Trinity TINYPRO3 Bedienungsanleitung

Tinypro3 – Operational Manual
TRINITY
[1]
USER’S MANUAL
TINYPRO3
POWER METER
This document contains the latest technical information about TINYPRO3 which is a
micro-controller based Power meter. The product Infinity is sophisticated electronic
equipment, and the user is advised to read this User’s Manual carefully before
attempting to install or operate the equipment.
Published on: (mention the date of publishing)
Document Version: 1.0

TINYPRO3 – Operational Manual
TRINITY
[2]
Warranty statement
Trinity warrants to the original retail purchaser of the Trinity product enclosed with this
limited warranty statement that the product, if purchased new and used in the India
conforms to the manufacturer’s specifications and will be free from defects in
workmanship and materials for a period of one year from the date of original
purchase, unless expressly stated otherwise by Trinity, in a written format.
Should your Trinity product prove defective during the warranty period, please bring
the product securely packaged in its original container or an equivalent, along with
proof of the date of original purchase, to our Trinity Dealer or Factory. You are
responsible for all costs (shipping, insurance, travel time) in getting the product to the
service location. Trinity will, at its option, repair or replace on an exchange basis the
defective unit, without charge for parts or labor. When warranty service involves the
exchange of the product or of a part, the item replaced becomes Trinity property. The
replacement unit may be new or refurbished to the Trinity standard of quality, and at
Trinity’s option, the replacement may be another model of like kind and quality.
Trinity’s liability for replacement of the covered product will not exceed the original
retail selling price of the covered product. Exchange or replacement products or parts
assume the remaining warranty period of the product covered by this limited warranty.
What This Warranty Does Not Cover:
This warranty does not apply to refurbished or reconditioned products. This warranty
covers only normal use in India. This warranty does not cover damage to the Trinity
product caused by parts or supplies not manufactured, distributed or certified by
Trinity. This warranty is not transferable. This warranty does not cover third party
parts, components or peripheral devices added to the Trinity product after its
shipment from Trinity. Trinity is not responsible for warranty service should the Trinity
label or logo or the rating label or serial number be removed or should the product fail
to be properly maintained or fail to function properly as a result of misuse, abuse,
improper installation, neglect, improper shipping, damage caused by disasters such
as fire, flood, and lightning, improper electrical current, interaction with non-Trinity
products, or service other than by an Trinity Authorized Service.
The warranty and remedy provided above are exclusive and in lieu of all other
express or implied warranties including, but not limited to, the implied warranties of
merchantability or fitness for a particular purpose. In the event, the remedies above
fail, Trinity’s entire liability shall be limited to a refund of the price paid for the Trinity
product covered by this limited warranty. Except as provided in this written warranty,
neither Trinity Energy Systems Pvt. Ltd. nor its affiliates shall be liable for any loss,
inconvenience, or damage, including direct, special, incidental, or consequential
damages, resulting from the use or inability to use the Trinity product, whether
resulting from breach of warranty or any other legal theory.

TINYPRO3 – Operational Manual
TRINITY
[3]
Contents
Introduction ................................................................................................................4
The Main Features Available in This Model..........................................................4
Front View of the Unit ...........................................................................................4
Technical Specifications...........................................................................................5
Installation and Commissioning...............................................................................6
Connection Scheme..............................................................................................9
RS485 Connection..............................................................................................10
Operational Details ..................................................................................................11
Programming Mode................................................................................................12
Setting CT- primary.............................................................................................12
Setting a unit address for RS485 port.................................................................12
Run Mode ...............................................................................................................14
Run Mode Displays.............................................................................................14
Freezing and unfreezing the displays.................................................................15
Communication........................................................................................................16
Modbus RTU on RS485 Port..............................................................................16
Appendix.................................................................................................................17
Ordering Options......................................................................................................18

TINYPRO3 – Operational Manual
TRINITY
[4]
Introduction
Tinypro3 is a microcontroller based power meter which measures basic parameters
and displays on a red seven segment. Tinypro3 is a host of low cost, easy to use
individually that offers for the basic measurement capabilities required to monitor
electricity over and above basic metering. The unit can be installed to either 3P4W or
3P3W in an electrical installation and is able to measure parameters such as PF,
Active power (KW) and Active Energy (KWh).
The unit also has communication, RS485 port supporting MODBUS-RTU protocol for
integration with SCADA/EMS. The entire range is very rugged and cost-effective
solution. The unit is field proven and more than 100,000 units are active in service.
The Main Features Available in This Model
•Multi parameter Monitoring with LED indicators
•Displays with 0.4 Red Seven Segment
•Measurement of KW, PF and KWh.
•Modbus-RTU on RS485 port with SCADA/EMS
•All parameters with default accuracy class 1.0S
Front View of the Unit

