Elsner 71300 Leitfaden

EN
Installation and Adjustment
KNX eTR gl
Temperature Sensor with integra-
ted PI Control
Item numbers 71300 (white), 71302 (black)


1 Contents
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Temperature Sensor KNX eTR gl • from application 1.0
Version: 07.04.2021 • Technical changes and errors excepted.
1. Safety and operating instructions ....................................................... 3
1.1. Installation notes ...................................................................................................... 3
2. Description ........................................................................................... 3
2.1. Scope of delivery ...................................................................................................... 4
2.2. Technical data ........................................................................................................... 4
2.2.1. Accuracy of the measurement ..................................................................... 5
2.2.2. Device structure ............................................................................................ 5
3. Installation ........................................................................................... 6
3.1. Installation location and preparation ...................................................................... 6
3.2. Mounting ................................................................................................................... 6
4. Notes on mounting and commissioning .............................................. 8
4.1. Addressing of the device at the bus ....................................................................... 8
5. Maintenance and care .......................................................................... 8
6. Disposal ............................................................................................... 8
7. Transmission protocol ......................................................................... 9
7.1. List of all communication objects ........................................................................... 9
8. Setting the parameters ...................................................................... 11
8.1. Behaviour on power failure/ restoration of power .............................................. 11
8.2. General settings ..................................................................................................... 11
8.3. Temperature measured value ............................................................................... 11
8.4. Temperature PI controller ...................................................................................... 12
8.4.1. Heating control stage 1/2 ........................................................................... 17
8.4.2. Cooling control stage 1/2 ........................................................................... 19

2 Clarification of signs
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to-
date version of the manual is available.
Clarification of signs used in this manual
Installation, inspection, commissioning and troubleshooting of the device
must only be carried out by a competent electrician.
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER! ... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
WARNING! ... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
CAUTION! ... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
ATTENTION! ... indicates a situation which may lead to damage to property if it is
not avoided.
ETS In the ETS tables, the parameter default settings are marked by
underlining.

3 Safety and operating instructions
Temperature Sensor KNX eTR gl • Version: 07.04.2021 • Technical changes and errors excepted.
1. Safety and operating instructions
1.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• Comply with the locally applicable directives, regulations and provisions
for electrical installation.
• De-energise all cables to be mounted and take safety precautions
against unintentional switch-on.
• Inspect the device for damage before installation. Only put undamaged
devices into operation.
• Immediately take the device or system out of service and secure it
against unintentional switch-on if risk-free operation is no longer guaranteed.
Use the device exclusively for building automation and observe the operating
instructions. Improper use, modifications to the device or failure to observe the
operating instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition and
after conclusion of all installation and operational start-up tasks, and only in the
surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2. Description
The Temperature Sensor KNX eTR gl measures the room temperature. The indoor
sensor can receive an external measured value via the bus and process it with own
data to an overall temperature value (mixed value).
The KNX eTR gl has a integrated PI controller for a heating/cooling system.
Functions:
•Measurement of temperature
•Mixed values from own measured value and external values (proportions can
be set in percentage)
•PI controller for heating (one or two step) and cooling (one or two step)
depending on temperature. Control according to separate target values or
basic target temperature

4 Description
Temperature Sensor KNX eTR gl • Version: 07.04.2021 • Technical changes and errors excepted.
2.1. Scope of delivery
• Temperature Sensor with mounting
• 4 screw anchors 4 × 20 mm, 4 flat head screws 3 × 25 mm
2.2. Technical data
The product conforms with the provisions of EU guidelines.
General:
Casing Genuine glass, plastic
Colours • similar to RAL 9003 signal white
• similar to RAL 9005 deep black
Installation on the wall or on device socket according to DIN 49073
Dimensions housing approx. 81.5 mm x 81.5 mm (W x H),
mounting depth approx. 12 mm
Total weight approx. 70 g
Ambient temperature 0…+55 °C
Ambient humidity 5...95 % RH, non-condensing
Storage temperature -30…+85 °C
Overvoltage category III
Degree of contamination 2
KNX bus:
Medium TP1-256
Configuration mode S-Mode
Group addresses max. 254
Assignments max. 254
Communication objects 41
Nominal voltage 30 V SELV
Power consumption maximum 10 mA
Connection
Conductor diameter
Stripping length
KNX plug terminals
0.6…0.8 mm² s
5mm
Connection
Conductor diameter
Stripping length
Spring-loaded terminals
• rigid and flexible conductors 0.2...0.75 mm²
• flexible conductors with ferrules 0.25...0.34 mm²
7...9 mm
Duration after bus voltage
restoration until data is
received
approx. 5 seconds
Sensor:
Temperature measurement
range
0…+55 °C
Temperature resolution 0.1 °C

