US Automatic PATRIOT Series Betriebsanleitung

Heavy Duty Battery Powered Solar or AC Charged
PATRIOT I
Single Swing Gate Operator
PATRIOT II
Dual Swing Gate Operator
Installation/Owners Manual

2
PATRIOT Series AUTOMATIC GATE OPERATORS
This Patriot Gate Operator is intended to be installed on the four different
classes of gate operators identified in the UL325 Standards.
RESIDENTIAL VEHICULAR GATE OPERATOR – CLASS I
A vehicular gate operator (or system intended for use in garages or parking areas associated with a
residence of one-to four single families.
COMMERCIAL/GENERAL ACCESS VEHICULAR GATE OPERATOR – CLASS II
A vehicular gate operator (or system) intended for use in a commercial location or building such
as a multi-family housing unit (ve or more single family units), hotel, garages, retail store, or other
buildings accessible by or servicing the general public.
INDUSTRIAL/LIMITED ACCESS VEHICULAR GATE OPERATOR – CLASS III
A vehicular gate operator (or system) intended for use in an industrial location or building such as a
factory or loading dock area or other locations not accessible by or intended to service the general
public.
RESTRICTED ACCESS VEHICULAR GATE OPERATOR – CLASS IV
A vehicular gate operator (or system) intended for use in a guarded industrial location or building such
as an airport security area or other restricted access locations not servicing the general public, in
which unauthorized access is prevented via supervision by security personnel.
Solar Friendly
The Patriot system design and the accessories recommended are all Solar Friendly meaning that
they require the least amount of energy possible to perform the job they were designed to do. The
solar option allows you to install the gate operator in remote areas or in applications where you prefer
to be solar charged. Solar charging provides additional isolation from lightning that might damage the
unit via the AC power needed for the transformer.
BATTERY REQUIRED FOR OPERATION (Battery not included)
Recommended battery type:
Battery 12-volt, Group U-1; sealed (maintenance free); 30 amp hour minimum.
Using a smaller amp hour battery may cause damage to the charging system.
The wiring harness has two 1/4” ring terminals to connect to battery posts.
CAUTION: Do not install wet cell battery into control box; this type of battery
usually has removable caps used for service and will vent into control box.
The battery is charged using the 120V AC Powered Transformer (PN #520004) OR the Patriot Solar
Panel kit (PN 520025). Typically only one panel will be required. For information on what you can
expect from a solar charged system see the solar charging section of this manual. Accessories that
are added to your gate operator must be solar friendly accessories.
PLEASE READ THE ENTIRE MANUAL CAREFULLY PRIOR TO INSTALLATION.
Study the entire Safety Section paying particularly close attention to the entrapment zones and
install monitored entrapment devices to protect all entrapment zones identied. Installation by a
Qualied Technician is recommended to verify all safety concerns are addressed.
© USAutomatic, LLC, 2019 rev. A
All rights reserved. No part of this manual may be reproduced by any means
without the expressed written consent of the publisher.
USAutomatic Part # 720004

