SUTO S 430 Handbuch

English
Instruction and Operation Manual
S430
Pitot Tube Flow Sensor

Dear Customer,
Thank you for choosing our product.
Before starting up the device please read this manual in full and
carefully observe instructions stated. The manufacturer cannot be held
liable for any damage which occurs as a result of non-observance or
non-compliance with this manual.
Should the device be tampered with in any manner other than a
procedure which is described and specified in the manual, the warranty
is void and the manufacturer is e empt from liability.
The device is designed e clusively for the described application.
SUTO offers no guarantee for the suitability for any other purpose.
SUTO is also not liable for consequential damage resulting from the
delivery, capability or use of this device.
2 S430

Table of contents
1 Safety instructions......................................................................5
2 Registered trademarks.................................................................7
3 RF e posure information and statement.........................................8
4 Application.................................................................................9
5 Features...................................................................................10
6 Technical data...........................................................................11
6.1 General data.......................................................................11
6.2 Electrical data.....................................................................12
6.3 Output signals.....................................................................12
6.4 Accuracy ...........................................................................13
7 Dimensional drawing..................................................................15
8 Installation...............................................................................16
8.1 Installation requirements......................................................16
8.2 Determining the installation point..........................................17
8.2.1 Inlet and outlet sections...............................................17
8.2.2 Insertion angles..........................................................19
8.3 Calculating the insertion depth..............................................20
8.3.1 Center installation.......................................................21
8.3.2 100 mm-depth installation............................................22
8.4 Installing the sensor............................................................23
8.5 Performing the zero flow calibration.......................................24
8.5.1 Prerequisites...............................................................24
8.5.2 Using the service App S4C-FS.......................................25
8.5.3 Using the local display.................................................26
8.6 Removing the sensor ..........................................................27
8.7 Making electrical connection..................................................27
8.7.1 M12 connector plugs ...................................................28
8.7.2 Ethernet connection.....................................................29
9 Configuration............................................................................31
9.1 Description of sensor settings...............................................31
9.1.1 Flow settings..............................................................31
9.1.2 Unit settings...............................................................31
9.1.3 Reference conditions....................................................31
9.1.4 Factory settings..........................................................32
9.1.5 Output settings...........................................................32
9.1.6 Language setting.........................................................32
9.2 Configuration using the service App S4C-FS............................32
9.3 Configuration using the optional sensor display.......................33
9.3.1 Starting process..........................................................33
9.3.2 About the home page..................................................33
9.3.3 Configuration instructions.............................................34
S430 3

10 Sensor signal outputs...............................................................35
10.1 Analog output...................................................................35
10.2 Pulse output......................................................................35
10.3 Pulse connection diagram...................................................37
10.4 Modbus output .................................................................38
10.5 M-Bus output....................................................................40
11 Calibration..............................................................................41
12 Maintenance...........................................................................41
13 Disposal or waste....................................................................41
14 Appendi A – Flow measurement ranges.....................................42
14.1 Volumetric flow ranges.......................................................42
14.2 Analog output...................................................................43
15 Appendi B - Modbus communication e ample............................44
4 S430

1 Safety instructions
1 Safety instructions
Please check if this instruction manual matches the
product type.
Please observe all notes and instructions indicated in this
manual. It contains essential information which must be
observed before and during installation, operation and
maintenance. Therefore this instruction manual must be read carefully
by the technician as well as by the responsible user / qualified
personnel.
This instruction manual must be available at the operation site of the
flow sensor at any time. In case of any obscurities or questions,
regarding this manual or the product, please contact the manufacturer.
W RNING!
Compressed air!
ny contact with quickly escaping air or bursting
parts of the compressed air system can lead to
serious injuries or even death!
•Do not e ceed the ma imum permitted pressure range (see
sensors label).
•Only use pressure tight installation material.
•Avoid that persons get hit by escaping air or bursting parts of the
instrument.
•The system must be pressureless during maintenance work.
W RNING!
Voltage used for supply!
ny contact with energized parts of the product, may
lead to an electrical shock which can lead to serious
injuries or even death!
•Consider all regulations for electrical installations.
•The system must be disconnected from any power supply during
maintenance work.
•Any electrical work on the system is only allowed by authorized
qualified personal.
S430 5