5 Description
Temperature Sensor KNX eTR gl • Version: 07.04.2021 • Technical changes and errors excepted.
2.2.1. Accuracy of the measurement
When measuring temperature, the self-heating of the device is considered by the
electronics. The heating is compensated for in the device.
2.2.2. Device structure
2
3Fig. 1
Back view with mounting
2/3 Screw holes for different sockets. Fastening
with 2 screws is sufficient. For wall mounting,
use a fixing material suitable for the ground!
2
22
33
3
Fig. 2
Back view without mounting
4 KNX bus terminal +/- for connection when
mounted on a socket
5 Spring-loaded terminals KNX bus for moun-
ting directly on the wall
6 Programming LED
7 Programming button (recessed) for teaching
device
8 Temperature sensor
PRG key is accessible from below/outside when
the device is mounted (see chapter Addressing
the device).
4 576 8

6 Installation
Temperature Sensor KNX eTR gl • Version: 07.04.2021 • Technical changes and errors excepted.
3. Installation
3.1. Installation location and preparation
The Temperature Sensor KNX eTR gl is made for wall mounting. The device can be
mounted directly on plaster or on device socket according to DIN 49073 and other
sockets, e.g. Swiss device socket.
May be installed and operated in dry interior rooms only.
When selecting an installation location, ensure that the measurement results are
affected as little as possible by external influences. Possible sources of interference
include:
• Direct sunlight
• Drafts from windows and doors
• Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
• Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
• Connection lines and ducts which lead from warmer or colder areas to the
sensor
Measurement variations from permanent sources of interference can be corrected in
the ETS in order to ensure the specified accuracy of the sensor (offset).
3.2. Mounting
DANGER!
Danger due to electrical voltage
(mains voltage)!
• The socket, in which the device is installed, must not contain cabling
with 230 V.
• Observe the regulations and standards applicable to SELV circuits
during installation and wiring of the KNX connection and inputs.
Prepare the device
Remove the front panel from the mounting. Release the lock by moving the front panel
a few millimetres upwards. The two parts can then be easily separated (Fig. 3).

7 Installation
Temperature Sensor KNX eTR gl • Version: 07.04.2021 • Technical changes and errors excepted.
Screw the mounting onto the wall or socket. The connecting wires (bus line +/-) are led
through the opening in the mounting.
Installation directly on the wall
The wires are pushed into the connection openings.
Installation on a socket
To avoid falsifying the temperature value, use a wind-proof socket and also seal the in-
let pipes against draughts.
Fig. 3 Locking of front panel and mounting
Remove the red-black KNX bus terminal, it is not
required.
Connect the bus +/- connecting wires to the spring-
loaded terminals on the front panel.
Fig. 4 Spring-loaded terminals
To pull it out, press the spring down, e.g. with a
screwdriver.
If there is a cavity behind the device, e.g. when
using a socket, you can use the red/black KNX bus
terminal for connection.

8 Notes on mounting and commissioning
Temperature Sensor KNX eTR gl • Version: 07.04.2021 • Technical changes and errors excepted.
Finish mounting
Snap the front panel into place on the mounting (see Fig. 3): Place it slightly above the
centre position, hook it in and slide it downwards.
The mounting must be installed so that the large opening faces downwards (see Fig.
4). This is necessary for a correct temperature measurement.
4. Notes on mounting and commissioning
Configuration is made using the KNX software as of ETS 5. The product file can be
downloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de in the “Service” menu. There you will also find the
product manual.
After the bus voltage has been applied, the unit will enter an initialisation phase lasting
approx. 5 seconds. During this period, no information can be received or transmitted
via the bus.
4.1. Addressing of the device at the bus
The individual address is assigned via the ETS. A button and a control LED are located
on the unit for this purpose (Fig. 2, No. 6+7).
The programming button is located at the bottom outer side of the front panel of the
device and is recessed. Use a thin object to reach the button, e. g. a 1.5 mm² wire.
The equipment is delivered with the bus address 15.15.255. Another address can be
programmed using the ETS.
5. Maintenance and care
Fingerprints on the glass panel are best removed with a cloth moistened with water or
a microfiber cloth. Do not use an abrasive cleaning agent or aggressive cleansing
agents.
6. Disposal
After use, the device must be disposed of or recycled in accordance with the legal reg-
ulations. Do not dispose of it with the household waste!
PRG
Fig. 5
View from bottom
Temperature sensor
Dieses Handbuch passt für folgende Modelle
1
Inhaltsverzeichnis
Andere Elsner Zubehör Handbücher

Elsner
Elsner Cala KNX AQS/TH Leitfaden

Elsner
Elsner Vari KNX 3L Leitfaden

Elsner
Elsner Vari KNX 3L-TH-D Leitfaden

Elsner
Elsner KNX AQS/TH Leitfaden

Elsner
Elsner Sewi KNX TH-L-Pr Leitfaden

Elsner
Elsner KNX AQS/TH-B-UP Series Leitfaden

Elsner
Elsner KNX R Leitfaden

Elsner
Elsner KNX LW Series Bedienungsanleitung

Elsner
Elsner Leak Bedienungsanleitung

Elsner
Elsner KNX L Bedienungsanleitung