1
INTRODUCTION
Entrapment Device Requirements and Zones ............................................................................................2-3
Important Safety Instructions and Safety Installation Information .............................................................4-5
Patriot Parts Inventory ..................................................................................................................................6
Patriot Hardware Inventory ............................................................................................................................7
Actuator Dimensions .....................................................................................................................................8
General Tool Requirements ...........................................................................................................................8
PREPARATION AND OVERVIEW
Gate Qualications/Applications ....................................................................................................................9
Proper Gate Design .....................................................................................................................................10
INSTALLATION INSTRUCTIONS
1. Mounting Site Review ......................................................................................................................... 11
2. Determine Opening Method (pull to open or push to open) ................................................................12
3. Determine Horizontal Mounting Location ............................................................................................13
4. Determine Best Method for Actuator Mounting Brackets - Pull to Open .............................................14
Determine Best Method for Actuator Mounting Brackets - Push to Open ...........................................15
Determine Best Method for Actuator Mounting Brackets - Columns ....................................................16
5. Mount Support Bracket .......................................................................................................................17
6. Installing Actuator Mounting Tube - Pull to Open ................................................................................18
Installing Actuator Mounting Tube - Push to Open ...............................................................................19
7. Installing Linear Actuator to Actuator Mounting Bracket .......................................................................20
8. Install Gate Bracket to Linear Actuator .................................................................................................20
9. Install Gate Bracket to Gate .................................................................................................................21
10. Install Patriot Control Box / Control Box Dimensions ...................................................................21 - 22
11. Install Patriot Control Board ................................................................................................................22
12. Installing Receiver and Smart Charger / Charge Controller and Entrapment Siren .............................23
13. Install Linear Actuator Cable ................................................................................................................23
13a. Splicing Linear Actuator Cable Cable and Dual Gate Cable .................................................................24
14. Installing Monitored Entrapment Protection Devices ...........................................................................25
Monitored Photo Eye (Type B1) Installation .........................................................................................25
Monitored Contact Edge (Type B2) Installation ....................................................................................25
Constant Pressure (Type D) Installation ..............................................................................................25
15. Install Battery ........................................................................................................................................26
16. Install Charger / Charge Controller Power Source (AC or Solar) .................................................26 - 27
17. Connect Power Source to Smart Charger / Charge Controller ...........................................................28
18. Install Safety Signs ...............................................................................................................................28
19. Connect Linear Actuator Cable to Control Board ................................................................................28
20. Photo Eye Alignment ............................................................................................................................28
21. Operating Gate For The First Time .......................................................................................................29
22. Optional Soft Stop for Retract and Extend Position ............................................................................30
23. Gate Delay Feature ..............................................................................................................................30
24. Making Retract and Extend Limit Adjustments ....................................................................................31
25. Sensitivity Adjustment and Entrapment Alarm .....................................................................................32
26. Verifying Inherent Entrapment Protection System (Type A) Operation ................................................32
26a. Verifying Monitored Entrapment Devices .............................................................................................33
27. Patriot Control Board Information ..................................................................................................34 - 37
28. Programming Transmitter and Receiver .............................................................................................38
PROGRAMMING WIRELESS KEYPAD ..................................................................................................39 - 41
PERIODIC SERVICE / EMERGENCY MANUAL RELEASE..................................................... 44
ACCESSORIES ............................................................................................................................... 45 - 47
TROUBLESHOOTING.........................................................................................................48 - 63
APPENDIX
A. Photo Eye - Vehicular Protection Only..............................................................................................64 - 65
B. Extending Charge Device Location..........................................................................................................66
C. Charge Controller ....................................................................................................................................67
WARRANTY............................................................................................................................. 69
TABLE OF CONTENTS

2
Effective August 1, 2018 a vehicular swing gate operator must have provisions for, or be supplied
with, at least two independent entrapment protection means for each direction of travel as specied
in current UL325 standard Table 31.1. At installation, both entrapment protection devices must be
installed and operational before gate operation is allowed. *Exception allowed if no entrapment exist
in one direction of travel then only 1 device is required, the other direction must have 2 entrapment
protection devices active. The gate operator will monitor for proper operation before movement is
allowed.
USAutomatic control boards utilize type A (Inherent entrapment protection system) as the rst
entrapment protection means identied. The second entrapment device identied must be a
monitored Type B1 or Type B2 device that has been tested and approved with the gate operator.
These devices are listed below.
USAutomatic control boards can monitor one photo eye (B1) for the open direction, one photo eye
(B1) for the closed direction and one contact edge (B2) for the open/close direction. If additional
entrapment devices are required the USAutomatic expansion module (part # 500015) is required
Type B1 - Non-contact sensor (photoelectric sensor or the equivalent). Identied as Normally Closed
N/C contact switching.
Type B2 - Contact sensor (edge device or the equivalent). Identied as 10K resistor installed for
presence monitoring.
Type D - Actuating device requiring continuous pressure to maintain motion of the gate.
External entrapment devices approved for use are listed below
Wired Contact Edge Type B2 Devices
Manufacturer: ASO
Models: Sentir Edge 95.25, 92.20, 85, 35.55, 65, 25.30, 25.45, 15.10
Manufacturer: Miller Edge
Models: MGR20, MGS20, ME120, MG020, ME112, MG123
Wireless Contact Edge Type B2 Devices
Miller Edge Model: R Band RB-G-K10
Transmitter Solutions: IGAZE RE KIT-UL
EMX Model: WEL-200K
Non-Contact sensors (photoelectric sensor or the equivalent) Type B1 Devices
Manufacturer: USAutomatic, LLC
Models: 550011, 550014
The entrapment zones illustrations on the following page denes the most common entrapment
areas. It is the responsibility of the installer to identify all entrapment areas and install the appropriate
compliant monitored entrapment device or devices to protect each area identied.
USAutomatic recommends upgrading all systems to current UL325 standards.
Entrapment Devices Required and Approved for Operation

