12
DIP Modes and functions Option Effect
DIP1 OFF
DIP2 Advance warning
ON the flashing light comes on and the operation begins after a 3
second warning
OFF the flashing light comes on and the operation begins
immediately
DIP3 Opening mode
ON step-by-step opening (the gate halts if a key command is
activated during opening, and closes if activated again)
OFF collective opening (the control board does not obey the key
commands during opening)
DIP4 Automatic or step-by-step mode
(for pedestrian and total operation)
ON automatic mode (the gate closes automatically after standby
time has passed, which is adjusted using T.E.). A key command
(or photocell activation) causes standby time to restart
OFF step-by-step mode (the gate only closes when receiving the key
command)
DIP5 Automatic mode optional
(only if DIP4 = ON)
ON during standby, the gate obeys the key commands (can be
closed before standby time finishes)
OFF the gate cannot be closed until standby time finishes; a key
command will cause standby time to restart
DIP6 Gate movement
direction
ON gate which opens to the left
OFF gate which opens to the right
DIP7 Encoder ON encoder enabled
OFF encoder disabled
DIP8 Slowdown ON the gate reduces its speed before reaching the stopper
OFF the gate reaches the stopper at high speed
Function and mode selection using SW1 (DIP1 = OFF)
T.E (Standby Time): gate open standby time
If automatic functioning mode has been programmed
(DIP4=ON), set T.E. to adjust standby time with the gate
open (before automatic closing begins).
•Minimum value: 0 seconds; maximum value: 90
seconds
P.M (Torque Regulator): motor torque
Use P.M. to adjust the maximum motor power value.
‹Adjust the torque to respect the maximum closing
thrusts set out in Standard EN12453:2000. Make
the measurements as described in Standard EN
12445:2000.
Waiting
Time
POT2
P268M
Potentiometer adjustment