optris CS series Bedienungsanleitung

optris®CS
¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
Infrared Sensor
Operators manual


Optris GmbH
Ferdinand-Buisson-Str. 14
D – 13127 Berlin
GERMANY
Tel.: +49-30-500 197-0
Fax: +49-30-500 197-10
E-mail: info@optris.de
Internet: www.optris.com
Optris GmbH
Ferdinand-Buisson-Str. 14
D – 13127 Berlin
GERMANY
Tel.: +49-30-500 197-0
Fax: +49-30-500 197-10
Internet: www.optris.com
CE-Conformity
The product complies with the following standards:
EMC: EN 61326-1:2006 (Basic requirements)
EN 61326-2-3:2006
Safety: EN 61010-1:2001
The product accomplishes the requirements of the EMC Directive 2004/108/EG and
of the Low Voltage Directive 2006/95/EG.
References to other chapters are marked as: ►
Warranty
Each single product passes through a quality process. Nevertheless, if failures occur please contact the customer service at
once. The warranty period covers 24 months starting on the delivery date. After the warranty is expired the manufacturer
guarantees additional 6 months warranty for all repaired or substituted product components. Warranty does not apply to
damages, which result from misuse or neglect. The warranty also expires if you open the product. The manufacturer is not
liable for consequential damage. If a failure occurs during the warranty period the product will be replaced, calibrated or
repaired without further charges. The freight costs will be paid by the sender. The manufacturer reserves the right to
exchange components of the product instead of repairing it. If the failure results from misuse or neglect the user has to pay
for the repair. In that case you may ask for a cost estimate beforehand.
optris CS – E2010-12-A
1

optris CS – E2010-12-A
2
Content
Page Page
Description 3SoftwareCompactConnect 24
ScopeofSupply 3Installation 24
Maintenance 3 Communication Settings 25
Cautions 4Digital Command Set 26
Factory Default Settings 4 Basics of Infrared Thermometry 27
TechnicalData 6Emissivity 28
General Specifications 6 Definition 28
Electrical Specifications 7 Determination of unknown Emissivities 28
Measurement Specifications 9 Characteristic Emissivities 29
Optical Charts 10 Appendix A – Emissivity Table Metals 30
Close Focus Optics 11 Appendix B – Emissivity Table Non Metals 31
LED Functions 12 Appendix C – Smart Averaging 32
Automatic Aiming Support 12
Self Diagnostic 13
Temperature Code Indication 14
Installation 15
Mechanical Installation 15
Mounting Accessories 16
Air Purge Collars 17
Further Accessories 18
Electrical Installation 19
Schematic Circuit Diagrams for Maintenance Appl. 22

Description
The sensors of the optris CS series are non-contact infrared temperature sensors.
They calculate the surface temperature based on the emitted infrared energy of objects [►Basics of Infrared
Thermometry].
The sensor housing of the optris CS is made of stainless steel (IP63) and contains the complete sensor
electronics. The optris CS has a fixed mounted connection cable.
The sensors CS are sensitive optical systems. Please use only the thread for mechanical installation.
Avoid mechanical violence on the head
–
this ma
y
destro
y
the s
y
stem (expir
y
of warrant
y
).
Scope of Supply
CS incl. connection cable, two mounting nuts and operators manual
Maintenance
Lens cleaning: Blow off loose particles using clean
compressed air. The lens surface can be cleaned with a soft,
humid tissue moistened with water or a water based glass
cleaner.
PLEASE NOTE: Never use cleaning
compounds which contain solvents
(neither for the lens nor for the housing).
optris CS – E2010-12-A
3