3
The illustrations below are a guide to help identify entrapment areas for swing gate installations that
must be protected. Other entrapment areas may exist and must be identied by the installer and
protected by the appropriate entrapment protection device for the situation.
Zone A - Leading edge of gate where it meets a 2nd gate,
stop post or passes a column or post corner. -
recommended monitored entrapment protection
type is B2 contact sensor or equivalent.
Zone B - Gate opens toward an immoveable object with
less than 16 inches (40.6 cm) of clearance -
recommended monitored entrapment protection
type B1 photo eye or equivalent. If space is less
than 16” (40.6 cm), entrapment protection in this
area is required.
(ASTM F2200: 7.1.1.1 and 7.1.1.2)
Zone C - If distance from center of hinge rotation point to
corner of column, post or immovable object is
greater than 4 inches (10.16 cm), recommended
monitored entrapment protection type is B2 contact
sensor or equivalent.
Zone D - If the bottom edge of a swing gate is greater than
4 inches (10.16 cm) and less than 16 inches
(40.6.cm) above the ground at any point in its arc of
travel, one or more contact sensors must be located
on the bottom edge of the gate.
ENTRAPMENT ZONES
< 4”
> 4” and < 16”

4
1. READ AND FOLLOW ALL INSTRUCTIONS
2. SAVE THESE INSTRUCTIONS!!
3. Always keep people and objects away from the gate. NO ONE SHOULD CROSS THE PATH OF
A MOVING GATE.
4. Test gate operator monthly. The gate must stop and reverse directions upon contacting a rigid
object or when the secondary entrapment device is activated.
5. After all adjustments have been made to the sensitivity (current sense) circuit, secondary
entrapment devices and all other external devices installed, the safety devices must be
checked again. Failure to adjust and retest the gate operator can increase the risk of injury or
death. A Qualied technician should check these periodically for proper operation.
6. Use the emergency release ONLY when gate is not moving.
7. KEEP GATES PROPERLY MAINTAINED. Tighten all bolts and grease hinges and pivot points.
8. THE ENTRANCE IS TO BE USED BY VEHICLES ONLY. Pedestrians must use a separate
entrance.
9. Never let children operate or play with gate controls or any other activation device. Keep
remote control away from children.
10. The operator is intended for installation only on gates used for vehicles. Pedestrians must be
supplied with a separate access opening. The pedestrian access opening shall be designed to
promote pedestrian usage. Locate the gate such that persons will not come in contact with the
vehicular gate during the entire path of travel.
11. The gate must be installed in a location so that enough clearance is supplied between the gate
and adjacent structures when opening and closing to reduce the risk of entrapment.
12. Do not attempt to enter the gate area while the gate is moving. Wait until the gate comes to a
complete stop.
13. DO NOT ALLOW CHILDREN TO PLAY IN THE AREA OF THE GATE.
14. Do not allow anyone to ride on the gate.
15. Operate the gate only when it is fully visible, free of persons or obstructions, and properly
adjusted.
16. All controls are located at least six feet away from the gate to eliminate the chance of the
person operating the gate from coming in contact with the moving gate. Do not install external
buttons, which can be used to operate the gate within the reach of children.
*Exception: Emergency access controls only accessible by authorized personnel may be
placed at any location in line-of-sight of the gate.
17. Both Safety Signs are installed, one on each side of the gate and visible in the gate area.
IMPORTANT SAFETY INSTRUCTIONS
WARNING - TO REDUCE THE RISK OF INJURY OR DEATH

