EMC As per BS EN 61326
Panel sealing IP65
9. SAFETY AND EMC STANDARDS
AC line w.r.t. all inputs and outputs 2500Volts
All other inputs and outputs w.r.t. Relay contacts 2500VAC
8. ISOLATION BREAKDOWN RATINGS

INSTALLATION
SAFETY SUMMARY
This manual is meant for the personnel involved in wiring, installation, operation, and routine
maintenance of the equipment. All safety related codifications; symbols and instructions that appear in this operating
manual or on the equipment must be strictly followed to ensure the safety of the operating personnel as well as the
instrument. If the equipment is not handled in a manner specified by the manufacturer it might impair the protection
provided by the equipment.
CAUTION : Read complete instructions prior to installation and operation of the unit.
CAUTION : Risk of electric shock.
1. SAFETY INFORMATION
INSTALLATION INSTRUCTION
CAUTION :
3. Circuit breaker or mains switch must be installed between power source and supply terminals to facilitate
power 'ON' or 'OFF' function. However this switch or breaker must be installed in a convenient position
normally accessible to an A operator.
2. Conductors must not come in contact with the internal circuitry of the equipment or else it may lead to a
safety hazard that may in turn endanger life or cause electrical shock to the operator.
1. This equipment, being built-in-type,normally becomes a part of the main control panel and in such case
the terminals do not remain accessible to the end user after installation and internal wiring.
MAINTENANCE
1. The equipment should be cleaned regularly to avoid blockage of ventilating parts.
2. Use soft cloth for cleaning. Do not use isopropyl alcohol or any other organic cleaning agent.
4. Thermal dissipation of equipment is met through ventilation holes provided on chassis of equipment. Such
ventilation holes shall not be obstructed else it can lead to a safety hazard.
5. The output terminals shall be strictly loaded to the manufacturer specified values/range.
1. The equipment shall not be installed in environmental conditions other than those specified in this manual.
2. Fuse Protection - The equipment does not contain built-in fuse. Installation of external fuse for electrical
circuitry is highly recommended. Recommended rating of such fuse shall be 275VAC/1 Amp.
3. Since this is a built-in type equipment (finds place in main control panel), its output terminals get connected
to host equipment. Such equipment shall also comply with basic EMI/EMC and safety requirements like BS
EN 61326-1 and BS EN 61010 respectively.
CAUTION :
www.selec.com
6

INSTALLATION
WIRING INSTRUCTION
1. To prevent the risk of electric shock power supply to the equipment must be kept OFF while doing the
wiring arrangement.
2. Terminals and electrically charged parts must not be touched when the power is ON.
3. Wiring shall be done strictly according to the terminal layout with shortest connections. Confirm that all
connections are correct.
4. Use lugged terminals to meet M3.5 screws.
5. To eliminate electromagnetic interference use of short wire with adequate ratings and twists of the
same in equal size shall be made.
6. Cable used for connection to power source, must have a cross section of 1 or greater. These wires
shall have insulation capacity made of at least 1.5KV.
CAUTION :
2. Remove the clamp from the controller.
3. Push the controller into the panel cutout. Secure the controller in its place by pushing the clamp
from the rear side.
The equipment in its installed state must not come in close proximity to any heating sources, caustic
vapors, oils, steam, or other unwanted process by-products.
ELECTRICAL PRECAUTIONS DURING USE
Electrical noise generated by switching of inductive loads can create momentary disruption, erratic display,
latch up, data loss or permanent damage to the instrument.
To reduce noise :
A) Use of MOV across supply of temperature controller & snubber circuits across loads are recommended.
Part number are as follows :
1. Snubber : APRC-01
B) Use separate shielded wires for inputs.
C) The unit should preferably be shielded from the contactor
INSTALLATION GUIDELINES
Mechanical Installation :
For installing the controller
1. Prepare the panel cutout with proper dimensions as shown.
OVERALL DIMENSIONS (All dimensions in mm)
Panel Cutout
99
99 45.5
64
4
10
55 90.5
90.5
CAUTION :
www.selec.com
7

INSTALLATION
PIC352-11-U-C-1
1. Use proper input power cables with shortest connections and twisted type.
2. Layout of connecting cables shall be away from any internal EMI source.
EMC Guidelines :
2. TERMINAL CONNECTIONS
Digital input
Sensor supply
NPN / PNP
24VDC, 80mA Analog input
PIC352-11-U-0-1
www.selec.com
8
Dieses Handbuch passt für folgende Modelle
1
Inhaltsverzeichnis
Andere Selec Messgerät Handbücher

Selec
Selec MX300-1-C-CE Bedienungsanleitung

Selec
Selec EM306 Bedienungsanleitung

Selec
Selec MFM374 Bedienungsanleitung

Selec
Selec EM306A Bedienungsanleitung

Selec
Selec APFC146 Bedienungsanleitung

Selec
Selec MV Series Bedienungsanleitung

Selec
Selec EM306A Bedienungsanleitung

Selec
Selec MFM376 Series Bedienungsanleitung

Selec
Selec APFC346 Bedienungsanleitung