Read carefully, study these instructions before beginnin 9 work
This boiler must be installed by a qualified contractor.
The boiler warranty can be voided if the boiler is not installed, maintained and serviced correctly.
Boiler can be installed at high altitude with no burner adjustments. LP equipped boilers must not be installed at
elevations above 7,000 feet.
The equipment must be installed in accordance with those installation requirements of the authority having
jurisdiction or, in the absence of such requirements, to the current edition of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.
Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
I_,! If_,T0(H:(.,'_"]I:] I! / li'd [H I d_'l; f'_1L_[_ :_
The following are the recommended minimum
accessibility clearances between boiler and adjacent wall
or other appliances.
1. 16" from right side or left side of boiler.
2. 15" from top of boiler.
3. 4" from front of boiler.
4. Provide clearance for annual inspection of vent pipe
and condensate connections.
[Igl ! [oll J=1;I 1:1DI "J:ili ;(o] I :l I hV_ll._lliC-r__
The following LP requirements from the Uniform
Mechanical Code, section 304.6, may be in effect in
your geographic area:
"Liquefied petroleum gas burning appliances shall
not be installed in a pit, basement or similar location
where heavier-than-air gas might collect. Appliances
so fueled shall not be installed in an above-grade
under-floor space or basement unless such location
is provided with an approved means for removal of
unburned gas."
Jill Ih_l.'lllf:lll/:_l/[O]L_l F.'lll;iVJ:li'
The design of this boiler is certified for closet installation
with the following clearances:
I. 0" from left side, right side, rear, top, bottom, front
and combustible construction.
2. O" from vent pipe and combustible construction.
3. This boiler is design certified for use on combustible
floors.
:11 I'J IL_ _IL_Ib_[€'l i /-"I= I I/;V.'o]ll
Do not install this boiler on carpeting. Boiler
installation on carpeting is a fire hazard.
Liquefied Petroleum (LP) is heavier than air and may
collect or "pool" in a low area in the event of a leak
from defective equipment. This gas may then ignite,
resulting in a fire or explosion.
For new and existing installations, a Water Installation
Survey is available from Peerless Heater Company. The
survey will provide information on how a hot water
boiler works with your specific system and will provide
an overview of hot water system operation in general.
You can also use this survey to locate system problems
which will have to be corrected. To obtain copies of the
Water Installation Survey, contact your Peerless
representative.
Prepare sketches and notes of the layout to minimize the
possibility of interferences with new or existing
equipment, piping, venting and wiring. Review
limitations on vent pipe, vent terminal, and air inlet pipe
locations in Section 5, Venting.
Boiler is certified as an indoor appliance. Do not
install boiler outdoors or locate where it will be
exposed to freezing temperatures.
2