Siemens SED2-LONI/F Bedienungsanleitung

Installation Instructions
Document No. 129-387
October 2, 2009
SED2 VFD LON Interface Option
Item Number 129-387, Rev. BA Page 1 of 3
Product Description
The LONMARK® certified SED2 VFD LON Interface
Option (LON Interface) provides direct digital control of
SED2 Variable Frequency Drives (VFDs). The LON
Interface resides on a LONWORKS® network with
LONMARK products from multiple vendors.
Product Numbers
SED2-LONI/F, includes SED2 VFD LON Interface
Option, and CD-ROM with files and operating
instructions.
Warning/Caution Notations
WARNING:
Personal injury/loss of life may
occur if you do not perform a
procedure as specified.
CAUTION:
Equipment damage, or loss of
data may occur if you do not
perform a procedure as specified.
Installation
SED2 VFD Frame Sizes A, B, and C
WARNING:
Make sure that the SED2 VFD is
de-energized (off) before you install or
remove the LON Interface Option.
1. Remove the SED2 VFD operator panel.
2. Install the LON Interface on the SED2 VFD I/O
module (Figure 1) by inserting two bottom guides
into appropriate slots at the sides of the I/O
module and pushing the upper section inward
until the locking mechanism latches.
3. Route the network cable (without connector) to
the LON Interface.
4. Terminate the end of network cable with a single,
two-pin, female LONWorks FTT-10A connector.
5. Attach the network cable FTT-10A connector to
connector at bottom of LON Interface (Figure 2).
6. Reinstall SED2 VFD operator panel on LON
Interface.
Figure 1. Installing LON Interface Option on SED2 VFD
Frame Sizes A, B, and C.
Figure 2. Network Connection on Bottom of
LON Interface Option.
SED2
VFD
L
ON
INTERFACE
OPTION

Document No. 129-387
Installation Instructions
October 2, 2009
Page 2 of 3 Siemens Industry, Inc.
SED2 VFD Frame Sizes D, E, and F
WARNING:
Make sure that the SED2 VFD is
de-energized (off) before you install or
remove the LON Interface Option.
For frame sizes D, E, and F, the LON Interface mounts
inside the VFD housing.
1. Remove the SED2 VFD operator panel, side
cover, and bottom cover (Figures 3).
2. Disconnect operator panel extension module
(with ribbon cable) from control module by
pushing lever above extension module upwards
and simultaneously pulling extension module from
the upper sides and rocking it downward.
NOTE: Do not disconnect the ribbon cable.
3. Install the LON Interface on the control module
(Figure 4) by inserting two bottom guides into
appropriate slots at the sides of the control
module and pushing the upper section inward
until the locking mechanism latches.
4. Install the operator panel extension module on
LON Interface (Figure 4) by inserting two bottom
guides into appropriate slots at the sides of the
LON Interface and pushing the upper section
inward until the locking mechanism latches.
5. Route the network cable (without connector)
through a suitable cable opening to the LON
Interface (Figure 4).
6. Terminate the end of network cable with a single,
two-pin, female LONWorks FTT-10A connector.
7. Attach the network cable FTT-10A connector to
connector at bottom of LON Interface (Figure 2
and 4).
8. Reinstall the bottom cover, side cover, and the
SED2 VFD operator panel.
Figure 3. Removing the Operator Panel and Side Cover
of SED2 VFD Frame Sizes D, E, F.
Figure 4. Installing LON Interface Option on SED2 VFD Frame Sizes D, E, and F.

Document No. 129-387
Installation Instructions
October 2, 2009
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and
models as design improvements are introduced. Echelon, LonMark, LonWorks, LonTalk are registered trademarks of Echelon Corporation.
Product or company names mentioned herein may be the trademarks of their respective owners. © 2009 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089
+ 1 847-215-1000
Your feedback is important to us. If you have
comments about this document, please send them
to SBT_technical.editor.us.sbt@siemens.com
Document No. 129-387
Printed in the USA
Page 3 of 3
Wiring
WARNING:
A VFD can be switched on unintentionally if
the serial bus installation is not operated
correctly. Only personnel who are qualified
and trained in installing systems of this type
should start the bus.
DIP Switch
Leave DIP switches OFF for proper operation of the
LON Interface.
WIRING
Wiring must conform to local codes and ordinances.
WIRE ROUTING
Maintain a minimum of 5 ft (1.5 m) between VFDs and
network or sensor wiring.
If it is necessary for network and sensor wring to cross
VFD wiring, it should cross at 90-degree angles.
POWER
The LON Interface receives power through its SED2
VFD connection. If VFD power is switched off, the
LON Interface will not communicate on the network.
LONTalk® NETWORK
The LONTalk network connection is on the bottom
edge of the LON Interface (Figure 2). Figure 5 shows
the wiring schematic for this connection. See
www.echelon.com for more details on the network
cable and the FTT-10A connector.
The installation is now complete.
NOTE: This connection supports twisted pair,
unshielded, polarity-insensitive, peer-to-peer
communications at 78 Kbps.
Figure 5. LON Interface Option Wiring Schematic.