1 Safety instructions
TTENTION!
Permitted operating parameters!
Observe the permitted operating parameters, any
operation exceeding this parameters can lead to
malfunctions and may lead to damage on the
instrument or the system.
•Do not e ceed the permitted operating parameters.
•Make sure the product is operated in its permitted limitations.
•Do not e ceed or undercut the permitted storage and operation
temperature and pressure.
•The product should be maintained and calibrated frequently, at
least annually.
General safety instructions
•It is not allowed to use the product in e plosive areas.
•Please observe the national regulations before/during installation
and operation.
Remarks
•It is not allowed to disassemble the product.
•Always use spanner to mount the product properly.
TTENTION!
Measurement values can be affected by malfunction!
The product must be installed properly and
frequently maintained, otherwise it may lead to
wrong measurement values, which can lead to
wrong results.
•Always observe the direction of the flow when installing the
sensor. The direction is indicated on the housing.
•Do not e ceed the ma imum operation temperature at the sensors
tip.
•Avoid condensation on the sensor element because it will affect
the accuracy enormously.
6 S430

1 Safety instructions
Storage and transportation
•Make sure that the transportation temperature of the sensor
without display is between -30°C ... +70°C and with display
between -10 ... +60°C.
•For transportation it is recommended to use the packaging which
comes with the sensor.
•Please make sure that the storage temperature of the sensor is
between -10 ... +50°C.
•Avoid direct UV and solar radiation during storage.
•For the storage the humidity must be <90%, no condensation.
2 Registered trademarks
SUTO®
Registered trademark of SUTO iTEC
MODBUS®
Registered trademark of the Modbus Organization, Hopkinton, USA
HART®
Registered trademark of the HART Communication Foundation, Austin,
USA
PROFIBUS®
Registered trademark of the PROFIBUS User Organization, Karlsruhe,
Germany
Bluetooth® word mark and logos
Registered trademarks of Bluetooth SIG, Inc.
Android™, Google Play
Trademarks of Google LLC
S430 7

3 RF exposure information and statement
3 RF exposure information and statement
This equipment complies with FCC RF radiation e posure limits set forth
for an uncontrolled environment. This equipment should be installed
and operated with minimum distance of 20 cm between the radiator and
your body.
This device complies with part 15 of the FCC rules. Operation is subject
to the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
NOTE: The manufacturer is not responsible for any radio or TV
interference caused by unauthorized modifications to this equipment.
Such modifications could void the user’s authority to operate the
equipment.
NOTE: This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment
generates uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or
more of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
•Consult the dealer or an e perienced radio/TV technician for help
•This device and its antenna(s) must not be co-located or operating
in conjunction with any other antenna or transmitter.
8 S430

4 Application
4 pplication
The S430 flow sensor is designed to measure the consumption of
compressed air and a variety of other gases in wet air or high mass flow
/ velocity applications. The sensor can even work in wet and dirty gases
such as the outlet of a compressor.
The S430 can measure the following parameters for compressed air or
gases:
Parameter Factory default unit
Velocity m/s
Volumetric flow m3/h
Pressure bar
Total consumption m3
Temperature °C
Remark: You can change units by means of the service App S4C-FS,
the optional local display, or the optional service kit.
The S430 flow sensor is mainly used in compressed air systems in the
industrial environment, and is not designed for e plosive areas. To use
it in e plosive areas, please contact the manufacturer.
S430 9

5 Features
5 Features
•Flow and consumption measurement in wet air or high mass flow/
velocity applications.
•Measurement at the compressor outlet applicable.
•Product for bi-directional measurement available based on the
advanced auto-direction-detection technology.
•Insertion-type flow sensor facilitating installation under pressure
through a ball valve.
•High temperature application up to 230°C.
•Applicable to pipes with diameters from 1.25” up to 10”. Product
for greater-diameter pipes available on request.
•No mechanical wear parts.
•Stainless steel used for all parts that are in contact with the
medium.
•Mobile service App S4C-FS available for monitoring and
configuring the sensor through mobile devices.
•Optional local display available for monitoring and configuring
values directly on the sensor.
•Optional Power over Ethernet (PoE).
•Optional M-Bus output.
10 S430
Andere Handbücher für S 430
4
Inhaltsverzeichnis
Andere SUTO Messgerät Handbücher