TINYPRO3 – Operational Manual
TRINITY
[5]
Technical Specifications
* To be specified at the time of ordering along with PT primary.
SR.
NO
PARAMETERS
&
OPTIONS STATASTICS
1 Volts R-N Direct Voltage Input : Up to 300V L-N
Burden : 0.5VA
Secondary Voltage Input : 63.5V*
2 Volts Y-N
3 Volts B-N
4 Volts RY Direct Voltage Input : Up to 500V L-L
Burden : 0.5VA
Secondary Voltage Input : 110V*
5 Volts YB
6 Volts BR
7 Current R Secondary Current Input : 5A or 1A (To be specified at the
time of Ordering)
CT Primary : Site Selectable
Range of Reading : 5 – 5000A
Burden : < 1.0VA
Overload(Through CT) : 5A CT = 6A RMS Continuous
1A CT = 1.2A RMS Continuous
(Whole Current) : 120% of Imax continuous.
8 Current Y
9 Current B
10 KWh Range of Reading : 0 to 9999999.0 KWh
Accuracy : 1.0S as per IS13779.
11 System PF Accuracy : 1% of Reading (IPFI>0.5)
Range of Reading : 0.05 to 1.00 Lag/Lead
12 System KW Accuracy : 1.0% of Reading
(Between 0.5 Lag to 0.8 Lead)
13 DISPLAY 0.4” Red Seven Segment.
14 RS485 For Integration with EMS/SCADA
15 Bezel 96x96 mm DIN enclosure
16 Depth 55 mm

TINYPRO3 – Operational Manual
TRINITY
[6]
Installation and Commissioning
The unit can be used only for either 3P4W or 3P3W according to your ordering
option and requirement in your electrical installation.
To install and commission for 3P4W, proceed the following instructions:
1. Push the unit into the panel and mount using the claim provided on it.
2. Connect the auxiliary supply (80V AC to 270V AC) to the terminals marked P
and N.
3. Connect the three phases with the phase sequence being R-Y-B to the
terminals marked U1, U2 and U3 respectively. Make sure that the phases
coming to the unit come through control fuses of 1.0A rating. This will protect
the electronic inside from damage due to severe over voltage or phase faults
in the system.
4. Connect the neutral wire to the terminal marked U4.
5. Connect the two wires from the R-phase CT to the terminal marked M1 and
L1 such that S1 from CT goes to M1. Connect the two wires from the Y-phase
CT to the terminals marked M2 and L2 such that S1 from the CT goes to M2.
Connect the two wires from the B-phase CT to the terminals marked M3 and
L3 such that S1 from the CT goes to terminal marked M3.
6. Switch on the auxiliary supply as well as three phase supply and then, the unit
will come alive in order to display such as TRINITY ESPL, CT ratio, Unit
Address and Run Mode respectively.

TINYPRO3 – Operational Manual
TRINITY
[7]
7. Firstly, user should program the settable parameters, CT-primary and unit
address for RS485 communication port. (Refer Operational Details in the next
section).
8. Now the unit is ready for operation.

TINYPRO3 – Operational Manual
TRINITY
[8]
To install and commission for 3P3W, proceed the following instructions:
1. Push the unit into the panel and mount using the claim provided on it.
2. Connect the auxiliary supply (80V AC to 270V AC) to the terminals marked P
and N.
3. Connect the three phases with the phase sequence being R-Y-B to the
terminals marked U1, U4 and U3 respectively. Make sure that the phases
coming to the unit come through control fuses of 1.0A rating. This will protect
the electronic inside from damage due to severe over voltage or phase faults
in the system.
4. Connect the two wires from the R-phase CT to the terminals marked M1 and
L1 such that S1 from CT goes to M1. Connect the two wires from the B-phase
CT to the terminals marked M3 and L3 such that S1 from the CT goes to the
terminal marked M3.
5. Switch on the auxiliary supply as well as three phases supply and then, the
unit will come alive in order to display such as TRINITY ESPL, CT ratio, unit
Address and Run Mode respectively.
6. Firstly, user should program the settable parameters, CT-primary and unit
address for RS485 communication port as required. (Refer Operational
Details in the next section).
7. Now, the unit is ready for operation.

TINYPRO3 – Operational Manual
TRINITY
[9]
Connection Scheme

TINYPRO3 – Operational Manual
TRINITY
[10]
RS485 Connection
Inhaltsverzeichnis
Andere Trinity Messgerät Handbücher

Trinity
Trinity ENTITY Bedienungsanleitung

Trinity
Trinity SLM102 Bedienungsanleitung

Trinity
Trinity INFINITY Bedienungsanleitung

Trinity
Trinity XPERT-PRO Bedienungsanleitung

Trinity
Trinity VAF Bedienungsanleitung

Trinity
Trinity NF29 Bedienungsanleitung

Trinity
Trinity Olympus WS-811 Bedienungsanleitung

Trinity
Trinity TINYPRO6 Bedienungsanleitung

Trinity
Trinity E3000 Series Bedienungsanleitung