5
Install the gate operator when:
• Operator is appropriate for the construction of the gate and usage class is correct for the installation.
• All exposed pinch points are eliminated or guarded.
• The gate is installed in a location where enough space is supplied between adjacent structures and
the gate that when opening or closing the chance of entrapment is reduced.
• The gate is properly installed and moves freely in both directions. Do not over adjust the sensitivity
adjustment to compensate for an improper gate installation.
• All hard wired sensors used for monitored entrapment protection devices and their wiring are installed
in a manner which protects them from mechanical damage.
• The Reset button must be located in the line-of-sight of the gate. Activation of the reset button shall
not cause the operator to start.
Non Contact Sensors - Type B1 - Photo Eyes or equivalent
1. See entrapment zones for suggestions on placement of sensors.
2. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the
sensor while the gate is still moving.
3. One or more non-contact sensors shall be located where the risk of entrapment or obstruction
exist, such as the area reachable by a moving gate.
Contact Sensors - Type B2 - Contact Edge or equivalent
1. See entrapment zones for suggestions on placement of sensors.
2. One or more sensors shall be located on the inside and outside leading edge of a swing gate.
3. Additionally, if the bottom edge of a swing gate is greater than 4 inches (101.6mm) and less than
16 inches (406mm) above ground at any point in its arc of travel one or more sensors shall be
located on the bottom edge.
4. A hardwired sensor shall be located and its wiring arranged so that the wiring between the sensor
and the gate operator is not subjected to mechanical damage.
5. A wireless device such as one that transmits (RF) signals to the gate operator for entrapment
protection functions shall be located where the transmission of the signals are not obstructed or
impeded by building structures , natural landscaping or similar obstruction. A wireless device shall
function under the intended end-use conditions.
Constant Pressure - Type D - Emergency switch or equivalent
1. The gate operator controls must be placed so that the user has full view of the gate area when the
gate is moving.
2. An automatic closing device (such as a timer, loop sensor, or similar device) shall not be
employed. and no other activation device shall be connected.
3. Placard required shall be placed adjacent to the controls.
SAFETY INSTALLATION INFORMATION

6
All Operators include:
Cabinet with Control Board
Part # 600020 Cabinet
Part # 602020 Cover
Part # 500003 Control
Board
Patriot Actuator
Part # 510001-SS
Patriot I - 1 per
Patriot II - 2 per
Dual Gate Actuator
Extension Cable 40’
Part # 630020
Patriot II ONLY
Charge Controller
Part # 520006
AC Charging Transformer
Part # 520004
with Patriot AC Models
Solar Charging Kit
Part # 520025
with Patriot Solar Models
Safety Signs
Part # 601020
2 per
Photo Eyes
Part # 550011
1 set per
Operators purchased with LCR Radio
Controls include:
2 Button Transmitter
Part # 030210
2 per
LCR Radio Receiver W/Harness
Part # 030205
Coax Antenna Cable
and Bracket
Part # 030013
Antenna
Part # 030208
Optional Accessories & LCR Items:
See accessories section for complete list and descriptions
4 Button Transmitter - Part # 030212
Push to Operate Button - Part # 030215
Wireless Keypad - Plastic - Part # 050500
Wireless Keypad - Metal - Part # 050550
Garage Door Receiver - Part # 030214
12/24 Receiver - Part # 030207
Electric Gate Lock - Part # 070510
7 Day Timer - Part # 550015
Exit Sensor - #070310
Metal Photo Eye - #550014
External Reset Button - #630060
PARTS INVENTORY

