6
VUT 2000/3000 PBE EC
www.ventilation-system.com
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to
60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above
the dew point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a minimum
(20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage electronic
components. Never use the unit for dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
TECHNICAL DATA
MODEL VUT 2000 PBE EC VUT 3000 PBE EC
Voltage [V/50 (60) Hz] 3~ 400
Maximum fan power [W] 876 2226
Power of the integrated electric heater [W] 15000 21000
Maximum air flow [W] 15876 23226
Maximum unit current without a heater [A] 5.3 3.5
Current of the integrated electric heater [A] 21.7 30
Maximum current of the unit with an electric heater [A] 27.0 33.5
Air flow [m3/h] 2100 4300
Rotation speed [min-1] 2920
Noise level, 3 m [dBA] 36 46
Transported air temperature [°C] -25...+40
Casing material Aluzinc
Insulation, mineral wool [mm] 25 25
Filtering class of the extract filter G4
Filtering class of the supply filter G4
Connecting air duct diameter [mm] 315 400
Weight [kg] 140 281
Heat recovery efficiency [%] 50...67 59...72
Heat exchanger type Cross-flow
Heat exchanger material Aluminium
SEC class NRVU NRVU