Cautions
Avoid abrupt changes of the ambient temperature.
In case of problems or questions which may arise when you use the CS, please contact our service department.
Read the manual carefully before the initial start-up. The producer reserves the right to change the herein
described specifications in case of technical advance of the product.
Factory Default Settings
The unit has the following presetting at time of delivery:
Emissivity: 0,950
Transmission: 1,000
Average time: 0,3 s
Smart averaging: active
Smart averaging hysteresis: 2 °C
Ambient temperature source: internal (head)
Status-LED function: Self diagnostic
Input (IN/ OUT/ green): Communication input
Output (OUT/ yellow): mV output
Temperature range: 0...350 °C
optris CS – E2010-12-A
4
Output
voltage: 0...3,5 V
Vcc adjust: inactive
Signal processing: Hold mode: off
Calibration: Gain 1,000/ Offset 0,0
The default settings can be changed with the
optional USB kit (USB adapter cable + software).
If the unit is supplied together with the USB-kit the
output is already preset to digital communication
(bidirectional).
Failsafe: inactive

For a usage of the CS for online maintenance applications (in electrical cabinets e.g.) the following recommend
settings are already included in the factory default setting (but not active):
OUT At3-state output the following settings are default:
Pre-alarm difference: 2 °C
Noalarmlevel: 8V
Pre-alarmlevel: 5V
Alarmlevel: 0V
Service voltage: 10 V
IN/ OUT: At Alarm output (open collector) the following settings are default:
Mode: normallyclosed
Tempcodeoutput:activated (for values above alarm level)
Range settings: 0 °C = 0 %/ 100 °C = 100 %
Vcc adjust: If activated the following settings are default:
Output voltage range: 0-10 V
Differencemode: activated
optris CS – E2010-12-A
5
Alarm level Alarm value (IN/ OUT pin) Vcc
1 40 °C 11 V
2 45 °C 12 V
3 50 °C 13 V
4 55 °C 14 V
5 60 °C 15 V
6 65 °C 16 V
7 70 °C 17 V
8 75 °C 18 V
9 80 °C 19 V
10 85 °C 20 V

optris CS – E2010-12-A
6
Technical Data
General Specifications
Environmental rating IP63
Ambient temperature -20...80 °C
Storage temperature -40...85 °C
Relative humidity 10...95 %, non condensing
Material stainless steel
Dimensions M12x1, 85 mm long
Weight 58g
Cable length 1 m (standard), 3 m, 8 m, 15 m
Cable diameter 4,3 mm
Vibration IEC 68-2-6: 3G, 11 – 200 Hz, any axis
Shock IEC 68-2-27: 50G, 11 ms, any axis

optris CS – E2010-12-A
7
Electrical Specifications
Usedpin Function
OUT IN/ OUT
x Analog 0-5 V1) or 0-10 V2)/ scalable
x Alarm output voltage adjustable; N/O or N/C
x Alarm 3-state alarm output (three voltage level for no alarm, pre-alarm, alarm)
x Alarm programmable open collector output [0-30 V DC/ 50 mA] 4)
x Temp. Code Temp. Code Output (open collector [0-30 V DC/ 50 mA] 4)
x Input programmable functions:
external emissivity adjustment
ambient temperature compensation
triggered signal output and peak hold function
x x Serial digital 3) uni- (burst mode) or bidirectional
Status LED green LED with programmable functions:
alarm indication (threshold independent from alarm outputs)
automatic aiming support
self diagnostics
temperature code indication
Vcc adjust mode 10 adjustable emissivity and alarm values by variation of supply voltage/
Service mode for analog output

Output impedances min. 10 kΩload impedance
Current draw 10 mA
Power supply 5...30 VDC
1) 0...4,6 V at supply voltage 5 VDC; also valid for alarm output
2) only at supply voltage ≥11 V
3) inverted RS232, TTL, 9,6 kBaud
4) 500 mA if the mV output is not used
white Power supply
yellow OUT Analog output/ TxD (5 V)/ Alarm output
green IN/ OUT Analog input/ RxD (5 V)/ Open collector output
brown GND Ground ()
black Shield
optris CS – E2010-12-A
8
Andere Handbücher für CS series
1
Inhaltsverzeichnis
Andere optris Zubehör Handbücher