7
BRACKETS
Support Bracket
Part # 610425
Patriot I - 1 per
Patriot II - 2 per
Mounting Tube
Part # 610102
Patriot I - 1 per
Patriot II - 2 per
Gate Bracket
Part # 610107
Patriot I - 1 per
Patriot II - 2 per
Manual Release Pin
Part # 620010
Patriot I - 1 per
Patriot II - 2 per
Manual Release Pin Clip
Part # 620011
Patriot I - 1 per
Patriot II - 2 per
Bronze Bushing
Part # 610530
Patriot I - 2 per
Patriot II - 4 per
Nylon Washers
Part # 610529
Patriot I - 2 per
Patriot II - 4 per
⅜” Bolt
Part # 610512
Patriot I - 1 per
Patriot II - 2 per
⅜” SAE Flat Washers
Part #610516
Patriot I - 2 per
Patriot II - 4 per
⅜ inch Lock Nuts
Part # 610518
Patriot I - 1 per
Patriot II - 2 per
1” Plastic Standoff
Part #620008
Patriot I - 7 per
Patriot II - 8 per
Cable Clamp
Part # 650020
Patriot I - 1 per
Patriot II - 2 per
Entrapment Siren
Part # 530010
1 per
Charge Control Harness
Part # 630041
20 Amp Fuse
1 per
Screwdriver
Part # 610006
1 per
Warning Placard
Part # 601015
1 per
HARDWARE INVENTORY

8
• SAE Standard wrenches & sockets • Welder
• Nut driver • Drill and bits
• Level and tape measure • Drill adapter for socket attachment
• Pliers • Hack saw
• Wire Cutters/Strippers
Welding is the recommended method of securing the linear actuator mounts to the gate and hinge
post. Bolt on brackets require frequent service to keep tight. They must be very securely attached
(i.e. carriage bolts with lock nuts and washers). Lag type bolts are not recommended. Loose or
unstable linear actuator mounts will result in improper operation.
IMPORTANT CAUTIONS:
A. Do not perform any welding with the actuator cable plugged into the control board or the battery
connected. Serious damage to the control board and/or battery may occur if attempted.
B. Do not attempt to hold control box and drill mounting holes with components installed. This
could damage the components.
C. Always disconnect the battery power from the control board using the quick connect harness
prior to wiring any devices to the control board.
D. Do not test or operate without actuator securely attatched to the gate. Serious damage to the
actuator limit switch assembly may occur if attempted.
ACTUATOR DIMENSIONS
GENERAL TOOL REQUIREMENTS
Top of gear box to
wire harness.
This includes wire
harness clearance
as harness exits
bottom of housing.
Actual distance
housing is 8” plus
1.5” for harness.
Rear Gear box to front
Rear housing to motor end
TOP VIEW
Housing width
42.5”
33.75”
9.5”
9.75”
5.75”
4.25”
3”
(Measurements are to center of hole.)
Andere Handbücher für PATRIOT Series
1
Dieses Handbuch passt für folgende Modelle
3
Inhaltsverzeichnis
Andere US Automatic Toröffner Handbücher

US Automatic
US Automatic PATRIOT Series Betriebsanleitung

US Automatic
US Automatic PATRIOT RSL Betriebsanleitung

US Automatic
US Automatic PATRIOT RSL Betriebsanleitung

US Automatic
US Automatic PATRIOT RSL Betriebsanleitung

US Automatic
US Automatic PATRIOT I Betriebsanleitung

US Automatic
US Automatic STAR I Bedienungsanleitung

US Automatic
US Automatic Ranger HD Betriebsanleitung

US Automatic
US Automatic PATRIOT I Montageanleitung

US Automatic
US Automatic Ranger 500 S Betriebsanleitung

US Automatic
US Automatic SENTRY 300 S Betriebsanleitung